Abstract
In this study, we evaluated the concentrations of culturable airborne bacteria (CABs) in the underground environment of 16 subway stations in Seoul, South Korea. The effects of environmental factors on CAB distributions and concentrations, including temperature, relative humidity, depth, year of construction, number of subway passengers, and ventilation, were investigated. Tryptone soy agar was used as the culture medium. Isolated bacteria were initially characterized according to cell morphology and Gram staining and then further characterized using the VITEK 2 XL microbial identification system. There were significant correlations between CAB concentrations and station temperature, depth, and construction year. Micrococcus and Staphylococcus species accounted for 66 % of the total number of CABs identified. CAB concentrations in stations with ventilation systems were significantly lower than those in stations without ventilation systems (p < 0.001). Thus, it is critical to develop techniques to improve indoor air quality in subway stations with no ventilation system.
Similar content being viewed by others
Avoid common mistakes on your manuscript.
Introduction
Public indoor environments have sometimes been considered intrinsically different from the outdoors and most of people’s time is spent indoors (Smith 2008). Indoor particulate matter is especially linked with detrimental health impacts (Goyal and Kumar 2013; Son et al. 2013). Among the different types of particulate matters, bacteria play an important role in human health. In particular, some types of bacteria are resistant to antibiotics and are likely to spread among crowds of people in public areas, such as subway stations (Zhou and Wang 2013).
Subways are a principal means of public transportation in large cities around the world (Hwang et al. 2010). The confined spaces within subway stations make these locations potential targets for airborne dispersion of biological threat agents, making indoor air quality in subway stations an important consideration for public health (Dybwad et al. 2012). Notably, indoor air quality is worse in subway stations than in aboveground public buildings (Kim et al. 2008). Several recent studies have investigated the concentrations of airborne bacteria in subway environments (Bogomolova and Kirtsideli 2009; Dybwad et al. 2012; Kim et al. 2011; Robertson et al. 2013; Leung et al. 2014). However, the effects of ventilation systems in subway stations on the concentrations of culturable airborne bacteria (CABs) have not been well studied (Zhang et al. 2007).
The purpose of this study was to assess the concentrations of CABs in underground subway stations in Seoul, South Korea. We also evaluated environmental factors affecting the concentrations of CABs, including the temperature, relative humidity, depth, construction year, number of passengers, and presence of ventilation systems in these stations.
Materials and methods
Sampling and analyses
In the spring of 2013, 33 air samples were collected from 16 subway stations in Seoul, South Korea. All of the stations had drainage ditches for underground water under the platform, as well as heating, ventilation, and air conditioning systems. Air samples were taken two or three times at each station at a nominal height of 100 cm (50–150 cm) above the platform floor. Samples were collected through polycarbonate membrane filters to facilitate particle sample collection (filter pore size 0.4 μm, three-piece cassettes measuring 37 mm in diameter; Nuclepore Corp., Cambridge, MA, USA) at a flow rate of 2 L min−1 (1.98–2.23) for 60 min, using an air sampler (Escort LC Pump; Mine Safety Appliances Company, Pittsburgh, PA, USA) (NIOSH 1998). The size of bacteria is approximately 1–5 μm in diameter; therefore, the filter pore size used here (0.4 μm) is sufficiently small for collection of significant microbes (ACGIH 1999). During each sampling period, the temperature and relative humidity were recorded three times. The samples were delivered to an analytical laboratory within 24 h after sampling and were analyzed immediately after arrival.
To extract bacteria from the filter samples, 1.5 mL sterile peptone water (0.1 % w v -1 containing 0.01 % Tween 80) was pipetted onto the support pad through the cassette outlet, after which the connection was plugged. Next, 5 mL of sterile peptone water was transferred through the inlet, and the cassette was capped and vigorously shaken for at least 30 min. After shaking, the suspension was extracted with a syringe.
Tryptone soy agar was used as the culture medium for CABs. Plates were incubated at room temperature (25 °C) for more than 2 days, and the number of colony forming units (CFUs) was determined. The concentration of CABs has been expressed as colony forming units per cubic meter. Values below the detection limit were considered to be 3 CFU m-3. Values below the detection limit were assigned a value of the limit of detection (LOD)/√2 (Hornung and Reed 1990).
Bacteria isolated from the colonies were initially characterized according to cell morphology and Gram staining. Bacteria were further characterized using the VITEK® 2 XL system (bioMerieux, Inc., Marcy l’Etoile, France). Gram-negative (GN) bacteria were identified using the VITEK 2 GN card and subjected to antimicrobial susceptibility testing (AST) using the VITEK 2 AST-P580 and AST-N093 cards. Gram-positive (GP) bacteria were identified using the VITEK 2 GP card. In total, 10 % of the integrated samples were reserved for blank tests, and all of the results were below the detection limit.
Statistical analyses
Nonparametric analysis was used to test for statistically significant differences in CAB concentrations. The Kolmogorov-Smirnov analysis was performed to determine whether the CAB concentrations varied according to the presence or absence of a ventilation system. Spearman correlation analyses were used to assess the relationship between CAB concentrations and the other environmental factors. All statistical analyses were carried out using the SPSS software package (version 17.0).
Results
Table 1 summarizes the concentrations, species, and distributions of CABs in the subway stations. CAB concentrations ranged from 3 to 1952 CFU m−3 (average for all stations, 308 CFU m−3). Both GP bacteria (Micrococcus spp., Kocuria rosea, Corynebacterium jeikeium, Staphylococcus hominis, S. hominis spp., Staphylococcus saprophyticus, Staphylococcus cohnii, Bacillus spp., Staphylococcus epidermidis, Clostridium histolyticum, and Diphtheroides) and GN bacteria (Sphingomonas paucimobilis, Acinetobacter ursingii, Acinetobacter lwoffii, Moraxella spp., and Moraxella catarrhalis) were identified in the air samples.
Spearman’s correlation coefficients were calculated to evaluate whether there were associations between CAB concentrations and station temperature, relative humidity, depth, and year of construction (Fig. 1). We found that there was a significant correlation between CAB concentration and temperature (r = 0.45, p < 0.01), construction year (r = −0.52, p < 0.01), and depth of the station (r = −0.65, p < 0.01). However, CAB concentrations were not significantly correlated with relative humidity.
Table 2 shows a comparison of CAB concentrations in subway stations with or without ventilation. CAB concentrations in stations with operating ventilation systems, which served an average of 2856 passengers, were significantly lower than CAB concentrations in stations without ventilation systems, which served an average of 2834 passengers (p = 0.001). Most of the CAB concentrations were higher in stations without ventilation systems than in those with ventilation systems (Fig. 2).
Discussion
In this study, we measured the concentrations of CABs in subway stations of the Seoul Metro system. Interestingly, our results indicated that the CAB concentrations in subway stations were lower in 2013 than in previous years (Hwang et al. 2010). In line with this, Seoul Metro has been making an effort to improve the air quality of the underground indoor environment by monitoring air quality, installing highly efficient air conditioners, and improving aged ventilation facilities since 2007 (Seoul Metro 2012). However, CAB concentrations in two of the 16 stations (12.5 %) exceeded 800 CFU m−3, the accepted indoor level of airborne bacteria in subway stations, according to Korean guidelines (Ministry of Environment of Korea 2014). Thus, more work is still needed to improve air quality in underground subway stations. A previous study showed that the mean concentration of total airborne bacteria in subway station platforms was 134 CFU m−3, using a one-stage viable particulate cascade impactor for 10 min (Kim et al. 2011). Additionally, the study by Kim et al. (2011) did not detail changes in CABs according to environmental characteristics such as ventilation, depth, and year of construction, which are key determinants of airborne bacteria levels.
The maximum concentration of airborne bacteria in the community is governed by certain guidelines. For example, the guidelines for bioaerosols established by the National Institute of Occupational, Safety, and Health (NIOSH) states that bioaerosol concentrations must not exceed 1000 CFU m−3 (NIOSH 1998). Additionally, the Commission of the European Community (CEC) has classified bioaerosol concentrations below 500 CFU m−3 as low, those between 500 and 1000 CFU m−3 as intermediate, and those above 1000 CFU m−3 as high (CEC 1993). According to earlier studies, aggregated bacterial concentrations in 100 US office buildings were not elevated (indoor maximum 281 CFU m−3) (Tsai and Macher 2005). However, elevated bacterial counts, ranging from 600 to 1800 CFU m−3, were found at nine shopping malls in Hong Kong (Lee et al. 2002). Recommendations for improved ventilation are supported in a previous report of mold-damaged buildings, wherein airborne bacteria ranged from 14 to 1550 CFU m−3. In this study, the authors concluded that bacteria levels exceeding 600 CFU m−3 could be associated with insufficient ventilation or abnormal sources of microorganisms (Salonen et al. 2007).
The majority of isolated bacterial species belonged to the genus Micrococcus, followed by Staphylococcus, Kocuria, and Corynebacterium. Among these, Micrococcus and Staphylococcus accounted for 66 % of the total number of CABs identified. Micrococcus, Staphylococcus, and Corynebacterium, all of which included several species associated with an anthropogenic origin, were observed in almost all of the stations (Awad 2002; Seino et al. 2005; Kim et al. 2011). Hence, we concluded that anthropogenic sources of bacteria were major contributors to airborne bacteria in subway environments.
There was a significant correlation between CAB concentrations and station temperature, construction year, and depth. Temperature is a typical environmental factor influencing pathogenic agents (Heseltine and Rosen 2009), and our results were consistent with a previous study showing that higher CAB concentrations were significantly correlated with higher temperatures (Hwang et al. 2011). Moreover, we found a significant negative correlation between CAB concentrations and station construction year, which could be explained by the fact that older stations, built in the 1980s, were shallower than stations built in the 1990s. Similarly, the depth of the stations was significantly negatively correlated with CAB concentration, which may be related to the improvement of aged ventilation facilities since 2007 (Seoul Metro 2012).
The concentrations of CABs in stations with operating ventilation systems were significantly lower than those in stations without ventilation. This result is consistent with a previous study of university laboratories, which showed that the concentrations of microbes in laboratories with ventilation systems were significantly higher than those in laboratories without ventilation systems (Hwang et al. 2011). Ventilation is intended to remove or dilute the concentration of airborne microbes that can cause infectious diseases and to control the temperature and humidity. However, some poor ventilation systems have been associated with the prevalence of sick building syndrome (Seppanen and Fisk 2002). Better hygiene and the commissioning, operation, and maintenance of air-handling systems are particularly important in reducing the negative effects of ventilation systems (Mendell et al. 2008).
Other studies have found that the number of passengers is positively associated with the concentration of CABs in subway station environments, consistent with airborne microorganisms being dispersed into the air from subway passengers’ clothing and hair (Bogomolova and Kirtsideli 2009; Boudia et al. 2006; Cho et al. 2006). High concentrations of CABs in the morning and evening may be due to rush-hour commuter traffic in Korea. A similar study showed that the daytime levels of airborne bacteria at subway stations are higher than those at night (Dybwad et al. 2012). Moreover, changes in microbial communities between peak and nonpeak commuting hours can be largely attributed to increases in skin-associated genera (Leung et al. 2014) such as S. epidermidis, S. hominis, S. cohnii, Staphylococcus caprae, and Staphylococcus haemolyticus, which are present on human skin (Robertson et al. 2013). Our study suggested that supply of clean air via operational ventilation systems might reduce the concentration of CABs associated with high passenger load; indeed, the concentrations of CABs were lower in stations with ventilation, which had a higher average number of passengers than stations without ventilation. Another interesting finding of this study was that Acinetobacter spp. was only found in stations without ventilation. Acinetobacter is an important causative pathogen in nosocomial infections in healthcare settings (Horii et al. 2011). Hence, the presence of an operating ventilation system may help to reduce the presence of this GN bacterial species in enclosed subway stations.
One limitation of this study was that we were unable to measure the effectiveness of ventilation systems at various stations. Additionally, we sampled a relatively small number of sites, which may not be representative of all underground subway stations. Nevertheless, study showed that the overall concentrations of CABs were associated with environmental factors, such as station indoor temperature, relative humidity, depth, and construction year. We also found that an operating air supply system was critical for reducing the concentrations of CABs in the enclosed indoor environments of subway stations.
Conclusion
We measured the concentrations of CABs in 16 subway stations of the Seoul Metro system. The results showed that the concentrations of CABs in stations with ventilation systems were significantly lower than those in stations without ventilation systems. Thus, we suggest that all underground subway stations should have an adequate ventilation system. In particular, stations with a high level of passenger flow (over 2000 passengers per hour), such as stations b and p, could greatly benefit from a proper ventilation system, especially during commuting times (8–10 a.m. and 5–7 p.m.) and during the summer, when the ventilation system should be open and running at maximum power. It is important to check the supply of clean air regularly with a reliable device in order to monitor the concentrations of CABs and improve the air quality in underground subway stations.
References
American Conference of Governmental Industrial Hygienists (ACGIH) (1999) In: Macher J, Ammann HA, Milton DK, Burge HA, Morey PR (eds) Bioaerosols: assessment and control. American Conference of Governmental Industrial Hygienist, Cincinnati
Awad AHA (2002) Environmental study in subway metro stations in Cairo, Egypt. J Occup Health 44:112–118
Bogomolova E, Kirtsideli I (2009) Airborne fungi in four stations of the St. Petersburg underground railway system. Int Biodeterior Biodegrad 63:156–160. doi:10.1016/j.ibiod.2008.05.008
Boudia N, Halley R, Kennedy G, Lambert J, Gareau L, Zayed J (2006) Manganese concentrations in the air of the Montreal (Canada) subway in relation to surface automobile traffic density. Sci Total Environ 366:143–147. doi:10.1016/j.scitotenv.2005.09.094
Cho JH, Hee Min K, Paik NW (2006) Temporal variation of airborne fungi concentrations and related factors in subway stations in Seoul, Korea. Int J Hyg Environ Health 209:249–255. doi:10.1016/j.ijheh.2005.10.001
Commission of the European Communities (CEC) (1993) Indoor Air Quality and Its impact on Man, Report No. 12. Biological Particles in Indoor Environment, Luxemburg
Dybwad M, Granum PE, Bruheim P, Blatny JM (2012) Characterization of airborne bacteria at an underground subway station. Appl Environ Microbiol 78:1917–1929. doi:10.1128/aem. 07212-11
Goyal R, Kumar P (2013) Indoor–outdoor concentrations of particulate matter in nine microenvironments of a mix-use commercial building in megacity Delhi. Air Qual Atmos Health 6:747–757. doi:10.1007/s11869-013-0212-0
Heseltine E, Rosen J (2009) WHO guidelines for indoor air quality: dampness and mould. WHO Regional Office for Europe, Copenhagen
Horii T, Tamai K, Mitsui M, Notake S, Yanagisawa H (2011) Blood stream infections caused by Acinetobacter ursingii in an obstetrics ward. Infect Genet Evol 11:52–56. doi:10.1016/j.meegid.2010.10.011
Hornung RW, Reed LD (1990) Estimation of average concentration in the presence of nondetectable values. Appl Occup Environ Hyg 5:46–51
Hwang SH, Yoon CS, Ryu KN, Paik SY, Cho JH (2010) Assessment of airborne environmental bacteria and related factors in 25 underground railway stations in Seoul, Korea. Atmos Environ 44:1658–1662. doi:10.1016/j.atmosenv.2010.01.047
Hwang SH, Park DU, Ha KC, Cho HW, Yoon CS (2011) Airborne bacteria concentrations and related factors at university laboratories, hospital diagnostic laboratories and a biowaste site. J Clin Pathol 64:261–264. doi:10.1136/jcp.2010.084764
Kim KY, Kim YS, Roh YM, Lee CM, Kim CN (2008) Spatial distribution of particulate matter (PM10 and PM2.5) in Seoul Metropolitan Subway stations. J Hazard Mater 154:440–443. doi:10.1016/j.jhazmat.2007.10.042
Kim KY, Kim YS, Kim D, Kim HT (2011) Exposure level and distribution characteristics of airborne bacteria and fungi in Seoul metropolitan subway stations. Ind Health 49:242–248
Lee SC, Guo H, Li WM, Chan LY (2002) Inter-comparison of air pollutant concentrations in different indoor environment in Hong Kong. Atmos Environ 36:1929–1940
Leung HY, Wilkins D, Li KT, Kong KF, Lee KH (2014) Indoor-air microbiome in an urban subway network: diversity and dynamics. Appl Environ Microbiol 80:6760–6770. doi:10.1128/aem. 02244-14
Mendell MJ, Lei-Gomez Q, Mirer AG, Seppanen O, Brunner G (2008) Risk factors in heating, ventilating, and air-conditioning systems for occupant symptoms in US office buildings: the US EPA BASE study. Indoor Air 18:301–316. doi:10.1111/j.1600-0668.2008.00531.x
Ministry of Environment of Korea (2014) Indoor Air quality management in public facilities Indoor Air Quality Management Act Amendment
NIOSH (National Institute of Occupational, Safety and Health) (1998) Sampling and characterization of bioaerosols. NIOSH Manual Anal Methods 4:82–112
Robertson CE, Baumgartner LK, Harris JK, Peterson KL, Stevenss MJ, Frank DN, Pace NR (2013) Culture-independent analysis of aerosol microbiology in a metropolitan subway system. Appl Environ Microbiol 79:3485–3493. doi:10.1128/aem. 00331-13
Salonen H, Lappalainen S, Lindroos O, Harju R, Reijula K (2007) Fungi and bacteria in mould-damaged and non-damaged office environments in a subarctic climate. Atmos Environ 41:6797–6807
Seino K, Takano T, Nakamura K, Watanabe M (2005) An evidential example of airborne bacteria in a crowded, underground public concourse in Tokyo. Atmos Environ 39:337–341. doi:10.1016/j.atmosenv.2004.09.030
Seoul Metro (2012) Assessment of indoor air quality in Seoul Metro environment
Seppanen O, Fisk WJ (2002) Association of ventilation system type with SBS symptoms in office workers. Indoor Air 12:98–112
Smith KR (2008) WHO air quality guideline: moving indoors. Air Qual Atmos Health 1:17–18. doi:10.1007/s11869-008-0010
Son YS, Lim BA, Park HJ, Kim JC (2013) Characteristics of volatile organic compounds (VOCs) emitted from building materials to improve indoor air quality: focused on natural VOCs. Air Qual Atmos Health 6:737–746. doi:10.1007/s11869-013-0207-x
Tsai FC, Macher JM (2005) Concentrations of airborne culturable bacteria in 100 large US office buildings from the BASE study. Indoor Air 15(9):71–81
Zhang Z, Yu S, Wang Y, Wang X, Feng J, Ye B (2007) Ambient air quality of subway trains in Shenzhen. Chin J Public Health Eng 6:343–344
Zhou F, Wang Y (2013) Characteristics of antibiotic resistance of airborne Staphylococcus isolated from metro stations. Int J Environ Res Public Health 10:2412–2426. doi:10.3390/ijerph10062412
Author information
Authors and Affiliations
Corresponding author
Rights and permissions
About this article
Cite this article
Hwang, S.H., Park, W.M., Ahn, J.K. et al. Relationship between culturable airborne bacteria concentrations and ventilation systems in underground subway stations in Seoul, South Korea. Air Qual Atmos Health 9, 173–178 (2016). https://doi.org/10.1007/s11869-015-0316-9
Received:
Accepted:
Published:
Issue Date:
DOI: https://doi.org/10.1007/s11869-015-0316-9