Abstract
Two water treatment plants (Edfina and Kom-Hamada) in El-Beheira Governorate were selected to monitor disinfection by-products (DBPs) concentrations. A 12-month monitoring program from October 2011 to September 2012 was established for measuring some DBPs and some water quality parameters such as temperature, pH, turbidity, total organic carbon (TOC), ammonia and bromide. The concentrations of DBPs were determined by gas chromatography with ECD (GC-ECD). Trihalomethanes (THMs) and chloral hydrate (CH) were commonly seen in all samples collected from Plant 1 (Edfina) and Plant 2 (Kom-Hamada). THMs mean concentrations ranged from 34.5 to 64.6 μg/L and from 28.2 to 52.8 μg/L for Plant 1 and Plant 2. CH mean concentrations ranged from 3.3 to 6.76 μg/L and from 2.8 to 3.9 μg/L for Plant 1 and Plant 2, respectively. Dichloroacetonitrile (DCAN) mean concentrations ranged from 1.1 to 2.0 μg/L and from 1.2 to 2.1 μg/L for Plant 1 and Plant 2, respectively. Chloropicrin (CP) was detected in Plant 1 only with mean concentration ranging from 0.91 to 1.1 μg/L. Trichloroacetonitrile (TCAN) and dibromoacetonitrile (DBAN) were below the limit of quantification (LOQ) in all samples. Higher concentrations of THMs were measured in summer and spring as compared to winter. DBPs concentrations were higher in Plant 1 than in Plant 2. The DBPs levels in all samples collected from Edfina and Kom-Hamada were generally below the guideline values set by the Egyptian Health Minister in 2007.
Similar content being viewed by others
Explore related subjects
Discover the latest articles, news and stories from top researchers in related subjects.Avoid common mistakes on your manuscript.
Introduction
Chlorine is currently the most reliable chemical disinfectant used for water disinfection. Chlorine is one of the most commonly used disinfectants in water treatment due to its low cost, easy operation and especially its high efficiency in killing pathogenic microorganisms, but has been reported to form disinfection by-products (DBPs) which are suspected to be human carcinogens (Woo et al. 2002; Hu et al. 2010).
THMs consist of several methane derivative compounds and the four chemical species, comprise chloroform (CF), bromodichloromethane (BDCM), dibromochloromethane (DBCM) and bromoform (BF). THMs were suspected to cause not only cancer but also liver and kidney damage, retarded fetus growth, birth defects and possibly miscarriage (Wright et al. 2004). The US Department of Health and Human Services has determined that chloroform may be anticipated to be a carcinogen. Also, it has been shown that dibromochloromethane and bromoform could damage the nervous system (USEPA 2001). Though the reported concentrations of halonitromethanes (HNMs) were much lower than THMs and HAAs and have not been regulated, cytotoxicity and genotoxicity posed by HNMs are comparable or even higher as compared to THMs and HAAs (Richardson et al. 2007). To minimize the risk of cancer, the United States Environmental Protection Agency (USEPA) and the World Health Organization (WHO) have introduced regulations for levels of some DBPs in drinking water. USEPA regulation for THMs concentrations was set at 80 μg/L (USEPA 2001). WHO has suggested a provisional guideline value of 20 μg/L for DCAN, while DBAN guideline value was set at 70 μg/L (WHO 2008). The MCL for THMs compounds in Egypt was set at 100 μg/L, while CH, TCAN, DCAN and DBAN were set at 10, 1, 20 and 70 μg/L, respectively (Ministry of Health, 2007).
THMs concentrations were investigated in Egypt. Hassan et al. (1996) determined the range of THMs in Alexandria city in Egypt. The detected range of THMs was 49.6–67.3 μg/L. Chloroform and dichlorobromomethane constitute the major fraction of THMs (36.86 and 35.14 %, respectively). Chlorodibromomethane was detected in lower concentration (25.09 %), while bromoform was found only in trace amounts (2.91 %). Geriesh et al. (2008) studied the concentration of the THMs in eight water treatment plants along Ismailia Canal. THMs concentration ranged from 52 to 112 μg/L. It is noticed that the concentrations of THMs are remarkably increased during winter season in all of the examined treatment units, which may be attributed to the flourishing of microbiological life during this low stage of the canal water and increasing of the effluent income to its course.
In Egypt, the main focus of the disinfection by-products is THMs. Only limited researches are conducted on other DBPs such as haloacetonitriles, haloketones, chloropicrin and chloral hydrate. The objective of this study was to monitor the levels of disinfection by-products (DBPs) and other water quality parameters such as pH, turbidity, alkalinity, TOC, bromide and ammonia in raw and treated water from a treatment plant in Beheira Governorate, Egypt and compared with the maximum contaminant level (MCL).
Materials and methods
Sampling
Sampling was conducted monthly between the 10th and 20th each sampling day from October 2011 to September 2012 from two selected treatment plants in Beheira Governorate, Egypt. These plants are Edfina plant (Plant 1) and Kom-Hamada plant (Plant 2). These treatment plants were selected to cover different points of surface water in Beheira Governorate. Chlorine disinfection and conventional treatment processes are used in both plants. Conventional treatment processes phases were prechlorination, flocculation, sedimentation, filtration and postchlorination. The prechlorination was applied in the coagulation channels and the postchlorination was applied before the entrance of water to finished water reservoir in the distribution system.
Monthly results expressed as an average for three replicates of samples. The sampling period was chosen to cover the seasonal variations during one year and all operational changes. Raw water samples were collected from the entrance of surface water to the plant, while the treated samples were collected from the finished treated water tank; 144 samples were performed during this study (2 samples for each plant (raw, finished samples) × 3 replicates × 2 plants × 12 months).
Samples were collected in 1 liter plastic bottle for measurement of water quality parameters such as pH, turbidity, alkalinity, ammonia and bromide; 60 mL amber glass vials were used to collect samples for DBPs analysis. Temperature, residual chlorine and pH were measured in the field immediately.
Analytical procedures
All measurements were carried out according to the Standard Methods for the Examination of Water and Waste Water (APHA, AWWA, WEF, 2005). All chemicals and reagents were purchased from HACH, Sigma-Aldrich, Chemlab, Merck, Scharlau and Panreac.
Temperature and pH were measured for surface and treated water using portable HACH multi-parameter. Residual chlorine was measured for treated water by photometric method (S.M. 4500-Cl G) (APHA, AWWA, WEF, 2005 using HACH colorimetric.
Turbidity was measured for surface and treated water using HACH 2100 N turbidity meter (S.M.2130B) (APHA, AWWA, WEF, 2005). Ammonia and bromide were determined by Dionex-600 ion chromatography equipped with electrochemical detector (ECD-50), isocratic pump (IP25) using instrument manual. Ammonia and bromide were determined for surface and treated water.
Analysis of total organic carbon (TOC)
TOC analysis was performed according to (S.M. 5310B) (APHA, AWWA, WEF, 2005) for raw and treated water samples. TOC was analyzed with TOC Analyzer (Tekmar–Dohrmann Apollo 9000). The samples were acidified to a pH less than 2 by phosphoric acid and then introduced into the instrument.
TOC removal calculated as follows:
Analysis of DBPs
Trihalomethanes (chloroform, bromodichloromethane, chlorodibromomethane, and bromoform), haloacetonitriles (HANs) (trichloroacetonitrile, dichloroacetonitrile, dibromoacetonitrile), chloropicrin, 1,1,1-trichloropropanone and chloral hydrate were analyzed as described in USEPA method 551.1 (USEPA Method 551.1, 1995).
1,000 μg\L individual stock standard solutions of DBPs compounds were diluted to perform a calibration curve. Phosphate buffer prepared from 1 % sodium phosphate dibasic (Na2HPO4)/99 % potassium phosphate monobasic (KH2PO4) used to lower the sample matrix pH to 4.8–5.5. Ammonium chloride (NH4Cl) was used as a dechlorinating agent. Methyl tert-butyl ether (MTBE) was used for extraction.
From the sample, 10 mL was removed. The pH was checked in this 10 mL aliquot to verify that it is within a pH range of 4.5 and 5.5. 3.0 mL of MTBE was added, and then 8 gm of sodium chloride was added to each vial containing the water samples. The sample was shaken vigorously for exactly 2 min. Water and solvent phases were allowed to separate approximately for 2 min. Then 1.5 mL of solvent phase was transferred to the 2 mL auto sampler vial.
An Agilent 7890A Gas Chromatograph with an electron capture detector (ECD) with DB-1.30 m × 0.25 mm × 1.00 μm capillary column was used for identification and quantification of DBPs. GC conditions, injection temperature was 220ºC. ECD temperature was 300 ºC. Column temperature program was 35ºC held for 9 min, then a 1 ºC per minute increase to 40 ºC which was maintained for 3 min, and finally a 6 ºC per minute increase until a temperature of 150ºC was reached, which was held for 1 min. The injection was splitless with a set time of 0.5 min. Flow was set at 24.8 cm/sec linear velocity at 150 ºC.
Method validation and uncertainty
The validation procedure including limit of quantification (LOQ), recovery (%R) and relative standard deviation (% RSD) based on EURACHEM Guide for method validation (EURACHEM Guide 1998). All results are shown in Table 1. The mean recovery ranged from 82 to 120 %. The mean RSD ranged from 4 to 9 %. From these accuracy and precision results, method uncertainty estimated based on EURACHEM for quantifying uncertainty (EURACHEM 2000).
Calibration and quality control
-
Before processing any samples, a blank sample was analyzed to demonstrate that all glassware and reagent interferences are under control. Prepared by adding buffer/dechlorinating agent mixture to reagent water, and then extract and analyze like samples.
-
A calibration curve was set at five calibration standard levels.
-
As a continuing calibration check, two calibration standards at different concentration levels analyzed at the beginning and the end of sample set.
-
Surrogate standard (decafluorobiphenyl) injected in each sample to measure extraction efficiency with accepted recovery up to 20 %.
Results and discussion
Water quality characteristics
Bromide was below LOQ (70 μg/L) in all samples. Water quality parameters of raw and treated water of Plant 1 and Plant 2 are summarized in Tables 2 and 3. Raw water pH ranged from 7.32 to 8.1 and from 7.5 to 8.25 for Plant 1 and Plant 2, respectively. For Plant 1, the maximum average value of pH (7.72) for raw water was found in winter, while minimum average value (7.5) was in spring. For Plant 2, the maximum average value (8.1) for raw water was reported in autumn, while minimum average value (7.53) was in spring. Treated water pH ranged from 6.83 to 7.4 and from 7.5 to 8.25 for Plant 1 and Plant 2, respectively. For Plant 1, the maximum average value (7.22) for treated water was reported in summer, while the minimum average value (7.0) was in spring. There was no definite variation between seasons. For Plant 2, the maximum average value (7.6) for treated water was reported in autumn, while the minimum average value (7.2) was in winter.
Raw water turbidity results ranged from 2.1 to 3.9 NTU and from 2.2 to 15.3 NTU for Plant 1 and Plant 2, respectively. For Plant 1, the maximum average value (3.71 NTU) was reported in spring, while the minimum average value (2.3 NTU) was in autumn. For Plant 2, the maximum average value (12 NTU) was reported in autumn, while the minimum average value (7.4 NTU) was in spring. All results of treated water turbidity were below 1 NTU.
Raw water alkalinity results ranged from 150 to 240 mg/L and 124 to 180 mg/L for Plant 1 and Plant 2, respectively. For Plant 1, the maximum average value (213 mg/L) was reported in winter, while the minimum average value (165 mg/L) was in spring. For Plant 2, the maximum average value (163 mg/L) was reported in autumn, while the minimum average value (132 mg/L) was in spring.
Free residual chlorine results in treated water ranged from 0.89 to 1.8 mg/L and from 1.3 to 1.7 mg/L for Plant 1 and Plant 2, respectively. For Plant 1, the maximum average value was 1.6 mg/L reported in winter, while the minimum average value was 1.2 mg/L reported in summer. For Plant 2, the maximum average value was 1.6 mg/L reported in autumn, while the minimum average value was 1.37 reported in summer.
The raw water TOC results ranged from 4.8 to 7.9 mg/L and 4.8 to 9 mg/L for Plant 1 and Plant 2, respectively. For Plant 1, the maximum average value (6.6 mg/L) was reported in winter. The minimum average value (5.3 mg/L) was reported in spring. For Plant 2, the maximum average value (8.5 mg/L) was reported in winter, while the minimum average value (5.6 mg/L) was in spring. These ranges of TOC are higher than the ranges reported by Geriesh et al. (2008). They reported a range between 2.4 and 5.3 mg/L in Ismailia Canal in Egypt. They noticed also that the maximum result reported in winter was due to the low stage level of the canal during this season (effluent conditions). The treated water TOC results ranged from 2.9 to 5.7 mg/L and from 3 to 6.3 mg/L for Plant 1 and Plant 2, respectively. Table 4 shows the minimum required removal percentage of TOC for conventional treatment assigned by USEPA for different water quality parameters. All results of percentages of TOC removal for Plant 1 and Plant 2 meet these criteria (Table 5).
Raw water ammonia (NH3) results ranged from 0.55 to 5.1mg/L and 0.3 to 0.45mg/L for Plant 1 and Plant 2, respectively. For Plant 1, the maximum average value (3.1mg/L) (Fig. 1) was reported in winter, while the minimum average value (0.6mg/L) was reported in summer. For Plant 2, it was detected only in autumn. These ranges are higher than the ranges reported by Othman et al. (2012) in Ismailia Canal in Egypt (0.07–1.49mg/L). It was not present in all treated water samples (Fig. 2).
Occurrence and speciation of DBPs
THMs were detected in all samples of Plant 1 and Plant 2. THMs concentrations ranged from 19.9 to 81.4 μg/L and from 18.5 to 59.5 μg/L for Plant 1 and Plant 2, respectively. The maximum average value for Plant 1 was 64.6 μg/L. It was reported in spring, while its minimum average value was 34.5 μg/L. It was reported in winter (Fig. 3). The maximum average value for Plant 2 was 52.8 μg/L. It was reported in summer, while the minimum average value was 28.2 μg/L. It was reported in winter (Fig. 3). The increase in THMs concentration in spring and summer is related to increase of temperature. This trend is in agreement with what is reported in many researches (Golfinopoulos and Nikolaou 2005; El Shehawy and Awad 2012). El Shehawy and Awad (2012) reported lower maximum value for THMs (61.4 μg/L) in Fayoum, Egypt. They reported that the highest THMs formation occurred in spring and summer while the lowest occurred in winter.
Chloroform was the most abundant THMs species followed by BDCM and BDCM which represent about 54, 33 and 13 %, in Plant 1, and 55, 32 and 13 %, in Plant 2, respectively (Figs. 4, 5). Bromoform concentrations were below the LOQ in all samples. The percentages of chloroform were lower than those of Ates et al. (2007). They reported that chloroform was found to be the major THMs compound (77.9 %), followed by BDCM (16.4 %), DBCM (4.9 %), and bromoform (0.9 %).
Other DBPs including halogenated acetonitriles (HANs), 1,1,1-trichloropropanone (TCP), chloral hydrate (CH) and chloropicrin (CP) were usually detected in treated water samples but at lower concentrations from THMs (Figs. 6, 7).
CH is the most abundant compound after THMs. CH was detected in all samples of the two plants. CH ranged from 1.2 to 8.2 μg/L and from 1.8 to 5.2 μg/L for Plant 1 and Plant 2, respectively. The maximum average result in Plant 1 was 6.76 μg/L, it was reported in summer. Its minimum average result was 3.3 μg/L, it was reported in autumn (Fig. 6). The maximum average result in Plant 2 was 3.9 μg/L, it was reported in spring. Its minimum average result was 2.8 μg/L, it was reported in winter (Fig. 7). These ranges are in agreement with results reported by Lebel et al. (1997) and Wei et al. (2010). CH/THMs ratios were calculated to compare CH to THMs. This ratio ranged from 6 to 16 % and from 3 to 10 % for Plant 1 and Plant 2, respectively (Fig. 8). The highest ratio was reported in winter while the lowest one was reported in summer. These ranges are in agreement with Koudjonou et al. (2008).
For HANs, TCAN and DBAN were below LOQ in all samples in Plant 1 and Plant 2. DCAN was found in 75 and 67 % from samples of Plant 1 and Plant 2, respectively. The concentration range was from ND to 2.5 μg/L and from ND to 2.4 μg/L for Plant 1 and Plant 2, respectively. These ranges are in agreement with those of Wei et al. (2010); they found the range was from ND to 3.43 μg/L.
TCP was detected in all water samples of Plant 1 and Plant 2. The results ranged from 1.5 to 2.4 μg/L and from 1.6 to 2.6 μg/L for Plant 1 and Plant 2, respectively. These values are in agreement with those of Wei et al. (2010) but are lower than the values found in Turkey by Baytak et al. (2008), which reached 7.81 μg/L.
CP was found in about 30 % of the total samples of Plant 1, while it was not present in all Plant 2 samples. Plant 1 results ranged from ND to 1.3 μg/L. These values are lower than values found in Beijing City, China, by Wei et al. (2010), which reached 2.08 μg/L. It is noticed that CP was detected only from January 2012 to April 2012 in which level of ammonia in raw water was higher than 1.5mg/L.
In comparison, Plant 1 has generally higher DBPs concentration than Plant 2. This is because Plant 1 has a larger reservoir than Plant 2 which means higher contact time leading to higher DBPs formation. Maximum average value of Plant 1 is higher than Plant 2 maximum average values. But about seasonal variation, THMs concentration increase in summer and spring, while they decrease in winter. The percentages of each compound in THMs value are very close in the two plants. Plant 1 results show higher CH concentration and CH/THMs ratio than Plant 2. In the two plants, CH/THMs ratios have the highest value in winter and the lowest value in summer. DCAN and TCP results of both plants are in agreement with each other. There is no observed seasonal variation for these compounds. CP was not found in plant 2 while found in 30 % of samples of plant 1 due to high level of ammonia in plant 1 raw water in winter season.
Correlation between DBPs and water quality parameters
The DBPs concentration and speciation are affected by many water quality parameters (TOC level, pH, bromide/nitrite, etc.) and operating conditions (disinfectant type, dosage, reaction time). For chlorination, formation of THMs and HNMs generally increases with the increase of chlorine dose, contact time and NOM level (Song et al. 2010).
The rates of formation of most DBPs increase with increasing temperature. Water temperature was strongly correlated with THMs, while lower correlation was observed with CH and DCAN. But there was negative correlation between water temperature and TCP. In general, the rate of THM production increases with pH. Formation of THM depends mainly on the last step of THM reaction pathway, which is base-catalyst as with the haloform reaction (Hong et al. 2007). A correlation (r = 0.23, 0.37, 0.29, 0.33, respectively) was obtained between THMs, DCAN, CH, TCP formation and pH. A moderate correlation was obtained between DBPs formation and chlorine dosage. While negative correlation was obtained with residue free chlorine.
The DBPs are formed when the disinfectant reacts with NOM. TOC is one of the most widely used measures for quantifying the amount of NOM in water. In general, greater DBP levels are formed in waters with higher concentrations of TOC (USEPA 2006). A low correlation was obtained between DBPs formation and TOC, and a low negative correlation with a TOC removal.
Conclusion
-
Samples of drinking water from the two plants, Edfina and Kom-Hamada, were analyzed for water quality parameters and Disinfection by-products (DBPs). The results indicated that the DBPs levels in all samples collected from October 2011 to September 2012 were generally below MCL set for these compounds in drinking water guidelines.
-
Plant 2 has a higher maximum average pH, TOC and turbidity than plant 1.
-
The maximum average TOC values were found in winter, while the minimum values were found in summer.
-
Higher DBPs results were detected in spring and summer, while the lowest results detected in winter.
-
Plant 1 show higher DBPs concentrations than plant 2 due to larger reservoir of plant 1.
-
Chloroform was the most abundant THMs species with a percentage up to 55 %.
-
CH/THMs ratios were ranged from ratio increase during winter and decrease in summer.
-
CP detected only in the presence of high level of ammonia in raw water.
References
APHA, AWWA and WEF (2005). Standard Methods for the Examination of Water and Waste Water. 21th ed. American Public Health Association, Washington, DC
Ates N, Kaplan SS, Sahinkaya E, Kitis M, Dilek FB, Yetis U (2007) Occurrence of disinfection by-products in low DOC surface water in Turkey. J Hazard Mater 142:526–534
Baytak D, Sofuoglu A, Inal F, Sofuoglu SC (2008) Seasonal variation in drinking water concentrations of disinfection by-products in IZMIR and associated human health risks. Sci Total Environ 407:286–296
El Shehawy R, Awad J (2012) Monitoring and modeling of fayoum distribution networks according to trihalomethanes formation. Civ Environ Res 2:59–68
EURACHEM (2000). CITAC guide number 4. Quantifying uncertainty in analytical measurement, 2nd edn. ISBN 0-948926-15-5
EURACHEM guide (1998). The fitness for purpose of analytical methods. A laboratory guide to method validation and related topics. ISBN 0-948926-12-0
Geriesh MH, Balke KD, EL-Rayes AE (2008) Problems of drinking water treatment along Ismailia Canal Province Egypt. J Zhejiang Univ Sci B 9:232–242
Golfinopoulos SK, Nikolaou AD (2005) Survey of disinfection by-products in drinking water in Athens, Greece. Desalination 176:13–24
Hassan AAM, Benfenati E, Fanelli R (1996) Detection and quantification of trihalomethanes in drinking water from Alexandria. Egypt Bull Environ Contam Toxicol 56:397–404
Hong HC, Liang Y, Han BP, Mazumder A, Wong MH (2007) Modeling of trihalomethane (THM) formation via chlorination of the water from Dongjiang River (source water for Hong Kong’s drinking water). Sci Total Environ 385:48–54
Hu J, Song H, Karanfil T (2010) Comparative analysis of halonitromethane and trihalomethane formation and speciation in drinking water: the effects of disinfectants, pH, bromide, and nitrite. Environ Sci Technol 44:794–799
Koudjonou B, LeBel GL, Dabeka L (2008) Formation of halogenated acetaldehydes, and occurrence in Canadian drinking water. Chemosphere 72:875–881
Lebel GL, Benoit FM, Williams DT (1997) A one-year survey of halogenated disinfection by-products in the distribution system of treatment plants using three different disinfection processes. Chemosphere 34:2301–2308
Ministry of Health (2007) Criteria for Potable Water. Egyptian Ministry of Health, Cairo
Othman AA, Rabeh SA, Fayez M, Monib M, Hegazi NA (2012) El-Salam canal is a potential project reusing the Nile Delta drainage water for Sinai desert agriculture: microbial and chemical water quality. J Adv Res 3:99–108
Richardson SD, Plewa MJ, Wagner ED, Schoeny R, Demarini DM (2007) Occurrence, genotoxicity, and carcinogenicity of regulated and emerging disinfection by-products in drinking water: a review and roadmap for research. Mutat Res 636:178–242
Song H, Addison JW, Hu J, Karanfil T (2010) Halonitromethanes formation in wastewater treatment plant effluents. Chemosphere 79:174–179
USEPA (1998). Disinfectants/disinfection by-products. Final rule. Federal Register, EPA, Washington, DC, 63(241):69390
USEPA (2001). National primary drinking water standards. United States Environmental Protection Agency, EPA 816-F-01-007
USEPA (2006). Initial distribution system evaluation guidance manual for the final stage 2 disinfectants and disinfection byproducts rule. EPA, Washington, DC, 815-B-06-002
USEPA method 551.1 (1995). Determination of chlorination disinfection by-products, chlorinated solvents, and halogenated pesticides/herbicides in drinking water by liquid–liquid extraction and gas chromatograph with electron-capture detection. Much, J.W., Hautman, D.P., Office of Research and Development, Washington, DC
Wei J, Ye B, Wang W, Yang L, Tao J, Hang Z (2010) Spatial and temporal evaluations of disinfection by-products in drinking water distribution systems in Beijing. China Sci Total Environ 408:4600–4606
WHO (2008). Guidelines for Drinking Water Quality. In: Recommendations, 3rd ed., vol. 1. World Health Organization, Geneva
Woo Y-T, Lai D, McLain JL, Manibusan MK, Dellarco V (2002) Use of mechanism-based structure–activity relationships analysis in carcinogenic potential ranking for drinking water disinfection by-products. Environ Health Perspect Suppl 110:75–87
Wright JM, Schwartz J, Dockery DW (2004) The effect of disinfection by-products and mutagenic activity on birth weight and gestational duration. Environ Health Perspect 112:920–925
Author information
Authors and Affiliations
Corresponding author
Rights and permissions
This article is published under license to BioMed Central Ltd. Open Access This article is distributed under the terms of the Creative Commons Attribution License which permits any use, distribution, and reproduction in any medium, provided the original author(s) and the source are credited.
About this article
Cite this article
Ibrahim, H.Z., Abu-Shanab, M.A. Monitoring of some disinfection by-products in drinking water treatment plants of El-Beheira Governorate, Egypt. Appl Water Sci 3, 733–740 (2013). https://doi.org/10.1007/s13201-013-0121-2