Economical operation on power system network has two objectives, one is active power regulation and another is reactive power dispatch. Both the objectives can be improved by introducing renewable sources to the system. Nowadays, renewable sources play an important role on the performance of interconnected power system. They not only minimize harmful green house gas emissions and dependency on fossil fuel but also reduce long-term generation cost of electric power. This article will also show the importance of renewable sources to minimize the active power losses in the system. An interconnected power system is modeled with the help of IEEE 14-bus and IEEE 30-bus test system and is analyzed with ORPD problem by using Jaya algorithm. Jaya algorithm is simple yet powerful optimization algorithm, which is based on the objective that the solution finding out from a problem should be the best solution and should avoid the worst solution. The main objective is to improve the performance of the power system by introducing renewable sources to the system along with controlling the reactive power flow and hence minimizing transmission losses and increasing reliability of the system. The ORPD equation has been formulated with considering the injection of renewable unit to the system, and the best solutions of controlled parameter value (i.e., generator bus voltage, tap changer of transformer, reactive power source) have been found out using Jaya algorithm without violating the equality constraints and inequality constraints. Hence, the best solution for minimizing active power losses has been evaluated. More emphasis is given in the generation of power using renewable energy along with conventional sources in order to reduce the generation cost and to preserve the non-replenishable sources for high demand period. There is an increasing penetration of renewable energy in the system. Thus, in this paper, the solar energy has been incorporated into the IEEE bus test system where the power output from photovoltaic (PV) arrays are integrated along with the existing thermal power to the generator bus in order to minimize the transmission line power loss in the system [1,2,3,4,5].

2 Problem Formulation

2.1 The ORPD Problem

The objective of the ORPD problem is minimization of active power loss, and it is solved by determining the optimal location of the control variables without the violation of any constraints. The objective function of the problem is expressed as follows [3]:

$${\text{Min}}\,P_{\text{loss}} = \sum\limits_{{k \in {\text{NL}}}} {g_{l} } (V_{a}^{2} + V_{b}^{2} {-}2V_{a} V_{b} \cos \delta_{ab} )$$
(1)

where Ploss is the total active power loss in the transmission lines, NL denotes number of transmission lines, gl depicts conductance of branch l, Va, Vb are magnitude of the bus voltages the ath and bth buses, respectively, and \(\delta_{ab}\) is the phase difference between these voltages. There are few equality constraints given below [6]:

$$P_{Ga} - P_{Da} {-}V_{a} \sum\limits_{b = 1}^{\text{NB}} {V_{b} [G_{ab} \cos \theta_{ab} + B_{ab} \sin \theta_{ab} ] = 0}$$
(2)
$$Q_{Ga} - Q_{Da} {-}V_{a} \sum\limits_{b = 1}^{\text{NB}} {V_{b} } [G_{ab} \sin \theta_{ab} + B_{ab} \cos \theta_{ab} ] = 0$$
(3)

where NB denotes the number of buses, PDa and QDa are the active and reactive load demands of bus a. PGa and QGa are the active and reactive powers generated at the ath bus, respectively. Gab and Bab are the conductance and susceptance the between ath and bth buses, respectively.

There are few inequality constraints given below [6]:

The inequality constraints of the independent variables are:

$$V_{Ga}^{\hbox{min} } \le V_{Ga} \le V_{Ga}^{\hbox{max} } ;\quad a = 1, \ldots ,N_{\text{GB}}$$
(4)
$$Q_{Ca}^{\hbox{min} } \le Q_{Ca} \le Q_{Ca}^{\hbox{max} } ;\quad a = 1, \ldots ,N_{\text{SC}}$$
(5)
$$T_{a}^{\hbox{min} } \le T_{a} \le T_{a}^{\hbox{max} } ;\quad a = 1, \ldots ,N_{\text{T}}$$
(6)

where VminGa and VmaxGa are the maximum and minimum generator voltages of the ath bus, respectively. QminCa and QmaxCa are the maximum and minimum reactive power injection of the ath shunt compensator, respectively, and Tmina, Tmaxa are the maximum and minimum tap settings of the ath transmission line, respectively. NGB is the total number of generator buses, NSC is the number of shunt compensators and NT is the number of tap-changing transformers. The inequality constraints of the dependent variables are:

$$V_{La}^{\hbox{min} } \le V_{Li} \le V_{Li}^{\hbox{max} } ;\quad i = 1, \ldots ,N_{\text{LB}}$$
(7)
$$Q_{Gi}^{\hbox{min} } \le Q_{Gi} \le Q_{Gi}^{\hbox{max} } ;\quad i = 1, \ldots ,N_{\text{C}}$$
(8)
$$S_{Li} \le S_{Li}^{\hbox{max} } ;\quad i = 1, \ldots ,{\text{NL}}$$
(9)

where VminLa and VmaxLa are the minimum and maximum voltages of the load bus a, respectively. QminGa and QmaxGa are the minimum and maximum reactive power generations of the ath generator bus, respectively. SmaxLa depicts the maximum apparent power flow in the ath line and NLB denotes the number of load buses.

2.2 Inclusion of PV Unit to the System

In this paper, the study is done by considering the PV unit to be situated at the generator buses and their active power outputs are added to the power output of the conventional generators situated at the generated buses of the standard systems. The power output of the solar PV arrays are determined by using the simplified method of estimating the output of the PV modules under different operating conditions.

2.3 Performance Prediction Model of PV Array

The factors that are mostly responsible for the performance of a PV array are the temperature of the PV module (T) and solar irradiance (E) of the area. The electrical characteristics which are important for the operation of PV array are open-circuit voltage (Voc), short-circuit current (Isc), the peak power output (Pmax) and fill factor (FF) [7].

$$I_{\text{sc}} = I_{{{\text{sc}}0}} \left( {\frac{E}{{E_{0} }}} \right)^{x}$$
(10)

where \(E_{0}\) is the solar irradiance and \(I_{{{\text{sc}}0}}\) is the short-circuit current of the PV module under \(E_{0}\). Isc is the short-circuit current of the PV module under the solar irradiance E. The nonlinear effects on the photocurrent are indicated by the exponential term \(x\). The open-circuit voltage \(V_{\text{oc}}\) under a given condition is given by

$$V_{\text{oc}} = \frac{{V_{{{\text{oc}}0}} }}{{1 + y\ln \frac{{E_{0} }}{E}}}\left( {\frac{{\tau_{0} }}{\tau }} \right)^{z}$$
(11)

where \(V_{{{\text{oc}}0}}\) is the open-circuit voltage of the PV module when exposed to normal solar irradiance at temperature \(\tau_{0}\), y is a coefficient of technology-specific of PV module technology which is dimensionless and z is used for considering all the nonlinear effects of voltage and temperature. Fill factor FF is dimensionless and it helps in measuring the deviation of the actual IV characteristic from the ideal one. The equation for calculating FF is given below:

$${\text{FF}} = {\text{FF}}_{0} \left( {1 - \frac{{R_{\text{s}} }}{{V_{\text{oc}} /I_{\text{sc}} }}} \right)$$
(12)

where \(R_{\text{s}}\) is the series resistance, \({\text{FF}}_{0}\) is the ideal fill factor of the PV module and \(v_{\text{oc}}\) is the normalized value of open-circuit voltage to the thermal voltage. \({\text{FF}}_{0}\) and \(v_{\text{oc}}\) are given by

$${\text{FF}}_{0} = \frac{{v_{\text{oc}} - \ln \left( {v_{\text{oc}} + 0.72} \right)}}{{1 + v_{\text{oc}} }}$$
(13)
$$v_{\text{oc}} = \frac{{V_{\text{oc}} }}{nK\tau /e}$$
(14)

where \(n\) is the ideality factor and it ranges between 1 and 2, e is the charge of an electron (1.6 × 10−19 C) and K is the Boltzmann constant (1.38 × 10−23 J/K). The maximum power output of the PV module is given by

$$P_{\hbox{max} } = {\text{FF}} \cdot V_{\text{oc}} \cdot I_{\text{sc}}$$
(15)

If there are NS number of series and NP number of parallel PV modules and \(P_{\text{M}}\) be the module power output, then the array power output is given by

$$P_{\text{A}} = N_{\text{P}} \cdot N_{\text{S}} \cdot P_{\text{M}}$$
(16)

2.4 Calculated Power Output of PV Array

The active power output from the PV array is calculated using the following parameters from Table 1 [7]. The location chosen in this problem is Srinagar, India, and data is taken from the year 2012 [8]. The calculated power output of the PV array is 348.35 kW.

Table 1 Values of the different parameters of PV array

In this paper, the model of each PV unit has been considered to have 10 modules in both series and parallel and generates around 348.35 kW of power. A total of 20 units can be combined to generate a power of 6.967 MW of power at a particular generator bus. Thus, this power from the PV system is combined to that of the power from the thermal generators at all the generator buses of the system.

3 Implementation of Jaya Algorithm

The Jaya algorithm is a metaheuristic algorithm developed by Rao [9] to solve the objective functions of stochastic optimization techniques. The objective of the algorithm is to proceed toward the best solution and keep avoiding the worst solution. The algorithm keeps on updating the values of the control variables wherever it obtains a better solution compared to the previous iteration. Let f(x) be an objective function which needs to be minimized. Let ‘v’ be the number of design variables (i.e., a = 1, 2, …, m) and i be a particular iteration for which the number of candidate solutions be ‘c’ (i.e., population size, b = 1, 2, …, c). Let f(x)best and f(x)worst be the best and worst solutions of the function f(x) and the candidates obtaining the best and worst solutions be recorded as the best and the worst candidates, respectively. Let value of the ath variable be Aa,b,i for the ath candidate in the ith iteration. The modified value is represented as:

$$A_{a,b,i }^{\prime } = A_{a,b,i} + r_{1} \left( {A_{{a,{\text{best}},i}} {-}\left| {A_{a,b,i} } \right|} \right){-}r_{2} (A_{{a,{\text{worst}},i}} {-}\left| {A_{a,b,i} } \right|)$$
(17)

where Aa,best,i is the best candidate value of the ath variable and Aa,worst,i is the worst value of the ath variable. Aa,b,i is the updated value of Aa,b,i and r1 and r2 are two random numbers in the range [0, 1].

3.1 Effectiveness of Jaya Algorithm

The Jaya algorithm has proved to be a superior algorithm over many metaheuristic algorithms in determining the optimal solution of the active power loss in the ORPD problem like PSO, DE, ABC and DE-ABC [10]. Here, the Jaya algorithm is used to determine the active power loss in the transmission lines by incorporating the solar energy into the system, and then, it is comparing with the results of those from the actual system without PV.

4 Simulation Results

The ORPD problem is solved using the Jaya algorithm for minimization of the objective function of active power loss. The algorithm is tested on IEEE 14-bus and IEEE 30-bus test system for two different cases for each system. In the first case, the active power output is considered to be delivered only from the conventional generators and then the real power losses are calculated for the ORPD problem using both PSO and Jaya algorithms. In the second case, the bus data of the systems are modified by adding the active power output from the PV blocks to the power output from the generators at the generator buses. Again, the real power losses are calculated for the ORPD problem using both PSO and Jaya algorithms, and the results are compared. The results for both cases applying the two algorithms are compared, and the results are given below.

4.1 IEEE 14-Bus Test System

There are 5 generators in IEEE 14-bus test system which are situated at buses 1, 2, 3, 6 and 8 where bus 1 is the slack bus and the others are the PV buses. It has 20 numbers of branches with 3 branches (4–7, 4–9 and 5–6) having tap-changing transformers connected to them. The initial active power loss of the transmission line of the network for the base case is 13.49 MW [11]. The load flow for the system is run by taking the line data and bus data from [12]. The case studies for the test system are as follows:

  • Case 1:

The number of control variables considered for this case is 10 and their details are listed below [13]:

  1. (a)

    5 numbers of generator voltages at the PV buses 1 (slack bus), 2, 3, 6 and 8. Their range is [0.9, 1.1] p.u.

  2. (b)

    3 numbers of tap-changing transformers connected in the lines between (4–7, 4–9 and 5–6). Their range is within [0.9, 1.1] p.u.

  3. (c)

    2 numbers of static VAR compensators (SVCs) situated at buses 9 and 14. Their range is [0, 0.18] p.u.

Here, the power from the PV unit is not included in the system.

  • Case 2:

In this case, the control variables and their limits were kept unchanged, only the active power output from PV system has been added to the generator bus data along with the power of the thermal generators. A total of 6.967 MW power is added to all the generator buses (1, 2, 3, 6 and 8) individually.

The ORPD problem has been solved for all the cases using both PSO and Jaya algorithms and their results along with the comparison of the convergence characteristics for both the cases are shown in Table 2 and Fig. 1, respectively.

Table 2 Comparative results of IEEE 14-bus test system
Fig. 1
figure 1

Convergence characteristics of PSO and Jaya algorithms for power loss for both the cases on the IEEE 14-bus test system

4.2 Effectiveness of PV on ORPD for Minimization of Active Power Loss and Voltage Deviation

The results obtained from Table 2 and Fig. 1 prove that the penetration of solar power has reduced the active power loss in the system largely, and specifically, the results from Jaya algorithm depict the superiority of the algorithm in determining the optimal solution over PSO. Since, the PV cannot deliver reactive power, but its contribution in active power in the lines helps in reducing the voltage deviation in the buses as shown in Fig. 2 and thus improves the voltage profile of the system. Thus, Jaya algorithm has the ability to successfully reduce the power loss as well as the voltage deviation in the buses to a greater extent compared to PSO.

Fig. 2
figure 2

Convergence characteristics of PSO and Jaya algorithms for voltage deviation for both the cases on the IEEE 14-bus test system

4.3 IEEE 30-Bus Test System

The standard IEEE 30-bus test system comprises of total of 6 generators that are situated at the buses 1, 2, 5, 8, 11 and 13 out of which bus 1 is the slack bus and the others are PV buses. There are 41 numbers of branches in which 4 numbers of adjustable transformers are connected in branches (6–9, 6–10, 4–12 and 28–27). The load flow for the system is run by taking the line data and bus data from [11]. Initially, transmission line active power loss is 17.8984 MW for the base case [11]. The two case studies for the test system are as follows:

  • Case 1:

The number of control variables considered in this particular case for the optimization problem is 12. The variables along with their limits are listed below [13]:

  1. (a)

    6 numbers of generator voltages at the PV buses 1 (slack bus), 2, 5, 8, 11, 13. Their range is [0.9, 1.1] p.u.

  2. (b)

    4 numbers of tap-changing transformers connected in the lines between (6–9, 6–10, 4–12 and 28–27). Their range is within [0.9, 1.1] p.u.

  3. (c)

    2 numbers of static VAR compensators (SVCs) situated at buses 10 and 24. Their ranges are [0, 0.2] p.u. and [0, 0.04] p.u., respectively.

Here, the power from the PV unit is not included in the system.

  • Case 2:

The control variables in this case has been kept unchanged along their limits. Here, only the active power output from the PV system is included along with the power of the thermal generators in the generator bus data. A total of 6.96 MW power is added to all the generator buses (1, 2, 5, 8, 11 and 13) individually. Both PSO and Jaya algorithms are used to solve the ORPD problem of minimization of active power losses of the transmission lines. The results along with the convergence characteristics compared for both the cases are shown in Table 3 and Fig. 2, respectively.

Table 3 Comparative results of IEEE 30-bus test system

The results obtained from Table 3 and Fig. 3 for the above-mentioned cases imply that the addition of power from the solar energy has helped in reducing the active power losses in the transmission lines to a great extent. Thus, the penetration of the solar energy in the system helps in getting a better result of the ORPD problem. Moreover, the convergence characteristics prove that Jaya is superior in determining the optimal solution to the problem and also minimizes the objective function largely compared to the other mentioned algorithm in the literature.

Fig. 3
figure 3

Convergence characteristics of PSO and Jaya for both the cases on the IEEE 30-bus test system

5 Conclusion

In this paper, the output from the PV system is added with that of the initial output from the conventional thermal generators of the respective standard systems. The results from the solutions of the ORPD problem from the case studies prove that the transmission line power loss is reported to be lower when the solar power is integrated to the system compared to that of the result when there is no intervention of solar power into the system. Thus, the penetration of additional renewable energy (solar energy in this paper) in the system helps in reducing the power loss in the transmission lines in the ORPD problem. On the other hand, the Jaya algorithm seems to have minimized the objective function largely compared to the other reported algorithm and thus is much more efficient, consistent and superior in determining the optimal solutions to the objective function. In other terms, it is a better choice compared to PSO in finding out the optimal values of control variables in the ORPD problem and thus optimizing the problem faster when tested on the different case studies for the standard IEEE 14- and 30-bus test systems.