1 Introduction

Concrete hydration is an exothermic reaction that can produce high amounts of heat during curing, especially in the first few days after concreting. Temperature changes due to hydration heat will cause thermal cracks not only in mass concrete structures [1, 2], but also in relatively thin concrete slabs in bridges [3]. During the cooling phase at the end of hydration, contraction occurs in the concrete deck. These cracks develop due to the stud-caused constraint of steel girder on the contraction of concrete deck [4]. Generally, these cracks occur shortly after the concrete casting of deck slabs, even before opening to traffic. As such, not only the early-age performance of concretes but also the service life of composite girder bridges will be adversely affected [5, 6].

To avoid early cracking in concrete decks, effects of hydration should be estimated before concrete placement. In this regard, priority should be given to the temperature distribution of composite girder during hydration process. In situ measurements should be performed on large-scale segments or actual bridges to reflect the actual distribution of the hydration heat temperature of real bridges as much as possible. William et al. [7] instrumented a reinforced concrete deck on a three-span continuous steel girder to measure the temperature development and regressed the linear relationship between temperature changes and stress changes. Subramaniam [8] studied the variation of temperature rise in the concrete deck and steel girder by field test on a composite girder during hydration process. Choi et al. [9, 10] execute a model test on a simple-supported composite girder at a depth of 0.76 m and a length of 8.0 m to investigate the characteristic of temperature distribution in the concrete deck and steel girder. All these measurements suggested that the temperature distribution of composite girder was exactly uneven during hydration process. Also, obvious temperature differences were observed between steel and concrete. However, temperature measurements are often limited in number of measuring points, making it difficult to obtain a spatially continuous bridge temperature field, with which the thermal effect cannot be directly calculated. The most comment used method of fine calculation is the unidirectional thermo-mechanical coupling analysis, in which the temperature distribution is firstly calculated and a mechanical analysis is secondly performed. Faria et al. [11] and Huang et al. [12] calculated the thermal effect of a restrained concrete slab and a massive concrete pier during concrete hydration successfully by using this method, respectively. Other than that, Lee et al. [13] employed the microplane model of hydration heat and simulated the temperature field and the cracking patterns of concrete structures with early age. Zhang et al. [14] applied this method in the calculation of temperature and stress fields of a concrete pylon under solar radiation. The unidirectional thermo-mechanical coupling analysis is detailed but technically difficult, time-consuming and laborious, thus not convenient for direct applications in engineering.

In current specification system, such as AASHTO LRFD [15] and Eurocode 1 [16], the uniform temperature caused by air temperature changes and the temperature gradient caused by solar radiations in the bridge service stage are clearly specified. However, no applicative temperature patterns are available in current specifications for the thermal effect calculation of composite girders during hydration process, during which the concrete deck is more prone to cracking when the early-age concrete is inappropriately cured. When solar radiation acts on the top surface of bridges, temperatures are generally nonlinearly distributed within the top range of 0.3–0.5 m [17, 18]. Scholars have proposed several temperature gradient patterns, including polyline forms [15, 16], multiple parabolic forms [19,20,21,22,23,24,25] and exponential forms [22], for concrete, steel and composite girder bridges. Among them, Priestley [18] proposed a temperature gradient pattern with a 5th parabolic curve for concrete box girders. Li et al. [26] measured a deep concrete girder and proposed a third parabolic temperature gradient pattern. For steel girders, Tong et al. [27] established a similar temperature gradient pattern based on Priestley’s finding. Liu et al. [19, 28] established the 2nd–4th parabolic gradient patterns for composite girders. Additionally, in the calculation of solar-caused thermal effect, only the most unfavorable pattern needs to be concerned and the time-dependent characteristic is usually ignored [15, 16, 19, 21].

Influenced by hydration heat of composite girders, significant distinctions of thermal effect calculation exist between hydration stage and service stage [8,9,10, 22]. Firstly, the source position and form of internal hydration heat are totally different from solar heat source, causing quite different temperature distribution patterns. In addition, the time-dependent characteristic needs to be concerned in the thermal effect calculation during hydration process, because not only the mechanical properties of concrete but also the hydration temperature develops fast at the early age [23]. Therefore, the calculation of hydration heat-caused thermal effect is a spatio-temporal problem, and relevant conclusions of the solar-caused temperature actions and thermal effects are not exactly suitable for that.

This study focuses on developing a suitable spatio-temporal pattern of hydration heat temperature for the thermal effect calculation of composite girders. Figure 1 shows the flowchart of the methodology. Large-scale temperature measurements were firstly performed on an actual composite girder bridge, and the measured results were used for the verification of FEM method. Then, a comprehensive parametric study was carried out involving five basic parameters including final adiabatic temperature rise Tr,∞, initial temperature T0, curing temperature Tc, convective coefficient βt and deck thickness tc. After that, a spatio-temporal pattern was proposed in the form of the coefficient of temperature rise (CTR) by curve fitting. Through multiple regression analysis, parametric study results were used to establish a series of empirical formulae to predict the key coefficients in the pattern. Finally, by adopting the proposed pattern, a simplified method was presented to facilitate the thermal stress calculation of composite girders and cracking risk of concrete decks.

Fig. 1
figure 1

Flowchart of methodology

2 Hydration temperature field measurement

2.1 Tested composite girder

A field measurement was performed to investigate the temperature distribution of a composite girder bridge during hydration process. The bridge is situated at a mountainous area with an altitude of 491 meters, where the geographic coordinates are 108.51° E and 32.98° N. The composite girder with a span of 20 meters is grouped by a concrete deck lying on two longitudinal steel girders and three transverse steel beams. Figure 2 shows the layout of mid-span section. The height and width of the girder are 1.17 m and 3.70 m, respectively. The concrete deck has a general thickness of 0.19 m and a thickened part of 0.27 m. Reinforcement ratios of concrete deck in longitudinal and transverse are 0.85% and 2.54%, respectively. The two longitudinal steel girders have a same height of 0.90 m, and the spacing distance between each other is 2.0 m. Three I-shaped steel beams with a height of 0.25 m were evenly set on the webs of steel girders for cross connection. Shear connectors of 22 mm diameter were used in the interfacial region. C50 concrete was adopted for the concrete deck. Table 1 shows the mix proportion and corresponding thermal parameters of the C50 concrete. A type of P.O.52.5 Portland cement was used by 440 kg/m3, and the water–cement ratio is 0.35. In addition, polycarboxylate superplasticizer was used as water-reducing agent to improve the fluidity and workability of concrete, and type SY-HEA anti-cracking agent was employed to provide micro-expansion and fibers to prevent concrete cracking.

Fig. 2
figure 2

Layout of mid-span section (unit: mm)

Table 1 Mix proportion and thermal parameters of each component in C50 concrete

2.2 Sensor arrangement

For the accurate temperature measurement, 71 temperature sensors of DS18B20 digital thermometers were installed onthe composite girder. The section 0.5 m away from the mid-span section was selected as the experimental section to avoid the interference of cross-beam on sensor arrangement. Among the 71 temperature sensors, 47 of them were embedded into the concrete deck, while 24 of them were attached on the web surface of steel girder. Figure 3 shows the arrangements of these sensors. Additionally, environmental parameters, including air temperature, air humidity, wind speed, wind direction and solar radiation, were also recorded by a weather station nearby. The monitoring data from both the girder and external environment were obtained simultaneously at a time interval of 60 s. To reduce the jaggedness and increase the smoothness of the original collected data, the experimental data shown in the subsequent figures were all converted to hourly resolution.

Fig. 3
figure 3

Arrangement of temperature sensors (unit: cm)

2.3 Experimental program

Timber formworks were used for casting concrete. The concrete pouring, followed by an artificial vibration, was started at 1:30 p.m., and finished at 4:00 p.m. on December 27th. The concrete molding temperature was 13 °C, which could be considered as a uniform initial temperature of concrete deck. At one hour after casting, the top surface of concrete deck was covered by asbestos cloth for heat and moisture insulation. In addition, several hot water-heating boilers were set under the girder for continuous heat and moisture preservation. The asbestos cloth and wood formworks were both stripped at 48 h after concrete casting. The composite girder was supported by concrete blocks at 20–40 cm heights to allow natural ventilation for the bottom of steel girders. Experimental photographs are shown in Fig. 4.

Fig. 4
figure 4

Experimental photographs: a reinforcement assembly, b temperature sensors arrangement in concrete deck, c temperature sensors arrangement in steel girder, d mobile weather station, e concrete cast, f concrete curing with asbestos cloth and g constructed composite girder

2.4 Measured meteorological parameters

Figure 5 shows the variations of air condition within 72 h after concrete casting. The daily fluctuation of air temperature could reach a maximum range of 16.2 °C when the lowest temperature appeared at − 1.31 °C. In the contrast, curing temperature under the asbestos cloth held in a relatively stable range within 48 h after concrete casting. The curing temperature had an average value of 14.2 °C and a fluctuation value of 6.5 °C during the curing time with asbestos cloth. The air humidity had a maximum value of 70.15%. The flow of solar radiation into bridge deck was relatively small due to a rainy weather in the first two days, and the radiation increased to a maximum value of 1704 kJ/h m2 in the next two sunny days. There was not an obvious trend of wind speed during the hydration process, and the maximum wind speed was 3.3 m/s.

Fig. 5
figure 5

Meteorological parameters within 72 h during hydration: a air temperature and humidity, b solar radiation intensity and c wind speed

3 Finite element analysis

3.1 Heat transfer theory

3.1.1 Heat transfer equation

Concrete under the hydration reaction can be regarded as a continuous uniform medium with an internal heat source and a transient temperature field, which can be simulated with finite-element method. The general partial differential equation governing the heat conduction can be presented as [17]:

$$\rho c\frac{\partial T}{\partial t} = \lambda \left( {\frac{{\partial^{2} T}}{{\partial x^{ 2} }}{ + }\frac{{\partial^{2} T}}{{\partial y^{ 2} }}{ + }\frac{{\partial^{2} T}}{{\partial z^{ 2} }}} \right){ + }q\left( t \right)$$
(1)

where T is the temperature at the calculated point (°C); t is time, h; ρ is density (kg/m3); c is specific heat (kJ/kg °C); λ is thermal conductivity (kJ/m h °C); q(t) is the rate of hydration heat generated per unit volume (kJ/m3 h), which mainly depends on the cement type.

3.1.2 Hydration heat

During hydration reaction, the rate of exothermic hydration heat gradually slows down, and the accumulated hydration heat gradually increases to the final hydration heat, which is the end of hydration reaction. Based on the global kinetic law of reaction, a hydration heat model was present in research [24]. This model can take the initial temperature of concrete into consideration and thus has been used in the hydration heat temperature calculation of different concrete structures [24, 25]. The model is presented as

$$Q(t) = Q_{\infty } \exp \left\{ { - \omega \left[ {2\varphi \exp \left( {\zeta T_{0} } \right)\frac{t}{60}} \right]^{ - \xi } } \right\}$$
(2)

where Q(t) is the accumulated hydration heat (kJ/kg); Q is the final amount of accumulated hydration heat (kJ/kg); T0 is the initial temperature of concrete; t is the concrete age in minute; ω, φ, ξ and ζ are parameters.

Based on the above model, the rate of hydration heatcan be calculated by

$$q(t) = W\frac{{{\text{d}}Q}}{{{\text{d}}t}}$$
(3)

where W is the amount of cement per unit volume of concrete (kg/m3).

The final adiabatic temperature rise is completely converted from the heat generated by hydration reaction under an adiabatic condition, and it is related to the cement type and the concrete mix proportion [29]. It can be calculated by

$$T_{{{\text{r,}}\infty }} = \frac{{Q_{\infty } W}}{c\rho }$$
(4)

where Tr,∞ is the final adiabatic temperature rise (°C).

3.1.3 Boundary condition

The temperature difference between bridge surface and air environment results in heat loss or gain by a convective boundary condition, which is governed by Newton’s law of cooling [17] and can be expressed as

$$- \lambda \frac{\partial T}{\partial n} = \beta \left( {T_{\text{s}} - T_{\text{a}} } \right)$$
(5)

where Ts and Ta are the temperatures of bridge surface and air, respectively (°C); β is convective coefficient between the bridge surface and the surrounding air (kJ/m2 h °C). The β of smooth surfaces can be calculated with wind speed by [24]

$$\beta = 18.46 + 17.36v^{0.883}$$
(6)

where v is wind speed (m/s).

Formworks or insulation layers are often used for the shaping and curing of early-age concrete. The equivalent convective coefficient βe of the outer surface of formworks or insulation layers can be calculated by [29]

$$\beta_{\text{e}} = \frac{1}{{{1 \mathord{\left/ {\vphantom {1 {\beta_{0} }}} \right. \kern-0pt} {\beta_{0} }} + \sum {\left( {{{\delta_{i} } \mathord{\left/ {\vphantom {{\delta_{i} } {\lambda_{i} }}} \right. \kern-0pt} {\lambda_{i} }}} \right)} }}$$
(7)

where δi is the thickness of layer i (m); λi is the thermal conductivity of layer i (kJ/m h °C); β0 is the convective coefficient between the outermost insulation layer and the surrounding air (kJ/m2 h °C).

3.2 Finite-element model (FEM) development

3.2.1 FEM

Finite-element program ABAQUS 6.14 was used for the 3D heat transfer simulation of composite girder during hydration process. Figure 6 shows the FEM, in which all the components were meshed with the structured technique provided in ABAQUS. An 8-node linear heat transfer brick element, DC3D8, with a shape of hexahedron was employed for the simulation of concrete deck. A 4-node linear heat transfer shell element, DS4, with a shape of quadrangle was employed for the simulation of steel girder. The size of all the elements was set around 50 cm; as such, the node positions in the depth of concrete deck and steel girder can match the experimental arrangement of temperature sensors. The interfacial relationship between deck and steel girder was approximately modeled as “tie constraints,” so that the temperature and heat flux are continuous at the interface [21]. The thermal properties of concrete and steel are listed in Table 2. The density, conductivity and specific heat of concrete were valued as the average of each component with weights of the mix proportion in Table 1. The thermal properties of steel were referred to existing researches [19, 21, 28].

Fig. 6
figure 6

3D FEM of composite girder

Table 2 Thermal properties of concrete and steel

3.2.2 Hydration heat

A type of P.O.52.5 Portland cement was used in the deck of the test composite girder, and the corresponding final amount of accumulated hydration heat is 350 kJ/kg [29]. The rate of hydration heat was calculated with Eqs. (2) and (3), in which the coefficients ω, φ, ζ and ξ were taken as 55, 0.481, 0.039 and 1.25 [24]. Figure 7 shows the development of hydration heat. The maximum rate of hydration heat reached 5.91 × 103 kJ/m3 h.

Fig. 7
figure 7

Development of concrete hydration heat

3.2.3 Initial temperature and boundary conditions

In the FEM, the hydration temperature field was calculated every half hour for more accurate and detailed simulation results. The initial temperature was determined by the measured temperature, 13 °C for concrete deck, and 12 °C, 10 °C and 9 °C for the top flange, web and bottom flange, respectively. Temperatures of cross-beams were considered to be same as the web temperature.

The tested composite girder was located in a sulci form terrain. Blocked by concrete deck and the terrain, steel girders were not exposed to sunrays during the test period. Thus, the effect of solar radiation on the top surface of concrete deck was only taken into consideration. The recorded solar radiation intensity, as shown in Fig. 5b, was inputted in the FEM, and the solar absorptivity was taken as 0.4 for ordinary concrete surface [30] and 0.3 for white asbestos cloth [31].

The wind speed is not considered during the period when the composite girder was covered by the asbestos cloth at the first 48 h. The thermal conductivity and thickness of timber formworks are 0.837 kJ/m h °C and 1.5 cm, respectively. Then, it can be calculated with Eq. (7) that the equivalent convective coefficient of timber formworks is 13.871 kJ/m2 h °C. After the asbestos cloth and formworks was stripped, the convective coefficient was calculated with Eq. (6) by taking the wind speed into account.

4 Temperature results analysis

4.1 Temperature evolutions

Figure 8 shows the FEM and experimental temperature evolutions. Well agreements were shown between FEM and experimental results. Only the experimental web temperatures in S7 and S19 are relatively larger than FEM results because of the aforementioned heating boilers, which were not considered in the FEM. It can be also seen that temperature evolutions on the left and right sides are basically consistent. Concrete temperatures elevate significantly faster than the steel girder. Taking the left side as an example, at about 27 h, the center temperature in concrete deck reaches the first peak, 31.2 °C. At about 42 h to 44 h, the concrete temperature drops to the first valley, 27.3 °C. Subsequently, heated by solar radiation, the concrete temperatures elevate to another slight peak, 27.8 °C, at about 47 h. For steel girder, the heat flow is transmitted from the concrete deck and dissipated by air convection. The top flange is in contact with the concrete deck, and the temperature varies in similar trend with the concrete deck, whereas, with much slower elevation rate. The first measured peak of the top flange is 27.8 °C. The bottom flange is farthest away from the concrete deck. Thus, the temperature is mainly affected by and consistent with the variation of the curing temperature instead of hydration heat.

Fig. 8
figure 8

Temperature evolution of composite girder during hydration process: a left side and b right side

4.2 Temperature field contours

From the peaks and valleys in Fig. 8, the temperature evolution can be divided into the following four phases:

  • Phase I: the warming phase by hydration heat, during about 0–27 h.

  • Phase II: the first cooling phase, during about 27–43 h.

  • Phase III: the warming phase by solar radiation, during about 43–47 h.

  • Phase IV: the second cooling phase, after 47 h.

Figure 9 shows the comparison of experimental and FEM temperature field contours in typical times. These experimental contours were obtained by interpolating the measured temperature data through the Delaunay triangulation algorithm and calculating the weight of each temperature data with Thiessen polygons [22]. The comparison further suggests the accuracy of the FEM. In addition, these contours show that the temperature distribution is relatively uniform in the transverse direction of concrete deck, while large temperature difference exists in the vertical direction of composite girder.

Fig. 9
figure 9

Temperature field contours: a experimental results and b FEM results

4.3 Vertical temperature distribution

Figure 10 shows the experimental and FEM vertical temperature distributions of composite girder. The effect that the aforementioned hot water-heating boilers made the experimental web temperatures higher than the FEM results was also presented in the figures. Overall, temperatures of concrete deck were significantly higher and more uniformly distributed than the steel girder due to the effect of hydration heat. In Phase I and Phase II, hydration heat made the temperature at the center of the bridge deck the highest and gradually decreasing in both sides. While in phase III and phase IV, the effect of solar radiation gradually emerged, causing the temperature at the top of concrete deck to be highest and gradually decreasing downward. Temperatures of steel girders were the highest at the top flange contacted with concrete deck and gradually decreased to the lowest at the bottom flange, which is farthest from the heat source.

Fig. 10
figure 10

Vertical temperature distribution of the composite girder: a left side and b right side

Figure 11 shows the experimental and FEM vertical temperature difference (VTD) of composite girder and concrete deck. Well agreements are also shown between experimental and FEM results. Experimental results suggest that VTD of the composite girder varied slowly within about 5 °C in the first five hours and then rapidly increased to the peak of 18.28 °C at 16 h. Subsequently, the VTD decreased gradually, increased slightly due to solar radiation and finally decreased again. The VTD of concrete deck varied similarly to the composite girder, but consistently within 4 °C, much less than the VTD of the composite girder, throughout the hydration process.

Fig. 11
figure 11

Evolutions of the vertical temperature difference

Hydration heat, solar radiation and air convection are the main factors affecting the temperature distribution of the composite girder during the hydration process. With FEM, the effects of above three factors on temperature change in the four phases were quantitatively analyzed, as shown in Fig. 12. In Phase I, the ratio of the effects of hydration heat, solar radiation and air convection on the temperature change of concrete deck is 32.0:1:− 15.5, indicating that the composite girder was mainly warmed by concrete hydration heat and relatively cooled by air convection. In phase II, the effect ratio changes to 10.2:1:− 14.8. The cooling effect of air convection gradually exceeds the warming effect of hydration heat. In phase III, the effect ratio turns into 0.8:1:− 1.5. The effect of solar radiation becomes larger than the hydration heat. However, the temperature change in this phase is very small. In phase IV, the effect ratio becomes 5.4:1:− 14.9. The effect of air convection dominates the temperature decreasing of the composite girder, especially the steel girder. Overall, it is hydration heat and air convection that dominate the temperature change of composite girder, while the influence of solar radiation can be basically ignored.

Fig. 12
figure 12

Vertical distribution of temperature changes in: a phases I, b phase II, c phase III, and b phase IV

5 Parametric study

5.1 Parameters

The verified FEM can be used to perform a parametric study to investigate the influence of various parameters on the temperature distribution. A2D FEM, which was simplified from and proved to have the same accuracy as the verified 3D FEM, was used in the parametric study for an efficient calculation. A 4-node linear heat transfer element, DC2D4, with a shape of quadrangle was employed for the simulation of concrete deck and steel girder in 2D FEM. The element size was controlled same with the 3D FEM. The following five basic parameters are involved:

  • Final adiabatic temperature rise of concreteTr,∞ The accumulated hydration heat Q of ordinary cement ranges from 250 to 370 kJ/kg [29], and the amount of cement W commonly used for concrete deck ranges from 350 to 500 kg/m3 [32]. Therefore, the practical engineering range of Tr,∞ is set about 40 to 85 °C according toEq. (4).

  • Initial temperatureT0“Code for construction of concrete structures” GB 506666-2011 [32] stipulates that the molding temperature of concrete should not be higher than 35 °C and lower than 5 °C. Thus, T0 is set as 5–35 °C.

  • Curing temperatureTc In terms of T0, the parametric range of Tc is also set as 5–35 °C.

  • Convective coefficient of the top surface of concrete deckβtβt reflects the curing condition of the top surface of concrete deck. For a bare surface and a curing condition of 1.5 cm plastic foam + 3 cm straw, βt equals to 18.5 kJ/m2 h °C and 4.4 kJ/m2 h °C, respectively. Thus, the parametric range of βt is set as 5–20 kJ/m2 h °C.

  • Thickness of concrete decktc For short and medium span composite girder bridges, tc commonly ranges from 0.2 to 0.5 m [33].

The above five basic parameters are considered to be the main factors determining the hydration process of concrete deck. These parametric ranges are all set according to practical applications, and the specific values assigned to each parameter are listed in Table 3. For conditions of natural or covering curing, the difference between Tc and T0 generally does not exceed 10 °C, which can reduce some parameter combinations. As such, the total number of models is reduced to 640. Additionally, in the 2DFEM, Tc is simplified as a constant that does not vary with time. Although it is different from the actual curing condition, this simplification here is to realize a large-scale parametric study.

Table 3 Parameters for parametric study

5.2 Coefficient of temperature rise (CTR)

In the parametric study, a non-dimensional parameter of the coefficient of temperature rise (CTR) was defined as the ratio of actual temperature rise (T − T0) to the final adiabatic temperature rise Tr,∞ and can be calculated by

$$\gamma = \frac{{T - T_{0} }}{{T_{{{\text{r}},\infty }} }}$$
(8)

where γ is the CTR, which can reflect the actual temperature evolution of concrete deck in an actual engineering curing condition rather than adiabatic condition. In the subsequent results of parametric study, effects of parameters on the maximum CTR of concrete deck γc,max and the corresponding occurring time t0 were discussed.

5.3 Results and discussion

5.3.1 Effects of Tr,∞

Figure 13 shows the effects of Tr,∞ on γc,max and t0 for the parametric case T0 = 15 °C, Tc = 25 °C, βt = 10 kJ/m2 h °C and tc = 0.3 m. Results indicate that the increase of Tr,∞ values leads to decreasing trends of γc,max, which means that the higher the adiabatic temperature rise, the less thorough the hydration heat development of concrete under actual engineering conditions. For t0, a similar effect trend was also observed.

Fig. 13
figure 13

Effects of Tr,∞ on γc,max and t0 for the parametric case T0 = 15 °C, Tc = 25 °C, βt = 10 kJ/m2 h °C and tc = 0.3 m

5.3.2 Effects of T0

Figure 14 depicts the effects of T0 on γc,max and t0 for the parametric case Tr,∞ = 70 °C, Tc = 25 °C, βt = 10 kJ/m2 h °C and tc = 0.3 m. Not only γc,max but also t0 were observed to decrease with the increase of T0. When T0 is less than Tc, part of the contribution of temperature rise comes from air convection. On the contrary, when T0 is greater than Tc, the temperature drop generated by air convection will neutralize some of the temperature rise, thus lowering the hydration heat temperature rise. In addition, the influence of T0 on t0 is nearly linear.

Fig. 14
figure 14

Effects of T0 on γc,max and t0 for the parametric case Tr,∞ = 70 °C, Tc = 25 °C, βt = 10 kJ/m2 h °C and tc = 0.3 m

5.3.3 Effects of Tc

Figure 15 illustrates the effects of Tc on γc,max and t0 for the parametric case Tr,∞ = 70 °C, T0 = 15 °C, βt = 10 kJ/m2 h °C and tc = 0.3 m. It was depicted that both γc,max and t0 increase linearly with the increase of Tc. This influence characteristics is similar with T0, which has been explained before.

Fig. 15
figure 15

Effects of Tc on γc,max and t0 for the parametric case Tr,∞ = 70 °C, T0 = 15 °C, βt = 10 kJ/m2 h °C and tc = 0.3 m

5.3.4 Effects of βt

The effects of βt on γc,max and t0 for the parametric case Tr,∞ = 70 °C, T0 = 15 °C, Tc = 25 °C and tc = 0.3 m were depicted in Fig. 16. With the increase of βt, linear drop trends were observed both in γc,max and t0. In other words, the gradually deteriorating curing conditions accelerate the convection, which reduces and delays the maximum concrete temperature rise.

Fig. 16
figure 16

Effects of βt on γc,max and t0for the parametric case Tr,∞ = 70 °C, T0 = 15 °C, Tc = 25 °C and tc = 0.3 m

5.3.5 Effects of tc

The effects of tc on γc,max and t0 for the parametric case Tr,∞ = 70 °C, T0 = 15 °C, Tc = 25 °C and βt = 10 kJ/m2 h °C are illustrated in Fig. 17. As the increasing tc increases the mass of concrete deck, elevating trends of γc,max and t0 were observed with the increase of tc.

Fig. 17
figure 17

Effects of tc on γc,max and t0 for the parametric case Tr,∞ = 70 °C, T0 = 15 °C, Tc = 25 °C, and βt = 10 kJ/m2 h °C

5.3.6 Analysis of Variance (ANOVA)

Based on the results of above parametric study, ANOVA was employed to analyze the significance of the effect of each parameter on γc,max and t0. F-test was used to accept or reject the null hypothesis that the means of the different groups are the same at a stated level of significance. F value can be calculated by [34]

$$F = \frac{{{\text{MS}}_{\text{T}} }}{{{\text{MS}}_{\text{E}} }},\quad {\text{MS}}_{\text{T}} = \frac{{{\text{SS}}_{\text{T}} }}{{I_{m} - 1}},\quad {\text{MS}}_{\text{E}} = \frac{{{\text{SS}}_{\text{E}} }}{{I_{n} - I_{m} }}$$
(9)

where MST and MSE are the mean squares between groups and within groups, respectively; SST and SSE are the sum of squares between groups and within groups, respectively; Im is the number of groups; In is the total number of cases. For a given significant level α, if F ≥ F1−α(Im − 1, In − Im), the F-test will reject the null hypothesis, which means there are serious differences between the means of groups.

In this ANOVA, Im equals to 4 and In equals to 640. The α was selected as 0.05. Then F0.95(3, 636) was calculated to be 2.6. Figure 18 shows the significant analysis of parameters. It can be seen that all the F values of parameters were larger than 2.6, suggesting significance effects on both γc,max and t0. Additionally, among these parameters, tc had the greatest influence on γc,max, T0 had the greatest impact on t0, and Tr,∞ has the poorest effects on both γc,max and t0.

Fig. 18
figure 18

Significant analysis of parameters

6 Spatio-temporal pattern of CTR

To facilitate the thermal design of composite girder during hydration process, a spatio-temporal pattern of CTR consisting a vertical pattern and an evolutionary pattern was proposed in this section.

6.1 Vertical pattern of CTR

It has been observed from Figs. 10 and 11 that temperature differences in the concrete deck are significantly small, and the generated self-stress in concrete deck can also be ignored. Therefore, for the simplification of the vertical pattern of CTR, it can be reasonably considered that the temperature is evenly distributed in the thickness direction of concrete deck. Previous analysis has also shown that the steel temperature of the bottom flange is only affected and almost equals to the curing temperature, based on which a simplified vertical pattern of CTR was subsequently proposed as shown in Fig. 19.

Fig. 19
figure 19

Vertical patterns of TRC: ahs > h0, and bhs < h0

In the vertical pattern, γc is the uniform CTR of concrete deck. γsd is the CTR of the bottom flange of steel girder and can be calculated by assuming that the temperature at the bottom of the steel girder equals to the curing temperature. Δγ, which equals to γc minus γsd, is the difference of CTR in steel girder. n is the power exponent. h0 is the influence height of hydration heat on steel girder. hs is the height of steel girder. According to the relationship between hs and h0, the vertical pattern was divided into the following two categories:

  • When h0 > hs, the vertical pattern is composited with a uniform section in concrete deck, a variable section with power curve in steel girder, and a uniform section in steel girder, as shown in Fig. 19a and expressed with Eq. (10).

  • When h0 < hs, the uniform section in steel girder does not exist, only the uniform section in concrete deck and the partial variable section in steel girder remain, as shown in Fig. 19b and expressed with Eq. (11).

  • When hs > h0,

    $$ \gamma \left( y \right) = \left\{ {\begin{array}{*{20}l} {\gamma_{\text{c}} } \hfill & {y \le 0} \hfill & {{\text{Uniform}}\,{\text{section}}\,{\text{in}}\;{\text{concrete}}\;{\text{deck}}} \hfill \\ {\gamma_{\text{sd}} + \Delta \gamma \left( {1 - \frac{y}{{h_{0} }}} \right)^{n} } \hfill & {0 < y \le h_{0} } \hfill & {{\text{Variable}}\,{\text{section}}\,{\text{in}}\,{\text{steel}}\,{\text{girder}}} \hfill \\ {\gamma_{\text{sd }} } \hfill & {h_{0} < y \le h_{\text{s}} } \hfill & {{\text{Uniform}}\,{\text{section}}\,{\text{in}}\,{\text{steel}}\,{\text{girder}}} \hfill \\ \end{array} } \right. $$
    (10)
  • when hs < h0,

    $$ \gamma \left( y \right) = \left\{ {\begin{array}{*{20}l} {\gamma_{\text{c}} } \hfill & {y \le 0} \hfill & {{\text{Uniform}}\,{\text{section}}\,{\text{in}}\,{\text{concrete}}\,{\text{deck}}} \hfill \\ {\gamma_{\text{sd}} + \Delta \gamma \left( {1 - \frac{y}{{h_{0} }}} \right)^{n} } \hfill & {0 < y \le h_{\text{s}} } \hfill & {{\text{Variable}}\,{\text{section}}\,{\text{in}}\,{\text{steel}}\,{\text{girder}}} \hfill \\ \end{array} } \right. $$
    (11)

In the proposed vertical pattern, obviously, the influence height h0 can be expressed as the function of Δγ, and n can be subsequently calculated by h0. Through regression of the results of parametric study, the calculation formulae of h0 and n can be obtained as Eqs. (12) and (13). Figure 20 also shows their relationships. Among them, exponential relationships were shown between h0 and Δγ with T0 = 5 °C, 15 °C, 25 °C and 35 °C. The larger the T0, the smaller the h0. For another T0, interpolation method can be used to determine the corresponding h0. n is independent of T0 and increases linearly with the increase of h0.

Fig. 20
figure 20

Relationships between ah0 and Δγ, and bn and h0

$$ h_{0} = \left\{ \begin{aligned} &1.25\left( {1 - {\text{e}}^{ - 19.31\Delta \gamma } } \right)\quad T_{0} = 5, \hfill \\ &1.05\left( {1 - {\text{e}}^{ - 11.42\Delta \gamma } } \right)\quad T_{0} = 15, \hfill \\ &0.96\left( {1 - {\text{e}}^{\; - 8.66\Delta \gamma } } \right)\quad T_{0} = 25, \hfill \\ &0.93\left( {1 - {\text{e}}^{\; - 6.44\Delta \gamma } } \right)\quad T_{0} = 35, \hfill \\ \end{aligned} \right. $$
(12)
$$n = 4.25h_{0} - 0.39$$
(13)

Figure 21 shows the verification of the proposed vertical patten. Both the CTR results of FEM and in Choi’s [9, 10] experiments are in good agreement with the proposed patterns, and all the R2 are larger than 0.95, which well verifies the accuracy and applicability of the proposed vertical pattern. Based on the pattern, vertical temperature distributions can be obtained by only knowing the historical temperature evolutions of concrete deck and curing temperature. In addition, this pattern is independent of concrete age, as well can significantly reduce the number of sensors for the temperature measurement of composite girder during hydration process.

Fig. 21
figure 21

Verification of the proposed vertical pattern of CTR with a 3D FEM and 2 Choi’s experiment [9]

6.2 Evolutionary pattern of CTR

Measured temperature evolution of concrete deck is generally not available at the design stage. A simple method for the fast calculation of the temperature evolution of bridge deck is required. However, no readymade method is provided in the current specification system. Through measurement and FEM analysis, it was found that the evolutionary pattern of the CTR of concrete deck with age can be expressed by two “S” curves: ascending stage and descending stage, as shown in Fig. 22 and expressed with Eq. (14).

$$ \gamma_{\text{c}} \left( t \right) = \left\{ \begin{array}{lll} \frac{{\gamma_{c,{\text{max}} } }}{{1 + \left( {\frac{{t_{0} - t}}{{t_{0} - t_{1} }}} \right)^{p} }}, & t \le t_{0} ,& {\text{Ascending}}\;{\text{stage}} \hfill \\ \frac{{\gamma_{c,{\text{max}} } - \gamma_{{T_{\text{c}} }} }}{{1 + \left( {\frac{{t - t_{0} }}{{t_{2} - t_{0} }}} \right)^{q} }} + \gamma_{{T_{\text{c}} }} ,& t > t_{0} , & {\text{Descending}}\;{\text{stage}} \hfill \\ \end{array} \right. $$
(14)

where γc(t) is the CTR of concrete deck. γc,max is the maximum value of γc(t). γTc is the CTR after the hydration heat is over, γTc = (Tc − T0)/Tr,∞. t0 is the corresponding age to γc,max.t1 and t2 are the corresponding ages to γc,max/2 in ascending stage and (γc,max + γTc)/2 in descending stage. p and q are coefficients.

Fig. 22
figure 22

Evolutionary pattern of CTR of concrete deck

Based on the FEM results, multiple regression analysis was performed to derive the parametric formulae of characteristic parameters, γc,max and t0, in Eq. (14). The general functions adopted for regressions were all determined through repeated efforts. Through multiple regression analysis, the proposed formulae for γc,max and t0 were achieved and shown in Eqs. (15) and (16) with the five basic parameters Tr,∞ in  °C, T0 in  °C, Tc in  °C, βt in kJ/m2 h  °C and tc in m. In addition, with γc,max and t0, the empirical formulae of t1 and t2 were also established as Eqs. (17) and (18). Also, it was found that the five parameters had little influence on p and q. Thus, the average value of regression results was taken as the value of p and q, i.e., p = 5.69, q = 2.09.

$$ \begin{aligned} \gamma_{c,\hbox{max} }& = \left( {T_{0} - T_{\text{c}} } \right)\left( {T_{{{\text{r,}}\infty }}^{0.012} - 1.057} \right) + T_{\text{c}}^{0.069} - 0.005\beta \\ &\quad+ \left( { - 1.212t_{\text{c}}^{ 2} + 1.471t_{\text{c}} } \right) - 1.155 \end{aligned} $$
(15)
$$t_{0} = 1 7. 1 5 4 {\text{e}}^{{0.0002T_{{{\text{r,}}\infty }} \left( {T_{0} - T_{\text{c}} } \right) - 0.046T_{0} + 0.022T_{\text{c}} - 0.011\beta + \left( { - 2. 4 9 6t_{\text{c}}^{ 2} + 3. 2 0 1t_{\text{c}} } \right)}}$$
(16)
$$t_{1} = 1.896 - 0.545\gamma_{\text{c,max}}^{\;0.501} + 0.301t_{0}^{\;1.237} - 0.233\gamma_{\text{c,max}}^{\;0.501\;} t_{0}^{\;1.237}$$
(17)
$$ \begin{aligned} t_{2} &= 3.715 + 3.745\left( {\gamma_{\text{c,max}} - \gamma_{{T_{\text{c}} }} } \right)^{1.846} + 1.536t_{0}^{1.049} \\ &\quad+ 3.021\left( {\gamma_{\text{c,max}} - \gamma_{{T_{\text{c}} }} } \right)^{1.846} t_{0}^{1.049} \end{aligned} $$
(18)

For the purpose of checking the accuracy of the proposed formulae, comparisons of γc,max, t0, t1 and t2 between the predict values of the proposed formulae and FEM values of FEM analysis were carried out and shown in Fig. 23. In addition to R2, the average absolute error (AAE) and the root-mean-square error (RMSE) [35] were also used to check the accuracy of the proposed formulae. For γc,max, t0, t1 and t2, all the R2 exceed 0.97. Furthermore, the AAEs are only 0.015, 0.556 h, 0.246 h and 1.385 h, and the RMSEs are only 0.019, 0.667 h, 0.336 h and 1.724 h for γc,max, t0, t1 and t2. All the results indicate good accuracies and reliabilities of the proposed formulae.

Fig. 23
figure 23

Comparison between predicted value and FEM value of: aγc,max, bt0, ct1 and dt2

Figure 24 shows the comparisons of CTR evolution between the proposed patterns (plotted in lines) and FEM results (plotted in scatters) in some parametric cases. All the R2 of the comparisons exceed 0.97, verifying good accuracies and reliabilities. The proposed evolutionary pattern is a more efficient method and can be an approximate substitutionof FEM and experiment for the determination of the temperature evolution of concrete deck during hydration process. It also should be noted that this proposed evolutionary pattern was established to be applicable to a stationary curing temperature.

Fig. 24
figure 24

Verification of the proposed evolutionary pattern of CTR in parametric case: aT0 = 15 °C, Tc = 25 °C, βt = 10 kJ/m2 h °C and tc = 0.3 m, bTr,∞ = 70 °C, Tc = 25 °C, βt = 10 kJ/m2 h °C and tc = 0.3 m, cTr,∞ = 70 °C, T0 = 15 °C, βt = 10 kJ/m2 h °C and tc = 0.3 m, dTr,∞ = 70 °C, T0 = 15 °C, Tc = 25 °C and tc = 0.3 m, eTr,∞ = 70 °C, T0 = 15 °C, Tc = 25 °C, and βt = 10 kJ/m2 h °C

7 Thermal stress analysis

7.1 Simplified method for thermal stress calculation

This section presents a simplified method for the thermal stress calculation of composite girder with the proposed spatio-temporal pattern of CTR. As well known, mechanical properties of concrete develop in time during the hydration process [23]. Therefore, an incremental analysis procedure was performed at a time step Δti = titi-1. Additionally, the following limitations were also considered in the simplified method: (a) without regard to creep and shrinkage effect; (b) full interaction between concrete deck and steel girder, which means that the Euler–Bernoulli hypothesis is valid for the whole composite section; (c) the origin of y coordinate axis at the concrete–steel interface. Based on the above limitations, the increment of total axial strains Δεtot,i(y) at Δti must satisfy

$$\Delta \varepsilon_{{{\text{tot,}}i}} (y) = \Delta \varepsilon_{0,i} + \Delta \varphi_{i} \left( {y - y_{\text{iG}} } \right) = \Delta \varepsilon_{{{\text{e,}}i}} (y) + \Delta \varepsilon_{{{\text{T,}}i}} (y)$$
(19)

where yiG is distance from the centroid of composite section to the interface. Δε0,i is the increment of centroidal axial strain. Δφi is the increment of curvature. Δεe,i is the increment of elastic strain, which result in stresses. ΔεT,i is the temperature strain and can be calculated by:

$$\Delta \varepsilon_{{{\text{T,}}i}} (y) = \alpha (y)\Delta T_{i} (y)$$
(20)

where α(y) is the coefficient of thermal expansion, and refers to αc and αs for concrete and steel, respectively. ΔTi(y) is the vertical distribution of the temperature increment caused by hydration heat and can by calculated in terms of the proposed spatio-temporal pattern of CTR for an arbitrary parametric case. ΔTc,i denotes the temperature increment of concrete, and ΔTs,i(y) denotes the vertical distribution of the temperature increment of steel girder.

$$\Delta T_{i} (y) = T_{{{\text{r,}}\infty }} \left[ {\gamma_{i} \left( y \right) - \gamma_{i - 1} \left( y \right)} \right]$$
(21)

During hydration process, if no external forces are applied on the composite section, the centroidal axial force ΔNi and the moment around the centroidal axis ΔMi equals to zero. Then, the following equilibrium equations hold:

$$\Delta N_{i} = \int_{{A_{\text{c}} + A_{\text{s}} }} {E_{i} (y)\left[ {\Delta \varepsilon_{0,i} + \Delta \varphi_{i} \left( {y - y_{\text{iG}} } \right) - \Delta \varepsilon_{{{\text{T,}}i}} (y)} \right]{\text{d}}A} \; = 0$$
(22)
$$\Delta M_{i} = \int_{{A_{\text{c}} + A_{\text{s}} }} {E_{i} (y)\left[ {\Delta \varepsilon_{0,i} + \Delta \varphi_{i} \left( {y - y_{\text{iG}} } \right) - \Delta \varepsilon_{{{\text{T,}}i}} (y)} \right]\left( {y - y_{\text{iG}} } \right){\text{d}}A} \; = 0$$
(23)

where Ac and As are the areas of concrete deck and steel girder. Ei(y) is the elastic modulus and denotes Ec,i for concrete at ti and Es for steel. CEB-FIP 2010 [36] provides the development of elastic modulus Ec,i and tensile strength ft,i with the age and temperature for normal weight concrete as

$$E_{{{\text{c}},i}} = E_{{{\text{c}},28}} \left( {1.06 - 0.003T} \right)\left\{ {\exp \left[ {s\left( {1 - \sqrt {\frac{28}{{t_{i} }}} } \right)} \right]} \right\}^{0.5}$$
(24)
$$f_{t,i} = f_{t,28} \left( {1.16 - 0.008T} \right)\left\{ {\exp \left[ {s\left( {1 - \sqrt {\frac{28}{{t_{i} }}} } \right)} \right]} \right\}^{2/3}$$
(25)

where Ec,28 and ft,28 is concrete’s elastic modulus and tensile strength at an age of 28 days and a reference temperature of 20 °C. T is the temperature in °C. ti is the age of concrete in day. s is a coefficient and depends on the type of cement.

By defining ηi = Ec,i/Es, Δε0,i and Δφi in Eq. (19) can be solved as:

$$\Delta \varepsilon_{0,i} = \frac{{\eta_{i} \alpha_{\text{c}} \Delta T_{{{\text{c,}}i}} A_{\text{c}} + \alpha_{\text{s}} \int_{{A_{\text{s}} }} {\Delta T_{{{\text{s,}}i}} (y){\text{d}}A} \;}}{{\eta_{i} A_{\text{c}} + A_{\text{s}} \;}}$$
(26)
$$\Delta \varphi_{i} = \frac{{\eta_{i} \alpha_{\text{c}} \Delta T_{{{\text{c,}}i}} A_{\text{c}} y_{\text{cG}} + \alpha_{\text{s}} \int_{{A_{\text{s}} }} {\Delta T_{{{\text{s,}}i}} (y)(y - y_{\text{iG}} ){\text{d}}A} \;}}{{\eta_{i} I_{\text{c,0}} + I_{\text{s,0}} \;}}$$
(27)

where ycG is the coordinate of the centroid of concrete deck. Ic,0 and Is,0 are the moments of inertia of the concrete deck and the steel girder around the centroidal axis of composite section.

With Δε0,i and Δφi, the thermal stress increments of concrete deck and steel girder, Δσc,i and Δσs,i can be calculated by:

$$\Delta \sigma_{{{\text{c,}}i}} (y) = E_{{{\text{c,}}i}} \left[ {\Delta \varepsilon_{0,i} + \Delta \varphi_{i} \left( {y - y_{\text{iG}} } \right) - \alpha_{\text{c}} \Delta T_{{{\text{c,}}i}} } \right]$$
(28)
$$\Delta \sigma_{{{\text{s,}}i}} (y) = E_{\text{s}} \left[ {\Delta \varepsilon_{0,i} + \Delta \varphi_{i} \left( {y - y_{\text{iG}} } \right) - \alpha_{\text{s}} \Delta T_{{{\text{s,}}i}} (y)} \right]$$
(29)

7.2 Case study

In this section, a case study was performed on a composite girder with a C30 concrete deck. Figure 25 shows the section dimensions of the girder. Table 4 summarizes the relevant mechanical properties of C30 concrete and steel. Parametric cases that Tr,∞ = 70 °C, T0 = 25 °C, βt = 5 kJ/m2 h °C, and tc = 0.3 m in three curing temperature conditions of Tc = 15 °C, 20 °C and 25 °C were selected for the thermal stress calculation with the proposed simplified method.

Fig. 25
figure 25

Section dimensions of calculated composite girder (unit: mm)

Table 4 Mechanical properties

Figure 26 depicts the calculated axial stress development in the concrete deck; the design value of tensile strength ft,d of C30 concrete was also plotted for comparison. It can be seen that when the curing temperature is 15 °C, the tensile stress of concrete starts to exceed ft,d at the time of 107 h, resulting in potential cracking risk in the concrete deck. When the curing temperature is increased to 20 °C and 25 °C, the tensile stress of concrete is always lower than ft,d, and the cracking risk can be effectively controlled.

Fig. 26
figure 26

Calculation of concrete stress with the proposed simplified method

8 Discussion

The research in this paper is helpful to confirm that the early-age cracks mentioned by Darwin et al. [37] in the crack investigation of concrete deck. Subramaniam [8] observed the obvious temperature difference between the upper and lower flanges of the steel girder, believing that it contributed to the cracking of the concrete deck. Choi’s [9, 10] test also suggested this temperature difference and also the large concrete–steel temperature difference. However, they did not clearly define the distribution patterns based on the temperature differences. This paper not only gives the spatial temperature pattern in the form of CTR, but also established the evolutionary pattern. As the case study implies, the effect of hydration heat on the early cracking risk in concrete deck can be efficiently estimated with the proposed spatio-temporal pattern of CTR and the simplified method for thermal tress calculation. As such, reasonable and effective curing schemes can be preliminarily and easily selected to control the early-age cracking in concrete before actual cast-in situ construction of concrete deck.

The analysis presented here is based on several simplifications, including full interaction between concrete deck and steel girder and uniform temperature of concrete deck, which were all issues that need further considerations for a finer and more accurate calculation of thermal stress.

9 Conclusions

This paper is aimed to propose a reasonable spatio-temporal pattern of hydration temperature and a simplified method to preliminarily and efficiently estimate the thermal stress of concrete deck during hydration process. The spatio-temporal pattern was established by using finite-element models. These models were verified with large-scale temperament measurement on an actual composite girder bridge and then used to perform a comprehensive parametric study covering a wide range of basic parameters including Tr,∞, T0, Tc, βt and tc. Through multiple regression analysis, a series of empirical formulae was established to predict the key coefficients in the patterns. Based on the current investigation, main conclusions were drawn as follows:

  1. 1.

    Experiment shows that during hydration process, the temperature difference of concrete deck varied slowly within about 5 °C, significantly smaller than the temperature difference of entire composite section. The bottom flange temperature of steel girder basically changes in accordance with the curing temperature.

  2. 2.

    With experimental results, the accuracy of heat transfer FEM is fully verified at aspects of temperature evolution, vertical distribution and field contours. The ratio of the effects of hydration heat, solar radiation and air convection on the temperature change is 32.0:1:− 15.5 in the warming phase by hydration heat, which suggests that the influence of solar radiation can be basically ignored.

  3. 3.

    The spatio-temporal pattern proposed in the form of CTR includes vertical patterns and an evolutionary pattern. The vertical patterns consist of a uniform section in concrete deck, a variable section with power curve in steel girder and a uniform section in steel girder. The evolutionary pattern can be expressed by two “S” curves in ascending and descending stages. The accuracies and reliabilities of these patterns were all properly verified with the results of experiments or FEMs.

  4. 4.

    The simplified method for the thermal stress calculation of concrete deck during hydration process is established based on an incremental analysis procedure with the proposed spatio-temporal pattern of CTR. As such, reasonable and effective curing schemes can be easily selected to control the early-age cracking in concrete before actual cast-in situ construction of concrete deck.

The simplified method proposed in this paper is based on the assumption of full interaction between concrete and steel and does not consider the effects of creep and shrinkage. Additionally, the self-stress caused by the nonlinear temperature distribution of concrete deck is not considered neither, although the temperature is nearly uniformly distributed in the concrete deck. These are all the further researches that should be carried out in the future.