Introduction

High Impedance Faults (HIFs) generally appear on the primary distribution system when a bare energized overhead conductor comes in contact with high impedance surfaces [1]. HIF current contain some complex characteristics such as asymmetry, nonlinearity and low frequency. Due to that, it is quite challenging for any traditional over-current relays to detect the HIF because unlike other types of faults HIFs give rise to a very small amount of fault current, i.e. in between 10-100 (A) depending on the type of surfaces (i.e. dry or wet sand, asphalt, sod, grass, trees etc.). The failure of HIF detection may lead to fire hazard and arcing [1]. So it is necessary to identify the HIF and to isolate the corresponding feeder.

The main objective of many detection schemes is to identify the special features in the patterns of voltage and current associated with HIF. Identification techniques generally contain two vital steps: feature extraction and classification [2]. For many years, some protection engineers and researchers had introduced numerous feature extraction and classification techniques such as digital signal processing [3], fractal analysis [4], wavelet transform (WT) [510], crest factor [11], coefficient of variation [11], mathematical morphology [12], Kalman filtering [13], decision tree [14] etc. and various classifiers have been used such as Bays, nearest neighbor rule (NNR), artificial neural network (ANN) [15], ANFIS (adaptive neuro-fuzzy inference system) [16] etc. One of the main drawbacks of fourier transform (FT) based technique is that it does not have any time information associated with the fault instant. To overcome this limitation of FT another detection scheme based on wavelet transform (WT) was proposed. Unlike FT, the WT possesses information both in the time domain and in frequency domain and it deals with non-stationary signals such as those experiencing HIF arcing fault. The efficiency of WT decreases in noisy environments where as Stackwell transform(ST) [17] is very much sensitive to noise (i.e. it has the ability to identify any type of disturbance correctly in the presence of noise) due to which ST is more effective than WT for detecting HIF in the system. S-Transform has various applications in the field of Geophysics, Genomic Signal Processing, Biomedical Engineering, and Power System Protection.

In this paper, a contingent method is proposed that uses ST for feature extraction. The ST is an extended version of WT which is used to extract the time and frequency components of the voltage and current. The fixed resolution of the short time fourier transform (STFT) and the absence of phase information in the WT lead to the development of the S-transform, which not only retains the absolute phase information but also has good time frequency resolution for all frequencies. Again, this paper analyzes the usefulness of applying an artificial neural network (ANN) and support vector machine (SVM) for HIF classification based on the ST feature vector. The ANN classifiers perform better than other conventional method as it based on the gradient decent method which minimises the total squared error of the output. On the other hand SVM classifier is very much applied in various fields of engineering as it tries to find an optimal hyperplane that maximizes the margin between data samples in two classes in a higher dimensional feature space derived from the original data space through a kernel function. As, both the classifier have different advantages with each other and successfully applied by different researchers for various applications like power quality events classification, transmission line fault classification, speech recognition and islanding classification in microgrid etc. the same has been considered as a classifier for this work.

After capturing the discrete value of voltage and current waveforms for a definite sample of the power system, these data sets aree analyzed by ST and different distinguish features are extracted from STA matrix. Then the extracted features were fed as an input to the classifier to determine whether the HIF occur or not.

The major contributions of this study towards HIF detection problem are: (1) application of ST for feature extraction instead of using other popular signal processing technique like WT and ST. (2) use of SVM and ANN for classification and detection of HIF condition. (3) analysing the application of the above techniques under practical operating conditions. (4) presentation of extensive comparative results with recently published and well proved techniques.

The rest part of the paper structure is organized as follows: The complete power system model and description are introduced in “System Under Study”. The brief explanation of the ST is presented in “Stackwell Transform (ST)”. A brief description of the proposed classifier is illustrated in “Classification of Events”. Results have been illustrated and analyzed in “Results and Discussion” by the proposed methodology which justifies the efficiency of the methods for real time application. Lastly, the conclusion and future work has been enumerated in “Conclusion” and 7 respectively.

System Under Study

The initial step of every observation is to develop a proper model. In this paper not only HIF model, but also various transient conditions are simulated such as capacitor switch, load switch, normal ground fault models etc. All these models are generated with the help of the power system block set and are sampled at a rate of 5 KHz frequency, which is equal to 100 samples/cycle. The power system fundamental frequency is taken as 50 Hz.

  • (a) Power system model description with Single Line Diagram:

    In the proposed study both radial and mesh distribution system are taken into consideration as shown in the Fig. 1a and b respectively. In radial distribution system a generator of 50 MVA is connected to supply 138KV of voltage to the utility sector through a transmission line of 100 km long and a 138/25 KV star/delta transformer. A HIF fault is created on one of its distribution feeders at 15km from its source side. A three branched radial distribution network has been used with both linear and non-linear loads of 4MVA and 1MVA respectively. Two other branches with 2MVA and 4.262MVA non-linear loads are integrated in the system with 0.8 pf.

    Similarly, in mesh distribution system three generators, each with rating of 50 MVA are used to supply 138 KV of voltage to the utility sector through a 25KV transmission line. At each end three star-delta transformers are used with the rating of 5MVA to step-down the voltage from 138KV to 25KV. All other system conditions such as capacitor switching, load switching and normal fault condition has been implemented in the system. In total 4000 cases are used to test for classification purpose. By changing the parameters, 250 cases are taken for each type of faults such as L-G, L-L-G, L-L-L-G faults. So a total of 1750 each for HIF and normal fault conditions are simulated. Each with 250 cases of capacitor switching and load switching have been considered and simulated by changing parameters within a certain range.

  • (b) HIF Model Simulation:

    There are various types of HIF models as proposed by many researchers [18]. Out of which two types of HIF models are being used in the paper as shown in Fig. 2a and b respectively. Figure 2a shows a simplified HIF model having two unequal resistances that make unsymmetrical fault current [19].

Fig. 1
figure 1

System Models a Radial System Model (System 1), b Mesh System Model (System 2)

Fig. 2
figure 2

HIF Model a Type I, b Type II

Figure 2b shows a simplified two diode HIF model with two anti-parallel diodes (Dp, Dn), two unequal value resistors (Rp, Rn) which allows asymmetric fault current and two DC voltage (Vp, Vn) which perform as the inception voltage of air in soil or between trees and distribution line [20]. If Vph > Vp then current (I) flows towards the ground and when Vph < Vn then flow of current get reversed. For Vn < Vph < Vp no fault current flows. Here, both the models are based on Emanuel arc model. In this paper, both the models are used at different places on the transmission line to simulate the fault current.

Figure 3a and b depict the V-I characteristic curve which shows a non-linear cyclic pattern due to HIF model Type I and Type II respectively. Due to the occurrence of HIF at 0.1sec there is a distortion in current and voltage waveform as shown in Fig. 4a. Figure 4b shows the total current and voltage at the sub-station for HIF for single line to ground fault at B-ph.

Fig. 3
figure 3

Simulated HIF V-I Characteristic curve with HIF model Type I and Type II in (a) and (b) respectively

Fig. 4
figure 4

a Simulated HIF Voltage and current Waveform, b Sub-station current and voltage with HIF at B-g

Stackwell Transform (ST)

The S-transform [2023] is an extended version of wavelet transform which is based on shifting and scalable localizing Gaussian window. The continuous wavelet transform can be represented as:

$$ cwt_{g}^{\phi} \left( {\tau ,d} \right)={\int}_{-\infty}^{\infty} {g\left( t \right)}. \phi \left( {t-\tau ,d} \right)dt $$
(1)

Where the input signal g(t) is represented as a function of time (t).

The width (d) and the time of spectral localization (τ) controls the resolution of the wavelet CWT (τ,d), which is a scaled copy of the fundamental mother wavelet.

Mathematically ST is represented as a CWT along with a précised mother wavelet multiplied with phase factor (e j2πft).

$$ S\left( {\tau ,f} \right)=e^{-j2\pi ft}CWT\left( {\tau ,d} \right) $$
(2)

Where the mother wavelet for the particular case can be represented as

$$ \phi \left( {t,f} \right)=\frac{\left| f \right|}{\sqrt {2\pi}}. e^{\frac{{-t}^{2} f^{2}} {2}}.e^{-j2\pi ft} $$
(3)

\(\sigma \left (f \right )=\frac {1}{\left | f \right |}\), is the width of the Gaussian window. The time scale representation is produced by WT while ST is used to produce both time and frequency representation.

The ST may be represented as

$$ S\left( {\tau ,f} \right)=\int\limits_{-\infty}^{\infty} {g\left( t \right)\times \frac{\left| f \right|}{\sqrt {2\pi} } } e^{-\left( {\left( {t-\tau} \right)^{2}f^{2}/2} \right)}\times e^{j2\pi ft}dt $$
(4)

In discrete form ST may be written as

$$ S\left( {i,n} \right)=\sum\limits_{m=0}^{N-1} {g\left( {n+m} \right)e^{\left( {-2k^{2}\pi^{2}m^{2}/a+b\sqrt {\left| f \right|}} \right)^{2}}e^{j\left( {2\pi mi} \right)/N}} $$
(5)

Where i = 1, 2, … N-1 and n = 0, 1 … N-1 represents as time in sample and frequency step respectively. The output of ST is a N * M matrix represented as STA matrix

Classification of Events

In this section the intelligent classifiers used for the HIF detection are discussed.

Neural Network (NN)

The Back Propagation Neural (BPN) Network is used as a classifier between HIF and non-HIF events because of its fast response, lesser complexity and flexibility of use. BPN is a multilayer fast forward network with extended gradient-descent based delta-learning rule usually known as back propagation or error rule. Back propagation provides a computationally efficient method for changing the weight in a feed forward network, with differentiable activation function units, to learn a training set of input-output examples [24]. GE Hinton, Rumelhard and R.O.Williams first introduced BPN in 1986.Being a gradient descent method, which minimizes the total squared error of the output computed by the net. The network is trained by supervised learning method [25, 26]. The architecture of the neural network is shown in Fig. 5.

Fig. 5
figure 5

Architecture of NN

Support Vector Machines (SVM)

Support Vector Machine is a very important classifier which is widely used in various power system related problems. SVM introduces a unique training algorithm which is used to maximize the boundary between the various classes [27]. It carries a couple of data set: input vector and class (Pi , Qi), where i = 1, 2, … [28].

$$ L\left( w,\xi \right)=0.5(w^{T}w)+C\sum\nolimits_{i=1}^{l} {\xi_{i},\xi_{i}>0} $$
(6)
$$ Q_{i}\left( w^{T}\emptyset \left( p_{i} \right)+b \right)\ge 1-\xi_{i} $$
(7)

The solution of SVM is derived by minimizing Eq. 6 with respect to Eq. 7. Here b, ω and ξ are the bias, weight and error term respectively. L is known as the penalty factor. The different kernel functions like linear, radial, polynomial, sigmoid function are usually used for mapping and in this study sigmoid function is used due to its better performance. SVM maps the input vector into a large dimensional space. A hyper plane in feature space is used through various mapping functions to increase its ability of classification.

Results and Discussion

Performance of S-Transform on HIF Fault Detection Visually

In this paper, HIF, normal faults and other transient signals as capacitor switching and load switching events are taken for analysis. The ST is applied to the entire above mentioned distorted signal to generate time-frequency, time-amplitude and amplitude-frequency plots, that presents the disturbance pattern for visual inspections and to know the nature of the disturbance. All three important information as amplitude, frequency, and time can be easily calculated to detect and classify various signals. These signals are simulated using MATLAB/SIMULINK.

Figure 6 shows the HIF signal, the time frequency, time-amplitude and frequency-amplitude plots generated from its STA matrix. Figure 6a shows the HIF current signal and Fig. 6b shows the frequency versus time plot of STA which is called as time-frequency contour (TF-contour). It is clearly observed from the frequency contour that a substantial fluctuation occurred at the instant of HIF. Figure 6c shows the maximum amplitude vs. time plot (MAT-plot) that is obtained by searching columns of STA at each frequency. Figure 6d gives the maximum amplitude vs. frequency plot (MAF-plot) that is maximum magnitude versus normalized frequency by searching rows of STA matrix. The plot shows the disturbance frequency components and their maximum amplitude. Figure 6e shows the energy vs. time plot (MET-plot) that gives the energy versus time by searching columns of STA at every frequency. Figure 6f shows the energy vs. frequency plot (MEF-plot), that gives the energy versus frequency by searching row of STA. Figure 6g shows the time-standard deviation plot (STDT-plot), which gives the standard deviation versus time by searching columns of STA at every frequency. Figure 6h shows the frequency-standard deviation plot (STDF-plot), that gives the standard deviation versus normalized frequency by searching rows of STA. Figure 6i shows the median vs. time plot of STA matrix.

Fig. 6
figure 6

a B-ph current signal with HIF b TF-contour c MAT-plot d MAF-plot e MET-plot f MEF-plot g STDT-plot h STDF-plot i median vs. Time plot

Figure 7 shows a clear visual comparison between HIF and all other system conditions (normal fault, capacitor switching, load switching and no fault) based on energy with respect to time and frequency in Fig. 7a and b respectively. It is observed that the energy for normal fault condition is relatively higher than the other four conditions that can be easily distinguishable. In other four conditions, a little variation in the value of energy is observed but that can be accurately classified. Similarly Fig. 8 shows a complete visual comparison between HIF and all other conditions showing the magnitude vs. time plot (MAT-plot) and magnitude vs. frequency plot (MAF-plot) in Fig. 8a and b respectively. Figure 9 shows a clear visual comparison between HIF and all other conditions based on the standard deviation vs. time plot (STDT-plot) and standard deviation vs. frequency plot (STDF-plot) in Fig. 9a and b respectively. Figure 10 shows a noticeable visual comparison between HIF and all other conditions based on the median vs. time plot. There is a sudden hike in the value of median approximately at 500 samples with respect to time.

Fig. 7
figure 7

Comparison between HIF and all other system conditions based on Energy Vs Time and Frequency respectively in (a) and (b)

Fig. 8
figure 8

Comparison between HIF and all other system conditions based on magnitude Vs time and frequency respectively in (a) and (b)

Fig. 9
figure 9

Comparison between HIF and all other system conditions based on standard deviation Vs. Time and Frequency respectively in (a) and (b)

Fig. 10
figure 10

Median vs. Time plot

Extracted Features

S-transform is implemented to extract various features from generated current signals of all the proposed system conditions of power distribution networks. The time and frequency information of the resultant current signals is extracted from the generated S-matrix with accurate time and frequency resolution.

The time information is extracted from the S-matrix as:

$$MAT=\max \left( {abs\left( S \right)} \right) $$

Where MAT represents the maximum of the absolute value of the S-matrix (STA) generated from the S-transform which provides magnitude-time information.

Similarly frequency information is extracted using ST as:

$$ MAF=\max \left( {abs\left( {S^{T}} \right)} \right) $$
(8)

Where MAF states the maximum of the absolute value of the transposed STA generated using ST which provides magnitude-time(samples) information. Various features were extracted for each phases such as:

$$ F1_{i} =AF=1-\left( {\max (MAT)+\min \left( {MAT} \right)} \right)-F_{n} $$
(9)

Where ‘i’ represents phases (a, b, c)

F n = max (MAT) + min (MAT) for no fault condition and AF is known as amplitude factor, represented as F1.

$$ F2_{i} =entropy\left( {MAF} \right) $$
(10)

The entropy of magnitude-frequency plot (MAF-plot) is taken as feature 2 (F2).

$$ F3_{i} =\max \left( {MAF} \right) $$
(11)

Maximum value of magnitude-frequency plot (MAF-plot) is taken as feature 3 (F3).

$$ F4_{i} =\max \left( {MET} \right) $$
(12)

Maximum value of Energy-time plot (MET-plot) is taken as feature 4 (F4).

Energy is calculated using the equation

$$\begin{array}{@{}rcl@{}} MET=\max \left( {MAT^{2}} \right) \end{array} $$
(13)
$$\begin{array}{@{}rcl@{}} F5_{i} =\max \left( {MAT} \right) \end{array} $$
(14)

Maximum value of magnitude-time plot (MAT-plot) is taken as feature 5 (F5).

$$ F6_{i} =\max \left( {MSR\left( {STDF} \right)} \right) $$
(15)

Feature 6 (F6) represents mean square root (MSR) of standard deviation of magnitude-frequency plot (STDF)

$$ F7_{i} =STDF=std\left( {MAF} \right) $$
(16)

Feature 7 (F7) gives standard deviation of MAF

$$ F8_{i} =STDT=std\left( {MAT} \right) $$
(17)

Feature 8 (F8) represents the value of standard deviation of magnitude-time plot (STDT)

$$ F9_{i} =\max (R_{i} ) $$
(18)

Feature 9 (F9) represents the maximum value of the rate of change of energy (R) at each sample with respect to its previous sample.

Classification Of HIF

The total number of 4000 different HIF and non-HIF (capacitor switching, load switching and normal fault) cases are simulated to extract features from respective current signals. These data are used as features which are extracted from ST technique and are used in the detection of HIF events through the proposed pattern recognition technique. The flowchart of the proposed technique is shown in Fig. 11.

  1. A.

    Result ANN classifier using input as ST Feature

    In this paper, the HIF classification process is realized with multi-layer perceptron (MLP) neural network, where resilient back propagation (RPROP) is used as learning algorithm. The test system undertaken for the study is shown in Fig. 1.Out of total data 60 % are used for training and 40 % are used for testing for the classifier.

    Table 1 depicts the classification accuracy result for HIF and non-HIF events with and without noisy condition for one and the combination of two features vector. It is clearly seen that even with the reduced number of features the ANN gives an adequate performance classification. It is easily noticeable in Table 1 that by using feature vector F6 as an input to ANN results into higher accuracy then other single features vector. The overall performance of ANN using features vector F6 is shown in Table 2. It is evident from Table 2 that the overall accuracy for classification HIF with other transient events and normal fault is 98.75 %, 96.4 %, 94.06 % and 92.60 % for normal (without noise), with SNR 50db,with SNR 40db and with SNR 30db respectively.

    The confusion matrix (4 x 4) is shown in Table 3, where the diagonal element represents the correctly classified events and non-diagonal elements depicts the misclassification.

    Taking an appropriate combination of two feature vector (F6F7) ,the overall accuracy of classification is also shown in Table 1, where it indicates the percentage accuracy is increased to 100 %, 100 %, 97.70 % and 93.70 % for normal and noisy condition with SNR (signal to noise ratio) 50db, 40db and 30db respectively. The result indicates an inherent performance of the technique to detect HIF under noisy condition. The architecture of the MLP used for training with a combination of two feature vector is shown in Table 4.

  2. B.

    Result SVM classifier using input as ST Feature

    The overall performances of SVM for HIF classification with respect to Non-HIFs are explained in Tables 56 and 7. Table 5 depict the classification accuracy result for HIF and non-HIF events with and without noisy condition for one and the combination of two feature vector. It is clearly seen that even with the reduced number of features the ANN gives an adequate performance classification. It is easily noticeable in Table 5 that by using feature vector F6 as an input to SVM results in higher accuracy than other single features vector. The overall performance of SVM using features vector F6 is shown in Tables 6 and 7.

  3. C.

    Comparison of proposed method with existing technique based on accuracy

    This section provides a comparison view of proposed ST based method with the WT based method. Here the fault current extracted from PCC is processed through WT, and different features like energy content, standard deviation and entropy of signal are computed to train and test the ANN and SVM to discriminate the HIF from other transient condition and normal fault.

    From Table 8, it can be observed that the accuracy using WT_ANN in 30 dB noisy condition is 85.6 % where as in case of ST_ANN is 93.70 % which proves that ST provides a better accuracy under noisy condition than WT. So it is preferable to implement s- transform under noisy conditions to detect HIF. Table 9 demonstrates the comparison between the proposed s-transform based technique, and existing/proposed HIF detection methods. The information related to SNR 30 dB case are not available in the reference paper [5, 12, 29, 30] and is shown as NA (not available) in Table 9. The table clearly reveals an inherent performance of the technique to detect high impedance fault under noisy condition

    Fig. 11
    figure 11

    Flowchart of Proposed method

    Table 1 Performance of ANN with single and combination of two features vector
    Table 2 Overall performance of ANN with input feature F6 for system I
    Table 3 The classification accuracy in terms of confusion matrix having feature vector F6 with 50db noisy condition for system I
    Table 4 The architecture of MLP used for single feature vector
    Table 5 Performance of SVM with single and combination of two features vector
    Table 6 Overall performance of ANN with input feature F6 for system I
    Table 7 The classification accuracy in terms of confusion matrix having feature vector F6 with 30db noisy condition for system I
    Table 8 Comparison of proposed method with WT methods
    Table 9 Comparison of proposed method with existing methods

Conclusion

In this work a novel method based on s-transform and pattern techniques for HIF detection and classification is suggested. In this method the fault current extracted from PCC is processed through ST to extract time-and frequency information in term of STA matrix. For appropriate classification it is necessary to choose a suitable feature vector that can recognize the characteristics of signal. So statistical features vectors based on S-transform are retrieved. Then, the effectiveness of features is improved by selecting combination of optimum features vector. These features vector are used to train and test the intelligent classifier. ANN and SVM are used as intelligent classifier in this paper. Comparative result shows that the SVM based classifier is superior to ANN based classifier to detect HIF for noisy condition.

The scope of the paper is limited to the application of ST for feature extraction. Further, the performance of HIF detection can be improved through the application other fast version of discrete s-transform. In the classification stage, this work is limited to the use of ANN and SVM. So, the efficiency of HIF classification may enhance through the other new machine learning techniques like extreme learning machine(ELM), because of its fast response than SVM and ANN. The studied system can be further simulated by using of a time varying HIF model to test the performance of the proposed method.