Abstract
Grid-integrated wind turbine may experience low voltages during transient events in grid. An increase observed in inrush current leads to low voltage. To control the increased current, an enhancement in a low voltage ride-through (LVRT) capability is required. This study examines the impact of an LVRT scheme on grid-integrated doubly fed induction generator (DFIG)-based wind turbines which are represented with new stator-damping resistor unit (SDRU) and rotor current control (RCC). Besides, both stator and rotor circuits of DFIG were enhanced with electro-motor force (emk). Designed as hybrid with SDRU and RCC, DFIG was examined to analyses symmetrical and asymmetrical faults in the grid. Electro-motor-force dynamic modeling of both stator and rotor was developed. The responses of wind turbine against low voltage are investigated in terms of bus voltages, angular speed, electrical torque, stator and rotor current, and d–q axes current. The results of the study show that the system became stable in a short time when the SDRU and RCC were incorporated with the stator and rotor electro-motor-force models.
Similar content being viewed by others
Avoid common mistakes on your manuscript.
1 Introduction
Due to increased application of integration of wind power in power systems, a need for some specific technical requirement emerges, with grid codes the most important technical requirement. As low voltage cases emerge due to faults, grid codes must operate within certain limits [1]. For operation within certain limits of system, low voltage ride through (LVRT) capability methods is used in different studies in the literature.
To control rotor current and rotor voltage in rotor-side and grid-side converters of doubly fed induction generator (DFIG) during symmetrical voltage dip, hybrid current control models, feed-forward, vector control, and transient current control have been enhanced. Thanks to these models, inrush currents which occur in DFIG are removed [2–5]. For grid-rotor-side converter units of the DFIG, voltage control strategy is enhanced. Thanks to this voltage control, converter protection provides coordinated control during transient events, such as faults and wind speed increase–decrease [6, 7]. The finite-element method is used for the LVRT method in DFIG. Owing to the reduction of simple circuit components, the finite-element method provides active crowbar protection as well as torque control of DFIG [8]. Enhanced using the positive-sequence component, new LVRT capability improves voltage and phase angle during varios voltage sag problems with low-high-pass filters and reference current tracking used in wind farm based on DFIG [9, 10]. Electro-motive force voltages in DFIG based wind turbines provide the controls of not only rotor-side converter, but also stator-side converter during the transient cases, as well. With compensation of electro-motive force voltages, over-stator current and over-rotor current are reduced during transient cases. In [11, 12], passive and active LVRT compensators are used to improve the LVRT capability during symmetrical and asymmetrical faults in DFIG. The passive compensator and active compensator reduce power oscillations and time response of parameters during faults owing to new crowbar units. Besides, using virtual resistance, a different control strategy is proposed to reduce exceeding rotor-circuit currents in [13, 14], which can provide reactive power to compensate for the latest grid code requirement in transient conditions. To develop LVRT capability in DFIG, a different approach called crowbar trip activation time is used. Using bypass resistor in this control method, converter units prevent various faults cases [15]. As a new control strategy against transient cases in DFIG based on wind farm, DC-link voltage control techniques are used. With the modification of grid-side converter unit of DFIG, DC-link voltage control is carried out both by compensating active power of the system and by regulating voltage fluctuations for LVRT capability [16, 17]. Dynamic voltage resistor (DVR) devices are one of the most commonly used devices among control strategy of DFIG for LVRT capability. Besides, owing to the positive and sequence component in DFIG for LVRT, grid-side converter (GSC) and rotor-side converter (RSC) are provided for the control of DFIG during fault conditions [18, 19]. Power oscillation damping (POD) is important for regulating voltage dip or the exceed currents in the DFIG during grid faults, Besides, POD has provided to power control. Therefore, different LVRT methods with POD to protect of the DFIG are developed [20–22]. Besides all control strategies of DFIG based wind farm during transient conditions, capability, flexible AC transmission system (FACTS) devices are used to enhance LVRT capability. Especially, static synchronous compensator (STATCOM) has provided to reactive-power control and voltage controls as well as angle control [23, 24].
In this study, a new LVRT capability method in DFIG is enhanced. Not only stator, but also rotor circuits were modelled as electro-motive force instead of stator and rotor flux equations for LVRT in the DFIG, as well. Besides, for stability of the DFIG, the SDRU and RCC were developed. A comparison was made with and without the SDRU and RCC in conditions variations, such as three–two faults. It was shown that the SDRU–RCC LVRT capability control yielded efficient results in this study.
2 Doubly fed induction generators (DFIG)
A crowbar unit, GSC and RSC are the components of DFIG based on wind turbine. The DFIG circuit model is given in Fig. 1.
It is essential that the grid-side converter regulates the DC-link voltage besides providing reactive power, while the rotor side is needed to regulate the real and reactive powers of the DFIG. A crowbar unit control regulates voltage-current limits. It is with d–q-axes equivalence circuits that voltage, current and flux calculations of the DFIG are facilitated [25–27]. Mathematical enhancement of DFIG is based on some assumptions. An arbitrary reference frame is used in determining DFIG equations, while calculations of the DFIG equations in power systems are facilitated with p.u. values. Voltage and linkage flux computations obtained in line with p.u. values in the DFIG are shown in Eqs. 1 and 4:
where \({v}_{{ds}}\), \({v}_{{qs}}\), \({v}_{{dr}}\), \({v}_{{qr}}\): d- and q-axes are the stator and rotor voltages; \(\lambda _{{ds}},\,\lambda _{{qs}},\lambda _{{dr}},\,\lambda _{{qr}}\): d- and q-axes are the stator- and rotor-magnetizing fluxes; \({e}_{{d}}\), \({e}_{{q}}\): d- and q-axes are the stator source voltages; and \({w}_{{s}}\): synchronous speed, s: slip, \({r}_{{s}}\), \({r}_{{r}}\) are the stator and rotor resistances.
In creating the electro-motor force in the full-order model (FOM), Eq. 5 is obtained with the incorporation of Eq. 4 into Eq. 2:
Equation 6 is obtained with the isolation of the stator d–q current in Eq. 3:
d–q axes’ current obtained is given in Eq. 7:
Equation 8 is obtained with the incorporation of Eqs. 5 and 6 into Eq. 4:
The rotor electro-motive-force in the FOM is given in Eq. 9.
In the DFIG reduced-order model (ROM), a electro-motive force and transient reactance are applied rather than stator flux derivations. Stator and rotor d–q voltages in the FOM in mathematical equation of the ROM are given in Eqs. 1 and 4. Simplified rotor d–q-axes currents are obtained in Eq. 10:
With the incorporation of the rotor, d–q axes’ currents in Eq. 5 into Eqs. 3 and 11 are obtained:
Equation 12 is obtained with the re-designation of Eq. 11:
While stator transient reactance is shown in Eq. 13, steady-state reactance is shown in 14:
Without considering the linkage flux derivation in Eq. 1, Eq. 15 is achieved according to the descriptions in Eqs. 7–10:
With the incorporation of Eq. 10 into Eq. 2, the derivation of the electro-motive force shown as \({e}_{d}\) and \(e_q\) is given in Eq. 16 [28–30]:
The transient open-time constant of ROM in the DFIG is given in Eq. 17:
The aim is to maintain dynamic control of GSC–RSC by creating an electro-motive force in the rotor axis apart from the electro-motive force created without considering stator flux derivations in the ROM [31]. The d–q axes stator voltage obtained without considering the stator axis linkage flux derivation in the ROM is given in Eq. 18:
With the incorporation of Eq. 4 demonstrated in the ROM into Eq. 2, Eq. 19 is achieved:
Simplified d–q-axes stator currents in Eq. 3 are given in Eq. 20:
The d–q-axes derivation of the stator flux is achieved in Eq. 21:
With the incorporation of Eqs. 20 and 21 into Eqs. 19, 22 is achieved:
Equation 23 is achieved through the simplification of Eq. 22:
The rotor electro-motive force of the ROM achieved without considering the stator resistance and d–q-axes stator voltage is given in Eq. 24:
Whereas the angular speed based on stator flux is stable under normal operating conditions of DFIG, changes can be observed in angular speed in transient case. On the other hand, a drop in output voltage of DFIG does not change the flux drastically according to the basic flux rule. Accordingly, the stator flux ratio of the drop in three-phase’s voltage produces dc-component. This component is considered to be an oscillator during the transfer in synchronous reference frame, and it is applied as stator time constant at the same time. The stator flux change during the voltage drop is given in Eq. 25:
Considering Eq. (25) and without considering stator resistance and flux, equivalent rotor source voltage can be defined as in the following equation. The first line of Eq. 25 points to the pre-transient condition, while the second line points to the stator flux after transient conditions. The stator flux is demonstrated in two parts; before and after the voltage drop. The rotor d–q axes are used in controlling these two parts. In Eq. 26, \((L_m /L_{ss} )s\lambda _{sdq0} ^{+}\) points to the control as in the first part, when the sliding rate of Rotor \(E_{dq} \) voltage in transient conditions is comparatively low. In the second part, converter circuit in the rotor side is protected from the overcurrent and long-term unstable condition through rotor:
where \(\lambda _{sdqo} ^{+}\) is the positive-sequence steady stator flux linkage, while \(\lambda _{sdq2} ^{+}\) and \(\lambda _{sdq2} ^{-}\) are the positive and negative sequence transient stator flux linkages, respectively, t is the time, and \(\sigma \) is the stator-damping coefficient, as shown in Eq. (27):
3 Enhancement of SDRU and RCC in DFIG based wind farm
Three-phase resistors, r1, r2, and r3, directly connected to stator windings of DFIG based wind farm are shown in Fig. 2 [32, 33].
Equation 28 shows how the line voltages, ab and ca, of the stator and the grid voltages relate to each other:
Equation (28) is obtained on the assumption that a neutral current can find no way to flow out to ensure that zero sequence component of the stator current is zero. Accordingly, (\({i}_{{sa}} + {i}_{{sb}})\) replaces the phase c current \({i}_{{sc}}\). Following matrix multiplications, (28) is changed into the stationary reference frame through \(\alpha \beta \) axes, as follows:
The first line of (30) points to the grid voltage vector equation in stationary reference frame, demonstrated by
A dc term is obtained through the positive sequence component in the positive synchronous reference frame, d–q axes positive rotating at the angular speed. This can also be seen in the negative sequence component in the negative synchronous reference frame, d–q axes negative rotating at the angular speed. By replacing the positive into negative sequence components of the grid and d–q axes stator voltage shown in (31), Eq. (32) is obtained with some alterations as follows:
The positive and negative sequence components of the grid voltage are described in Eqs. (31) and (32) as functions of d–q axes stator voltage.
Under normal conditions, the outer power control loops, also known as mainstream vector control, prove instrumental in achieving the d–q components of the rotor reference current. During fault conditions, the d–q components obtained in this way can be used to develop the LVRT capability. In this section, a solution is proposed to enhance the LVRT capability during unbalanced voltage dips with the application of the asymmetrical SDR and through a profound elaboration on how to choose the d–q components of the rotor reference current during the fault. In accordance with d–q axes stator flux equations, the stator positive/negative sequence current, in terms of stator flux and rotor current, is shown as
Transformation of (33) and (34) into (32) produces the negative sequence of the grid voltage in terms of rotor current, stator voltage, and flux:
In this way, the negative sequence components of the stator voltage and flux turn out to be zero, thereby eliminating unbalanced voltage fluctuation the stator voltage. It is important to note that \({v}_{sdq}\) and \(\lambda _{sdq} \) are inter-dependent during the unbalanced voltage dip. In the light of (35), it is plausible to select the positive and negative sequence components of the rotor reference current in the positive/negative synchronous reference frames as follows:
The assumption that rotor current control loop is fast enough gives rise to the possibility that the rotor current can be set to its reference value. Accordingly, with the rotor current during the unbalanced voltage dip chosen according to (34) and (35), it is possible to nullify the negative sequence component of the stator voltage and current, thereby balancing stator voltage. It must be emphasized that the positive components of rotor current are controlled in positive synchronous reference frame, while negative components of rotor current are controlled and in negative synchronous reference frame. Therefore, as given in Fig. 3, separate controllers must be used for positive and negative sequence components of the rotor current.
The positive d–q frame helps in controlling positive sequence rotor current with positive stator flux orientation, where the d positive axis is fixed to the positive stator flux with the rotation speed of \({w}_{b}\), with its phase angle with the \(\alpha \) axis measuring \(\theta _{\lambda s0} \). In d positive frame with positive stator flux orientation, the q positive axis rotor current is used for the real-power control as well as the reactive-power control, while in the d–q axes frame, used to control negative sequence rotor current, the angular speed of d negative axis rotation is \(-w_b\) with the phase angle \(-\theta _{\lambda s0} \) regarding the \(\alpha \) axis.
4 Simulation study
The transient behaviour of the wind turbine was investigated through the 2.3 MW wind power system, as given in Fig. 4.
The full-order DFIG based wind turbine model and the developed DFIG based wind turbine model with an SDRU and RCC are the two models that demonstrate the wind turbine generator, as can be seen in the previous section. A 2.6 MW, 0.69 kV Y/34.5 kV \(\Delta \) transformer was used in connecting the wind turbine to a 34.5 kV system [34]. The distance between the wind turbine and the 34.5 kV grid was 1 km. The transmission grid connection was made available through the 0.69 kV Y/34.5 kV \(\Delta \) transformers. 8 m/s was taken as the constant speed of wind. The saturation of the transformers was neglected. A 34.5 kV grid-side short-circuit power value was selected as 2500 MVA, while the X/R rate was selected as 7. As used in the DFIG-based wind farm, parameter values are given in Table 1.
5 Simulation results
A comparison was drawn for the effect of the SDRU and RCC upon the system parameters during transient cases. First, three fault was formed in the middle of the transmission line during a 0.55–0.6 s event. The observation for the DFIG with and without the SDRU and RCC was examined impacts on bus voltages and variation DFIG parameters. The comparisons drawn are shown from Fig. 5a–h.
Figure 4a, b shows that there was a increase in the peak values of the 34.5 kV bus voltage of test system and output voltage of DFIG, system stabilized within shorter time using the SDRU and RCC in LVRT. With and without SDRU and RCC use in LVRT, 34.5 kV bus voltage of test system was nearly 0.25 and 0.2 p.u., respectively. Moreover, there was a considerable decrease in oscillations in the angular speed, electrical torque, and d–q-axes stator currents with the use SDRU and RCC in LVRT. While DFIG, angular speed, electrical torque, and d–q-axes stator–rotor currents with SDRU and RCC were stabilized in nearly 1.5, 1.25, 3, and 3 s after three-phase fault, respectively, DFIG angular speed, electrical torque, and d–q-axes stator–rotor currents without SDRU and RCC were stabilized in nearly 7, 6.5, 6.5, and 6.5 s after three-phase fault in 34.5 kV bus, respectively.
Second, two faults were formed in the middle of the transmission line between 0.55 and 0.6 s. The observation for the DFIG with and without the SDRU and RCC was examined impacts on bus voltages and variation DFIG parameters, and comparisons are given from Fig. 6a–h.
When there was a two-phase fault, the bus voltage of 34.5 kV of test system values and the output voltage of DFIG were nearly 0.2 and 0.25 p.u. without and with an SDRU and RCC in the DFIG, respectively, with an increase in the latter. The SDRU and RCC use also reduced oscillations in some parameters, such as the DFIG angular speed, electrical torque, and d–q-axes stator current variations, as was the case in the three-phase fault. While DFIG, angular speed, electrical torque, and d–q-axes stator–rotor currents with SDRU and RCC were stabilized in nearly 1.5, 1.25, 1.25, and 1.25 s after three-phase fault, respectively, DFIG angular speed, electrical torque, and d–q-axes stator–rotor currents without SDRU and RCC were stabilized in nearly 3, 5, 5, and 5 s after three-phase fault in 34.5 kV bus, respectively.
6 Conclusions
This study throws light on the application of an SDRU and RCC for DFIG based wind turbine grid-connected. The comparison of the transient behaviors of the system with and without the SDRU and RCC in DFIG was based on voltage dip. A three-phase fault and two-phase fault were regarded as transient stability cases which are likely to lead to a low-voltage sag in the grid. Oscillation increased considerably in the three-phase fault DFIG parameters, but it was lower in the two-phase fault. The results showed that the output voltage of DFIG and 34.5 kV bus voltage of test system increased with the use of an SDRU and RCC in the both three and two faults. It was found in the analysis results that the observed oscillations after transient cases decreased within very short time using the SDRU and RCC in DFIG based wind turbine.
References
Tsili M, Papathanassiou S (2009) A review of grid code technical requirements for wind farms. IET Renew Power Gener 3:308–332
Tapia A, Tapia G, Ostolaza X, Sáenz JR (2003) Modelling and control of a wind turbine driven doubly fed induction generator. IEEE Trans Energy Convers 18:194–204
Rahimi M, Parniani M (2010) Grid-fault ride-through analysis and control of wind turbines with doubly fed induction generators. Electr Power Syst Res 80:184–196
Chondrogiannis S, Barnes M (2008) Stability of doubly-fed induction generator under stator voltage oriented vector control. IET Renew Power Gener 2(3):170–180
Jiaqi L, Wei Q, Ronald GH (2010) Feed-forward transient current control for lowvoltage ride-through enhancement of DFIG wind turbines. IEEE Trans Energy Convers 25(3):836–843
Hansen AD, Michalke G, Sørensen P, Lund T, Iov F (2007) Co-ordinated voltage control of DFIG wind turbines in uninterrupted operation during grid faults. Wind Energy 10:51–68
Mohsen R, Parniani M (2010) Coordinated control approaches for low voltage ridethrough enhancement in wind turbines with doubly fed induction generators. IEEE Trans Energy Convers 25(3):873–83
Seman S, Niiranen J, Arkkio A (2006) Ride-through analysis of doubly fed induction wind-power generator under unsymmetrical network disturbance. IEEE Trans Power Syst 21(4):1782–1789
Hu S, Lin X, Kang Y, Zou X (2010) An improved low-voltage ride through control strategy of doubly fed induction generator during grid faults. IEEE Trans Power Electron 26(12):3653–3665
Bellmnunt OG, Ferré AJ, Sumper A, Jané JB (2008) Ride-through control of a doubly fed induction generator under unbalanced voltage dips. IEEE Trans Energy Convers 23(4):1036–1045
Mohsen R, Parniani M (2010) Efficient control scheme of wind turbines with doubly fed induction generators for low voltage ride-through capability enhancement. IET Renew Power Gener 4(3):242–252
Döşoğlu MK (2016) Hybrid low voltage ride through enhancement for transient stability capability in wind farms. Int J Electr Power Energy Syst 78:655–662
Morrent J, de Haan SWH (2005) Ride-through of wind turbines with doubly-fed induction generator during a voltage dip. IEEE Trans Energy Convers 20(2):435–441
Yang L, Xu Z, Ostergaard J, Dong ZY, Wong KP (2011) Advanced control strategy of DFIG wind turbines for power system fault ride through. IEEE Trans Power Syst 27(2):713–722
Lopez J, Gubia E, Olea E, Ruiz J, Marroyo L (2009) Ride through of wind turbines with doubly fed induction generator under symmetrical voltage dips. IEEE Trans Ind Electron 56(10):4246–4254
Dai J, Xu D, Wu B, Zargari NR (2011) Unified DC-link current control for low-voltage ride-through in current-source-converter-based wind energy conversion systems. IEEE Trans Power Electron 1:288–297
Okedu KE, Muyeen SM, Takahashi R, Tamura J (2010) Wind farms fault ride through using DFIG with new protection scheme. IEEE Trans Sustain Energy 3:242–254
Ibrahim AO, Thanh Hai N, Dong-Choon L, SuChang K (2011) A fault ride-through technique of DFIG wind turbine systems using dynamic voltage restorers. IEEE Trans Energy Convers 26:871–882
Wessels C, Gebhardt F, Fuchs FW (2011) Fault ride-through of a DFIG wind turbine using a dynamic voltage restorer during symmetrical and asymmetrical grid faults. IEEE Trans Power Electr 26(3):807–815
Knüppel T, Nielsen JN, Jensen KH, Dixon A, Østergaard J (2013) Power oscillation damping capabilities of wind power plant with full converter wind turbines considering its distributed and modular characteristics. IET Renew Power Gener 7:431–442
Li H, Liu S, Ji H, Yang D, Yang C, Chen H, Chen Z (2014) Damping control strategies of inter-area low-frequency oscillation for DFIG-based wind farms integrated into a power System. Int J Electr Power Energy 61:279–287
Domínguez-García JL, Ugalde-Loo CE, Bianchi F, Gomis-Bellmunt O (2014) Input-output signal selection for damping of power system oscillations using wind power plants. Int J Electr Power Energy 58:75–84
Heydari-doostabad H, Khalghani MR, Khooban MH (2016) A novel control system design to improve LVRT capability of fixed speed wind turbines using STATCOM in presence of voltage fault. Int J Electr Power Energy 77:280–286
Ananth DVD, Kumar GN (2015) Fault ride-through enhancement using an enhanced field oriented control technique for converters of grid connected DFIG and STATCOM for different types of faults. ISA Trans 62:2–18
Holdsworth L, Wu XG, Ekanayake JB, Jenkins N (2003) Direct solution method for initializing doubly-fed induction wind turbines in power system dynamic models. Proc Inst Electr Eng Gener Transm Distrib 150:334–342
Krause PC, Oleg W, Scott DS (2002) Analysis of electric machinery and drive systems. IEEE press, Piscataway
Kundur P (1994) Power system stability and control. Tata McGraw-Hill Education, New York
Lei Y, Mullane A, Lightbody G, Yacamini R (2006) Modeling of the wind turbine with a doubly fed induction generator for grid integration studies. IEEE Trans Energy Convers 21:257–64
Ekanayake JB, Holdsworth L, Jenkins N (2003) Comparison of 5th order and 3rd order machine models for double fed induction generators (DFIG) wind turbines. Electr Power Syst Res 67:207–15
Guo W, Xiao L, Dai S (2012) Enhancing low-voltage ride-through capability and smoothing output power of DFIG with a superconducting fault-current limiter-magnetic energy storage system. IEEE Trans Energy Convers 27:277–95
Xu L, Wang Y (2007) Dynamic modeling and control of DFIG-based wind turbines under unbalanced network conditions. IEEE Trans Power Syst 22:314–23
Rahimi M, Parniani M (2010) Coordinated control approaches for low voltage ride-through enhancement in wind turbines with doubly fed induction generators. IEEE Trans Energy Convers 25:873–883
Rahimi M, Parniani M (2014) Low voltage ride-through capability improvement of DFIG-based wind turbines under unbalanced voltage dips. Int J Electr Power Energy Syst 60:82–95
García-Gracia M, Comech MP, Sallan J, Llombart A (2008) Modelling wind farms for grid disturbance studies. Renew Energy 33:2109–2121
Author information
Authors and Affiliations
Corresponding author
Rights and permissions
About this article
Cite this article
Döşoğlu, M.K. Enhancement of SDRU and RCC for low voltage ride through capability in DFIG based wind farm. Electr Eng 99, 673–683 (2017). https://doi.org/10.1007/s00202-016-0403-4
Received:
Accepted:
Published:
Issue Date:
DOI: https://doi.org/10.1007/s00202-016-0403-4