1 Introduction

With the advancement of green buildings and promotion of new countryside construction, environment-friendly and energy-saving materials come to the spotlight. According to the recent statistics [1], plenty of expanded polystyrene (EPS) has a great negative impact on the ecological environment in the world. Moreover, comprehensive statistics above show that the output of desulfurization gypsum from power, heat and supply industries are approximately 66.437 million tons, of which more than 12 million tons are not comprehensively utilized. The industrial wasting gypsum not only occupies large amount of land resources, but also causes great harm to the natural environment through long-term accumulation. Therefore, it is necessary to broaden the utilization ways of solid waste desulfurization gypsum and EPS. Since the EPS has the characteristics of light bulk density, good crack resistance, excellent thermal insulation, low moisture absorption and good stability [2], it may be employed in building structures. In recent years, EPS [3, 4] has already been adopted as an ingredient in different building materials. Joseph [3] and Mousavi [4] employ the EPS as composing materials of concrete, which are, respectively, used in sandwich panels and super-lightweight shear walls. And the industrial waste flue gas desulfurization gypsum is also utilized in cement as building materials, such as Wu [5] and Zhang [6]. The researches indicated the two types of wasting materials would presumably be used as building materials in the future and the pollution caused by them would be significantly reduced.

Against the above background, a new type of light polymer material (LPM) is proposed in this study adopting EPS and desulfurization gypsum as main ingredients. Meanwhile, another type of LPM is prepared using EPS and cement as main ingredients. They are, respectively, defined as gypsum-based LPM and cement-based LPM for distinguish. Furthermore, the LPM exhibits lower density (less than 500 kg/m3), lower self-weight, better fire resistance, sound insulation characteristics and thermal insulating property (with the thermal conductivity less than 0.06 W/(m2 K)). Therefore, the LPM can make full use of the waste, protect the environment and satisfy the requirement of “green development” for construction industry. Additionally, the LPM can reduce the self-weight of structural components, and then decreases earthquake damages of the whole structures.

Due to the specific merits of LPM mentioned above, the LPM was applied as filling materials in the cold-formed steel (CFS) structures. Thus, a novel type of CFS structure using LPM-filled CFS shear wall (as shown in Fig. 1) was proposed. The application of LPM satisfied the needs of environmental-friendly and energy-saving performance for green buildings. Besides, the filled CFS shear wall can overcome the shortcomings, such as sound insulation performance and fire resistance, of conventional CFS shear walls. In addition, this novel composite wall has been used in low- and multi-rise residential and office buildings in Anhui province, China, as shown in Fig. 1. Until now, the previously published papers mainly investigated the performance of conventional CFS shear walls. The compressive behavior [7], cyclic behavior [8], fire performance [9], dynamic response [10] and design method [11] of CFS shear walls have been explored. Specially, Wang [12] conducted the cyclic test and numerical analytical assessment of CFS steel shear walls using tube truss. Apart from these abovementioned works, different types of filling materials are adopted in CFS shear walls to promote the performance. The material using in the CFS shear wall mainly include lightweight mortar [13], lightweight concrete [14], lightweight foamed concrete [15], high-strength lightweight foamed concrete [16] and lightweight flue gas desulfurization gypsum [17]. Nevertheless, available literatures concerning this type of LPM-filled CFS shear wall and the effect of LPM on the CFS shear wall can rarely be found.

Fig. 1
figure 1

Application of LPM-filled CFS wall in building

In this study, LPM was prepared by using suitable mixes and proportion. Material properties of gypsum-based and cement-based LPM including compressive strength, elastic modulus and thermal property were explored by tests. To explore the effect of LPM on CFS shear walls, a pure CFS framing wall without filling and two LPM-filled CFS shear walls were manufactured and tested under cyclic loading. The effect of LPM on the failure patterns, hysteretic behavior, mechanical behaviors and energy dissipation capacity was studied. Follow it, a modified equivalent bracing model is proposed to predict the lateral stiffness of shear wall in considering the filling material, wall panel and rib lath. Consequently, the results in this paper provide a reference to design and apply the novel LPM-filled CFS shear wall.

2 Light polymer material

2.1 Materials and mixture proportion

In this paper, light polymer materials are divided into gypsum-based and cement-based materials according to different cementitious materials. The fundamental properties of LPM are listed in Table 1. The gypsum-based LPM is produced incorporating the gypsum, retardants, expanded polystyrene (EPS), additives and water. Polystyrene beads with average diameter, bulk density and specific gravity of 6.5 mm, 16.6 kg/m3 and 0.016, respectively, were used as lightweight aggregate. In attempt to postpone fast setting time of the gypsum-based LPM, the retarders are added into the gypsum-based LPM. The gypsum retarder used in this paper was sodium polyphosphate.

Table 1 Mix proportion of LPM

The cement-based LPM is prepared using the cement, fly ash, expanded polystyrene, expansive agent, additives and water. Ordinary Portland cement and fly ash are employed as admixtures to improve the workability, enhance long-term strength and cut cost [18]. The using of expansive agent can improve the crack resistance of LPM notably. The expansive agent used in this paper was calcium sulfoaluminate. Additionally, the density and compressive strength of the LPM can be changed by varying the mixing amount of the light admixture.

The LPM specimens were cast to investigate the various performance parameters. Three cubes of 100 × 100 × 100 (mm), three prisms of 100 × 100 × 300 (mm) and three plate of 300 × 300 × 30 (mm) were casted for each type of LPMs. All specimens were kept at temperatures of 20 (± 5) °C and had the knockout time of 24 (± 2) h from completion of the pouring. Then, the specimens were kept in standard curing condition, which had the temperatures of 20 (± 2)  °C and the relative humidity more than 90%, until the day of testing. The compressive strength and elastic modulus of specimens were measured at 28 days in accordance with JGJ/T 70 [19]. The plate specimens were used to measure the thermal conductivity based on GB/T 10294 [20].

2.2 Properties of LPM knockout time of

2.2.1 Compressive strength

For each type of LPM (including gypsum-based and cement-based), three cubic specimens for compressive test are employed. The dry densities of gypsum-based and cement-based are, respectively, 449 kg/m3 and 456 kg/m3. Currently, there are no relevant regulations for LPM; so the test of LPM is conducted as per JG/T 266 [21]. The compressive strength of LPM is evaluated after 28 days at the loading rate of 0.1 kN/s. The photograph of test setup is shown in Fig. 2a. The measured average compressive strength of gypsum- and cement-based is 1.1 MPa and 2.1 MPa, respectively. The results demonstrated that the compressive strength of cement-based LPM is almost 1.9 times higher than that of gypsum-based LPM. In addition, the splitting tensile strength of LPM is calculated based on the empirical formulas showed by the previous experimental studies [22, 23], which present an obvious relationship between tensile and compressive strength.

Fig. 2
figure 2

Experimental photographs of LPM

2.2.2 Elastic modulus

For each type of LPM (including gypsum-based and cement-based), three prism specimens for compressive test are adopted. The elastic modulus of different LPM types is obtained by the method proposed in standards GB/T 50081 [24] and JG/T 266 [21]. The test photograph is shown in Fig. 2b, and stress–strain curve of each prism specimen is shown in Fig. 3. Based on the stress (σ)- strain (ε) curves, the elastic modulus of gypsum-based and cement-based LPM is obtained, the value of which are, respectively, 200 MPa and 250 MPa. Moreover, the stress–strain curves for gypsum-based and cement-based LPM are basically linear at the initial loading stage. After the linear stage, the curves of gypsum-based LPM growing slowly, while the curves of gypsum-based LPM exhibit a slight descent, which may be explained as the brittle failure for specimens. A small number of air voids in LPM caused by expansive agent can easily break and decrease the compressive strength.

Fig. 3
figure 3

Prism-compressive stress–strain curves and elastic modulus of LPM

2.2.3 Thermal property

For each type of LPM (including gypsum-based and cement-based), three plate specimens for each type of thermal conductivity are adopted, and the test photograph is shown in Fig. 2 (c). The thermal conductivity of gypsum-based and cement-based was 0.053 W/(m2.K) and 0.051 W/(m2.K), respectively, with corresponding standard deviations of 0.03 and 0.02. Compared with other light materials utilized in CFS shear walls such as foamed concrete [11, 25], the LPM appears better thermal properties. In accordance with the comparison, the gypsum-based and cement-based LPMs are suitable materials and can be applied as a structural bearing and insulation material in green building.

3 Methodology

3.1 Design of the specimens

In order to investigate the seismic response of LPM-filled CFS shear wall and the effect of LPM on the seismic performance of shear wall, three specimens were fabricated and designated by CFS1, LPM-CFS2 and LPM-CFS3. The specimen CFS1 without filling material was designed as a benchmark. The conventional filling materials mainly functioned as thermal insulation and appeared few effects on the mechanical behaviors of CFS shear wall. Thus, the conventional filling materials are usually neglected in the studies on the mechanical behaviors of CFS shear wall, such as Mohebbi [26] and Pan [27]. Gypsum-based LPM and cement-based LPM were, respectively, used in specimens LPM-CFS2 and LPM-CFS3. The two specimens were compared with specimen CFS1 to study whether this filling material could improve the performance of CFS framing.

The test specimens originated from a two-story building, as shown in Fig. 1. The detail information of all specimens is illustrated in Fig. 4. All specimens are rectangular with a height of 2755 mm and width of 3000 mm. According to specification JGJ 227 [28] and AISI S213 [29], each CFS framing consisted of interior studs, end studs, tracks and horizontal bracing. The wall studs were spaced at 600 mm on center. The CFS framings consist of identical C-section with dimension 89 mm × 41 mm × 11 mm × 0.9 mm, as shown in Fig. 4. To ensure the homogeneity of LPM density over wall specimens, the specimens were fabricated by spraying the LPM on a single-side panel instead of spraying the LPM into the shear wall from the top track with pre-punched holes. This way of pouring LPM can ensure the achieved densities of formed LPM in the range of ± 50 kg/m3.

Fig. 4
figure 4

Detail of specimen dimensions

In accordance with specification GB/T 15856 [30], CFS components were connected by ST4.8-grade (d = 4.8 mm) self-drilling screws to form CFS framing. Then, single-side wall panel were attached to the framing using ST4.8-grade self-drilling screws spaced at 150 mm and 300 mm. Following it, LPM was sprayed into the cavity of CFS framing as filling material. Finally, rib laths were attached to another side of framing, and the LPM was sprayed on the face of rib laths with a thickness of 25 mm. The whole of the rib lath and the 25-mm-thick LPM were jointly considered as the rib lath sheathing (as shown in Fig. 5) in this paper for convenience.

Fig. 5
figure 5

Configurations of rib lath sheathing

3.2 Material properties

The CFS framing components are fabricated from the galvanized steel sheets with a nominal yield strength of 550 MPa. The steel coupons are subjected to tensile tests to determine the mechanical properties. The material properties of the steel members are illustrated in Table 2. And the nominal yield strength of the rib laths is 345 MPa.

Table 2 Material properties of steel

The elastic modulus and static bending strength of the sheathings are obtained according to GB/T 17657 [31]. The results are listed in Table 3.

Table 3 Material properties of sheathing

3.3 Test setup and loading procedure

The test setup was arranged according to JGJ 227 [28], as presented in Fig. 6. The top and bottom tracks of the CFS framing were connected to the distributive girder and bottom foundation beam with six M16 × 190 mm bolts to facilitate the transfer of a horizontal shear load. The specimens were fastened to the top and bottom though four hold-downs in each wall corner (as shown in Fig. 7). The vertical loads were applied by a 500 kN, and the loads are transmitted uniformly to the specimen with a distributive girder. A 1000kN MTS hydraulic actuator with a displacement range of ± 250 mm was installed to impose the lateral cyclic loads to the specimens. In order to avoid out-plane deformation of the specimen, two constraint steel tubes were installed on the double side of specimens.

Fig. 6
figure 6

Test setup

Fig. 7
figure 7

Configurations of hold down

The vertical load imposed to the specimen is obtained by simulating the actual force condition, and the 80kN axial load was an average force in consideration of the dead loads and live loads on this wall. During the tests, the vertical loads remained constant. The lateral cyclic loads are applied to the distributive girder end according to the loading history. Generally, the displacement-controlled load is applied to all test specimens followed the ATC-24 [32], as depicted in Fig. 8. The loading is terminated after the load decreased to 85% of the peak loads or until failure.

Fig. 8
figure 8

Loading history

4 Experimental results

The influence of LPM on the failure modes and seismic response of CFS shear walls are discussed in this section.

4.1 Observed failure patterns

Figure 9(a) shows the failure modes of specimen CFS1, which indicated that unfilled CFS shear wall failed by local buckling of wall studs and the screw pull-over failure at the sheathing-to-stud connections. Owing to the increasing lateral displacement, the cracking and bulging of gypsum boards occurred and the both-side X-shaped bracings relaxed. In addition, the failure modes of specimen LPM-CFS2 also experienced a typical shear failure with local damage (see Fig. 9(b)). Bond-slip cracks between the LPM and wall studs occurred as the test continued. It should be stressed that the compressive failure caused by the cyclic loading occurred at the corners of the LPM. The relative slippage between the LPM and the wall studs improved the deformation capacity of the walls.

Fig. 9
figure 9

Typical failure modes of specimens

Comparison of the failure modes between specimens CFS1 and LPM-CFS2 showed that the specimen LPM-CFS2 failed with slight local buckling in interior studs, which indicated that LPM had an obvious effect on delaying the wall studs buckling of the CFS framing walls. It attributed to the restriction effect of LPM on the deformation of wall studs. Compared with the specimen CFS1 without filling material, slight bugling appeared on the gypsum board in specimen LPM-CFS1 because of the bonding between LPM and the gypsum board. The restriction effect improved with the compressive strength of LPM increasing. It resulted that no local bucking is observed at the interior studs of specimen LPM-CFS3 with cement-based LPM (Fig. 9(c)). Therefore, the LPM can apparently change the failure modes of CFS shear wall. Over all, in order to make full use of the performance of each component, appropriate failure patterns may be occurred from sheathing cracking to stud buckling to filling materials cracking.

4.2 Effect of LPM on hysteretic and envelop curves

The force–displacement hysteresis curves and envelop curves in Fig. 10 can obviously reflect the cyclic response of the test specimens. The test specimens reached the elastic–plastic stage rapidly after a short elastic stage, and the curves developed gradually from linearity to spindle shape. In addition, the curves displayed residual deformation after unloading. As the load increased, the curves became an arc shaped, accompanied by a certain level of pinching. Thus, the specimens entered the yield stage. When the hysteresis curves changed the shape to a reversed ‘S’ shape, the pinching level became distinct. As the loading reached the peak point, the curves again changed gradually from a reversed ‘S’ shape to a ‘Z’ shape, which resulted from the spalling of the wall sheathing, buckling of the wall studs and relative slippage between the CFS framing and LPM. And the pinching level became distinct with the further increase in displacement. Beyond the peak loads, significant strength and stiffness degradations occurred due to the buckling of wall studs and crushing of LPM and wall boards. The envelope curves of the test specimens exhibited no apparent yield point since the linear stage was relatively short and the obvious nonlinearity occurred early.

Fig. 10
figure 10

Load–displacement hysteretic behaviors of test specimens

Compared with specimen CFS1 without filling material, specimens LPM-CFS2 and LPM-CFS3 exhibited higher shear bearing capabilities and elastic stiffness. It indicated that the LPM resisted the deformation of the self-drilling screws and studs, and improved the bearing capacities of the studs. Besides, the curve of specimen sprayed with cement-based LPM declined slower than that of gypsum-based LPM specimen. It may be explained by the cement-based LPM appeared better ductility than gypsum-based LPM.

4.3 Effect of LPM on mechanical behavior

In this paper, the characteristic values were obtained in accordance with JGJ/T 101 [33], as illustrated in Fig. 11. The characteristic values of test specimens are given in Table 4. The test results exhibited that the peak load of CFS shear wall can be increased approximately 2.92–4.31 times by LPM. Compared with specimens LPM-CFS2 and LPM-CFS3, specimen CFS1 appeared a poor lateral bearing capacity owing to the buckling of the studs without the restrictive effect of the LPM. Additionally, the peak load of the specimen LPM-CFS3 with cement-based LPM was 28% higher than that of specimen LPM-CFS2. The initial stiffnesses of specimens LPM-CFS2 and LPM-CFS3 were, respectively, 2.12 and 3.09 times higher than that of specimen CFS1. This may be explained by the restriction effect of LPM and the certain stiffness of LPM on the CFS framing, which evidently increased the initial stiffness of LPM-filled CFS shear wall. The initial stiffness of the specimen LPM-CFS3 was 31% times higher than that of specimen LPM-CFS2. The results demonstrated that using LPM with higher compressive strength can improve load-bearing capacity and initial stiffness of the wall.

Fig. 11
figure 11

Definition of characteristic points

Table 4 Characteristic values on the load–displacement curves

4.4 Effect of LPM energy dissipation capacity

In this paper, the cumulative dissipated energies E were used to assess the energy dissipation capacity of test specimen, and the cumulative dissipated energies in each loading cycle are depicted in Fig. 12. The cumulative dissipated energy of specimens LPM-CFS2 and LPM-CFS3 were, respectively, 2.39 and 27.41 times higher than that of specimen CFS1 in the failure stage. It was benefited from the bond-slip performance between LPM and studs. Evidently, the energy dissipation capacity of specimen LPM-CFS3 was higher than that of specimen LPM-CFS2. This indicated that the bond-slip force between LPM and CFS framing is increased apparently, which can dissipate more seismic energy due to the increase in LPM compressive strength. Consequently, using LPM as filling material contributed to enhance the energy dissipation capacity of the shear walls and keep inelastic deformations before the collapse under earthquake force.

Fig. 12
figure 12

Cumulative dissipated energy E of test specimens

5 Calculation on lateral stiffness

The commonly used model for evaluating the late stiffness of CFS shear walls is the equivalent bracing model Ref. [34]. However, the available equivalent bracing model only took the wall studs, self-drilling screws and sheathings into consideration. Therefore, the simplified model is modified in this paper to consider the effect of X-shaped bracing, filling materials and rib lath (as depicted in Fig. 13 and Fig. 14). Assumptions for this model are as follows: (1) the CFS framing is supposed as bar elements that are connected with hinges, and the bases of the end studs are assumed as fixed ends in consideration of the hold-downs; (2) the wall panel is equivalent to a pair of crossed diagonal rods, which only bear the axial load; (3) the filling materials are equivalent to a pair of crossed diagonal rods among the adjacent two studs and horizontal bracing; (4) the rib lath is homogenized so it is assumed as a steel plate.

Fig. 13
figure 13

Modified equivalent bracing model of shear wall

Fig. 14
figure 14

Calculated substructure of LPM-filled CFS shear wall

Based on the abovementioned assumptions, structural mechanics theories and force-balance principles, the horizontal force in the top of shear wall can be expressed as Eq. (1):

$$P + Q_{\text{BA}} + Q_{\text{DC}} - 2\left( {n - 1} \right)N_{\text{BC}} \cos \alpha - \left( {2\sum\limits_{i = 0}^{2} {N_{\text{ri}} } + 2\sum\limits_{m = 0}^{2} {N_{\text{sm}} } } \right)\cos \beta = 0$$
(1)
$$Q_{\text{BA}} = Q_{\text{DC}} = - \frac{{3\Delta i_{1} }}{{\left( {H/2} \right)^{2} }}$$
(2)
$$\cos \alpha = \frac{l}{{\sqrt {l^{2} + H^{2} /4} }}$$
(3)
$$\cos \beta = \frac{{\left( {n - 1} \right)l}}{{\sqrt {\left( {n - 1} \right)^{2} l^{2} + H^{2} } }}$$
(4)

where QBA and QDC are the shearing forces of the end stud base; n is the number of wall stud; NBC is the compression of rod BC; α and β are depicted in Fig. 13; Nri is the axial force of diagonal rod, which is simplified from the i-side rib laths (i = 0,1,2); Nsm is the axial force of diagonal rod, which is simplified from the m-side wall panels; Δ is the lateral deformation of shear wall top; i1 is the linear stiffness of end stud.

In order to explore the effect of filling materials on lateral stiffness, a calculated substructure (as shown in Fig. 14) was extracted. The LPM of each calculated substructure is divided into two parts, which both have the shear deformation of Δ/2 under the top shear force P. Thus, the LPM is considered as a compressive rod BC and a tension road AD, and the two rods have identical absolute values of internal force. The NAD and NBC can be obtained by Eq. (5) according to deformation compatibility.

$$N_{\text{AD}} { = }N_{\text{BC}} = \frac{{\left( {\Delta /2} \right)lE_{\text{f}} A_{\text{f}} }}{{l^{2} + H^{2} /4}}$$
(5)

in which, Ef is the elastic modulus of LPM; Af is the cross-section area of equivalent compressive rod. The cross-section area Af could be obtained in accordance with Hwang [35,36,37], and the relevant formulas are expressed as:

$$A_{\text{f}} = a_{\text{w}} \times b_{\text{w}}$$
(6)
$$a_{\text{w}} = a_{\text{s}} = \left[ {0.25 + 0.85\frac{N}{{A_{\text{w}} f_{\text{c}}^{ '} }}} \right]L$$
(7)

where fc′ is the cylinder compressive strength; as is the horizontal length of the compression zone; aw is the uniform width of diagonal rod as a prismatic form; Aw is the cross-sectional area of the LPM.

Based on the abovementioned equivalent model, the wall panel can be assumed as two diagonal rods which have identical absolute values of internal force. The axial force Nsm can be calculated by Eq. (8).

$$N_{\text{sm}} = \frac{{\Delta \left( {n - 1} \right)lE_{\text{sm}} A_{\text{sm}} }}{{\left( {n - 1} \right)^{2} l^{2} + H^{2} }}$$
(8)
$$E_{\text{s}} A_{\text{s}} = \frac{1}{2} \cdot \frac{{\left[ {H^{2} + \left( {n - 1} \right)^{2} l^{2} } \right]^{1.5} }}{{\left( {HL/G_{\text{s}} t_{\text{s}} } \right) + \left( {2S_{0} /F_{\text{s}} n_{\text{s}} } \right)\left[ {H^{2} + \left( {n - 1} \right)lH} \right]}}$$
(9)

where EsmAsm is the axial rigidity of the diagonal rod, which was simplified by the m-side wall panels and obtained using Eq. (8) [33, 38]; Gs and ts are, respectively, the shear modulus and thickness of the wall panel; S0 is the deformation of the self-drilling screws connection; Fs is the strength of self-drilling screws connection; ns is the screw number along the vertical edge on one side of the wall. The formulas demonstrate that the self-drilling screws connections are the crucial influencing factor for the contribution provided by wall panels.

At the initial stage, the rib lath tentatively equivalent as a homogeneous steel plate, which can be assumed a wall panel of shear wall. Thus, the axial force Nri can be obtained using Eq. (10-11) referring the calculation of Nsm.

$$N_{\text{ri}} = \frac{{\Delta \left( {n - 1} \right)lE_{\text{ri}} A_{\text{ri}} }}{{\left( {n - 1} \right)^{2} l^{2} + H^{2} }}$$
(10)
$$E_{\text{r}} A_{\text{r}} = \frac{1}{2} \cdot \frac{{\left[ {H^{2} + \left( {n - 1} \right)^{2} l^{2} } \right]^{1.5} }}{{\left( {HL/G_{\text{r}} t_{\text{r}} } \right) + \left( {2S_{0} /F_{\text{r}} n_{\text{r}} } \right)\left[ {H^{2} + \left( {\text{n - 1}} \right)lH} \right]}}$$
(11)

where EriAri is the axial rigidity of the diagonal rod, which was simplified by the i-side rib lath. If the constructions of filling material, X-shaped bracing, rib lath and wall panel for lateral stiffness are considered, the calculation formula of lateral stiffness can be obtained by substituting Eq. (2-11) into Eq. (1), and the formula is expressed as Eq. (12):

$$\begin{aligned} K = \frac{P}{\Delta } = \frac{{24i_{1} }}{{H^{2} }} + \frac{{\left( {n - 1} \right)l^{2} E_{\text{f}} A_{\text{f}} }}{{\left( {l^{2} + H^{2} /4} \right)^{1.5} }} + \sum\limits_{i = 0}^{2} {\frac{{\left( {n - 1} \right)^{2} l^{2} }}{{\left( {HL/G_{\text{ri}} t_{\text{ri}} } \right) + \left( {2S_{0} /F_{\text{ri}} n_{\text{ri}} } \right)\left[ {H^{2} + \left( {\text{n - 1}} \right)lH} \right]}}} \hfill \\ \, + \sum\limits_{m = 0}^{2} {\frac{{\left( {n - 1} \right)^{2} l^{2} }}{{\left( {HL/G_{\text{sm}} t_{\text{sm}} } \right) + \left( {2S_{0} /F_{\text{sm}} n_{\text{sm}} } \right)\left[ {H^{2} + \left( {\text{n - 1}} \right)lH} \right]}}} \hfill \\ \end{aligned}$$
(12)

The results of the test lateral stiffness and those predicted based on the simplified model are compared in Table 5. The specimens from Ref. [14] and Ref. [15] are also adopted to verified the reliability of Eq. (12) It can be observed that the ratio of Kp to Kt is between 0.62 and 0.82 with the average ratio of 0.72 and the variation of 0.006, indicating that the proposed model can provide a conservative lateral stiffness which is safe in the design. Thus, the results indicated the modified equivalent bracing model can serve as a reliable and relatively conservative prediction method for the elastic lateral stiffness of LPM-filled CFS shear walls. It was notable that the predicted results were about 21% lower than the test results, which may be explained by the stiffness contribution of each component was calculated individually without fully considering the composite actions among the wall studs, sheathings and filling material. Moreover, further researches are still required to confirm the formula for LPM-filled CFS shear wall, because only two shear walls are experimented in this study.

Table 5 Comparison of lateral stiffness with tests and calculations

6 Conclusion

The following conclusions could be summarized based on the test and analytical results in this paper:

  1. (1)

    Two novel types of LPM were manufactured based on gypsum and cement, respectively. The measured compressive strength of gypsum- and cement-based were, respectively, 1.1 MPa and 2.1 MPa. And the thermal conductivities were all lower than 0.055 W/(m2.K). The results indicated that LPMs exhibited certain bearing capacities and significant thermal properties. Therefore, the gypsum-based and cement-based LPM might be suitable materials that could be adopted as structural load-bearing and insulation materials in green buildings.

  2. (2)

    The comparative analysis of specimen CFS1 and the other two specimens indicated the using of LPM could restrict the local buckling of wall studs and enhance the self-drilling screw connections. Regarding for the LPM-filled CFS shear walls, the dominant failure patterns were mainly the local buckling of the end studs, distortion of the interior studs, spalling of the gypsum board or cement fiberboard, titling of self-drilling screws and crushing of the LPM.

  3. (3)

    The experimental results confirmed that LPM can significantly improve the seismic responses of CFS framing walls in terms of bearing capacity, stiffness and energy dissipation capacity, which attributed to the bearing capacity of LPM, restriction effect of LPM on the CFS framing, and bond-slip behavior between LPM and CFS framing.

  4. (4)

    An equivalent bracing model was modified in this paper to assess the lateral stiffness of LPM-filled CFS shear walls. The proposed model considered the influences of filling material, rib lath and X-shaped bracing. The predicted results have been verified by experimental data in this paper and references. The results demonstrated that the proposed model can predict the lateral stiffness of the LPM-filled CFS shear walls approximatively and safely.