1 Introduction

Reinforced concrete (RC) buildings represent a large portion of the built environment in many countries, including Italy and other Mediterranean earthquake-prone countries. While new buildings are designed according to state-of-the art seismic codes, older RC buildings were often designed for gravity loads only. Post-earthquake damage surveys and seismic vulnerability assessment studies on existing buildings frequently show outdated anti-seismic criteria and lack of detailing in both structural and non-structural elements. For these reasons, older RC buildings often displayed unsatisfactory seismic behavior during past earthquakes (e.g., Mw = 6.8 Southern Italy 1980, Mw = 6.3 L’Aquila 2009, Mw = 6.1 Emilia 2012).

In the 2009 L’Aquila earthquake, that caused a total of 197 fatalities in the urban centre of L’Aquila, more than 130 fatalities (66%) were due to RC buildings’ failures, even though the majority of buildings in the City center were masonry structures and only 30% were RC frames (Ricci et al. 2011; Del Gaudio et al. 2017a). Several older RC buildings suffered heavy structural damage and, in a few cases, there was total collapse (Braga et al. 2011).

Such extensive damage to structural and non-structural elements in RC buildings was not found in previous Italian earthquakes, also because of the limited percentage of RC structures in the building stock of the affected zones, characterized by old historical centers mostly made of masonry structures. For example, Braga et al. (1982) report that in the towns hit by the 1980 Irpinia earthquake (Ml = 6.9), only 13% of buildings had RC structure. In the 2002 Molise earthquake (Ml = 5.3) Decanini et al. (2002) report that out of the 662 RC building inspected most showed no or light damage: only 3.5% experienced damage level 2 according to the EMS 98 scale (ESC 1998), corresponding to moderate damage to non-structural elements.

In the more recent 2012 Emilia earthquake sequence, most of the damage observed in RC building was limited to the external layer of the two-leaf masonry infills typically found in older Italian RC buildings. Only few severe damage cases were reported, with brittle failures in RC elements caused by either column-infill interaction or by poor reinforcement details (Manfredi and Masi 2014).

After the August 24, 2016 Mw 6.0 Central Italy earthquake the authors carried out a reconnaissance survey of structural and non-structural damage outside the “red zone” (i.e. the totally collapsed historic city center) of Amatrice—the most epicentral town hit by the August 24 earthquake—with a specific focus on RC buildings (Santarsiero et al. 2016). Following the damage survey, a vulnerability and damage estimation model, based on a mechanical approach, was applied in order to compare surveyed and predicted damage distributions.

After a short description of the seismic event characteristics and an overview of the building types and of the seismic code evolution in the area under study, the paper presents the damage survey outcomes and the damage prediction model results.

2 Characteristics of the August 24, 2016 seismic event

On August 24, 2016 Central Italy was struck by an earthquake of magnitude Mw 6.0. Several buildings and infrastructures suffered severe damage, causing 299 casualties. In the months following this strong event, the area was hit by a long sequence with two additional strong events on October 26 (Mw 5.9) and October 30 (Mw 6.5) 2016, whose characteristics and effects are not discussed in the present paper.

Figure 1 shows on the left column the triaxial recorded signals at the AMT (Amatrice) station during the August 24, 2016 mainshock and on the right column the relevant pseudo-acceleration response spectra (for 5% damping). The soil type at the AMT site is classified as B according to NTC (2008). This station is at the Joyner-and-Boore distance from the rupture plane RJB = 1.4 km.

Fig. 1
figure 1

Recorded signals and corresponding elastic pseudo-acceleration response spectra (5% damping) for East–West EW (a, b), North–South NS (c, d) and up–down UD (e, f) directions, respectively

The signals were extracted from the Engineering Strong-Motion (ESM) database (Luzi et al. 2016), which provides data processed according to Paolucci et al. (2011). Peak ground acceleration, velocity and displacement (PGA, PGV and PGD, respectively) and integral (Housner intensity, IH) values of the triaxial signals recorded at the AMT station are reported in Table 1. More insight into the question can be found in Iervolino et al. (2016) where detailed information on the ground motion analysis of this event is reported.

Table 1 Peak (PGA, PGV and PGD) and integral (Housner Intensity—IH) parameter values for triaxial signals recorded at AMT station (soil class B)

Additionally, the Italian National Institute of Geophysics and Volcanology (INGV) published the ShakeMap of the event (http://shakemap.rm.ingv.it/shake/index.html). The map was generated using the ShakeMap® software package developed by the USGS Earthquake Hazards Program (Wald et al. 2006) in order to obtain maps of the peak ground motion parameters (Michelini et al. 2008). The data used to obtain the real-time maps is provided mainly by the INGV broadband stations, some of which paired with strong motion sensors, in addition to strong motion data obtained from the Italian Strong Motion Network (RAN). The peak ground motion parameters (e.g., PGA and spectral pseudo-acceleration for different periods of vibration) are determined through different ground motion prediction equations (GMPEs) and, for events with Mw > 5.5, on the basis of the relations by Ambraseys et al. (1996) and Bommer et al. (2000) for PGA and PGV, respectively. Figure 2a reports the ShakeMap of the August 24, 2016 event, with PGA values from 0 to 1.00 g along with the location of each geo-referenced RC building analyzed in the present work. In order to define the seismic input for the fragility curves shown later in the paper, at each building location the corresponding PGA value was extrapolated from the ShakeMap provided by INGV, as shown in Fig. 2b.

Fig. 2
figure 2

ShakeMap data of the August, 24 2016 earthquake—http://shakemap.rm.ingv.it/shake/index.html (a) and zooming in on the study area (b)

3 Analysis of building types and damage

According to the ISTAT (2011) census data, Amatrice has a total area of about 175 km2 and a population of about 2650 inhabitants. The total number of buildings is 5288: of these, 4103 have a residential use while the number of units occupied by at least one person is 1278.

As shown in Fig. 3a, 86% of residential buildings (3511) are masonry buildings (Mas), 5% are RC buildings (219), and 9% are made with other materials (373). Figure 13b shows that 12% of residential buildings is characterized by a single storey, 47% by two-storeys, 39% by three storeys and the remaining 2% by buildings with at least four floors. This is typical for an Italian small town such as Amatrice. Finally, 27% of residential buildings were built before 1919, 18% between 1919 and 1945, 43% between 1946 and 1980, and 12% after 1981 (Fig. 3c).

Fig. 3
figure 3

Distribution of structural typologies (a), number of storeys (b) and age of construction (c) according to ISTAT (2011) census data for the municipality of Amatrice

The RC buildings surveyed in this study are identified in Fig. 4 and are located just outside the historical centre of Amatrice.

Fig. 4
figure 4

RC buildings surveyed in the town of Amatrice. RC buildings are indicated by a “C” prefix and are progressively numbered from C1 to C37

Considering the dataset reported in the ISTAT (2011) database, the 37 RC buildings inspected represent about 20% of the whole RC building stock of Amatrice. If we assume that all RC buildings are newer than the town masonry buildings and considering the percentage of RC buildings in the whole building stock, it is likely that the vast majority of RC buildings were constructed after 1981. Table 2 reports the typological characterization of the surveyed buildings, with a short identification based on the buildings’ height and on the presence of infill panels within the external structural frames. In accordance with previous vulnerability studies (Masi 2003) three building types are considered in Table 2: frames without masonry infills (BF, bare frame), frames with regularly arranged masonry infills (IF, infilled frame) and frames without masonry infills at the ground floor (PF, pilotis frame). BF type, which represent buildings without effective infills (i.e. with infills having many and/or very large openings or badly connected to the structure so that their contribution to the strength and stiffness of the structure can be neglected), is completely absent in the surveyed building set. Most of the surveyed buildings are low rise (less than 3 storeys), about 25% have between 3 and 6 storeys and have infill panels at all levels (IF). There are only 2 buildings with more than 6 storeys.

Table 2 Building typological characterization of surveyed building stock

3.1 Present and past seismic hazard provisions for Amatrice and their implications

The seismic hazard provisions for Amatrice, their changes in recent decades and the Italian seismic design code evolution are briefly described in this section. Past and present seismic hazards provisions are used to evaluate the expected seismic capacity (with respect to the current seismic hazard code level and to the August 24, 2016 earthquake intensity) of existing RC buildings designed according to old technical standards.

The first Italian seismic zonation that included Amatrice dated back to 1927 (Regio Decreto Legge 431 1927). Two seismic areas were identified: Amatrice belonged to the area with lower seismicity (second category). Further, Regio Decreto Legge 431 imposed a limitation on the max number of storeys (three or four) and generally prescribed lateral storey forces equal to 1/10 the storey weight for structures up to 15 m high, and 1/8 for higher structures. Between 1930 and 1937, three seismic codes were introduced (Regio Decreto Legge 682 1930; Regio Decreto Legge 640 1935; Regio Decreto Legge 2105 1937). The main novelties were in the definition of the lateral seismic forces. The base shear coefficient (i.e. the ratio between the base shear due to the horizontal seismic loads and the building seismic weight) for the second category seismic areas was reduced from 0.10 (Regio Decreto Legge 431) to 0.05 in Regio Decreto Legge 640 (1935) and to 0.07 in Regio Decreto Legge 2105 (1937). These prescriptions were left in the 1962 code (Legge 1684 1962), that increased the maximum allowed number of storeys to seven.

The 1975 seismic code (DM 3/3/1975) introduced the structure dynamic properties in the design process. The effects of the seismic actions can be evaluated by means of static or dynamic analyses. In the static analysis, a triangular distribution of lateral forces is imposed, with the total seismic base shear Fh given by Eq. 1, where W is the total weight of the structural masses; R the response coefficient, that depends on the fundamental period of the structure (T), and is 1 for T ≤ 0.8 s and 0.862/T^(2/3) for T > 0.8 s; C represents the seismic action (Eq. 2), and is defined by means of S, the seismic intensity parameter; ε and β take into account, respectively, soil compressibility (ε = 1.00–1.30) and the possible presence of structural walls (β = 1.00–1.20).

$${\text{F}}_{\text{h}} = {\text{C}} \cdot {\text{R}} \cdot\upvarepsilon \cdot\upbeta \cdot {\text{W}}$$
(1)
$${\text{C}} = {{({\text{S}} - 2)} \mathord{\left/ {\vphantom {{({\text{S}} - 2)} {100}}} \right. \kern-0pt} {100}}$$
(2)

For Amatrice (second category seismic area), S was assumed equal to 9. If ε and β are taken equal to 1 (corresponding to stiff soil and absence of structural walls), for a structure with T ≤ 0.8 s Fh/W was equal to 0.07 (similarly to the 1937 code). Fh/W represents an inelastic design acceleration demand that implicitly includes a strength reduction factor that accounts for the structure dissipative capacity, similarly to what current technical codes do through the behavior factor q.

The 1986 and 1996 seismic codes (DM 24/1/1986; DM 16/1/1996) did not change the 1975 lateral force calculation procedure. However, the Limit State method was introduced for safety verifications and, at the Ultimate Limit State (ULS), the design accelerations were increased by a factor of 1.50. The first prescriptions based on to the performance-based seismic design approach were introduced in 1997 with a non-mandatory document (Circ. M.LL.PP. 65 1997).

In the 2003 seismic code (OPCM 3274 2003) and its 2005 revision (OPCM 3431 2005) an updated seismic input definition was introduced: elastic spectra on stiff soil (type A) were provided for each municipality, based on an updated national seismic hazard map. Note that soil identification substantially complies with the ground classification scheme provided in EC8 (CEN 2004). Amatrice was classified as first category with the highest PGA (0.35 g on ground type A for a 475 years return period design earthquake). The elastic spectrum was amplified depending on site-specific soil category and topographic conditions. The elastic spectrum was then reduced by the q factor value to obtain the inelastic design spectrum. OPCM 3274 introduced capacity design principles. This innovative code was mandatory for strategic buildings and infrastructures only and its impact on the construction practice has been minor.

The current Italian building code (NTC 2008) defines site specific PGA values for different design earthquake return periods TR based on the geographic coordinates of the site. For Amatrice (latitude 42.633; longitude 13.286), the PGA is 0.259 g on soil type A for TR = 475 years. This is the PGA value of the elastic design spectrum at the Life Safety Limit State for ordinary structures.

To give an idea of the maximum intensity values recorded during the August 24 event, the spectral characteristics of the elastic design spectrum provided by NTC (2008) are compared with those of the records of the AMT station reported in Fig. 1. Since the AMT station is on type B soil, the code prescribed PGA value is increased to 0.299 g. Figure 5a superimposes the elastic design spectrum for TR = 475 years and the spectra of the two horizontal ground motion components recorded at the AMT station. The spectral ordinates for the NS ground record exceed the code spectrum over a wide period range (up to approximately T = 1 s), whereas for the EW record the spectral ordinates are significantly higher than those of the code spectrum over a narrower period range (up to the end of the constant acceleration branch, corresponding to TC = 0.46 s)—which likely corresponds to the range of interest for 2–3 storey RC buildings—with peaks up to three times those of the code spectrum.

Fig. 5
figure 5

Comparison between elastic design spectrum for TR = 475 years (soil type B) according to NTC (2008) for Amatrice (lat: 42.633; lon: 13.286) and elastic spectra of the ground motions recorded at AMT station in the EW and NS directions (a); comparison between NTC (2008) inelastic design spectra with different behavior factors q and DM 3/3/1975 and DM 16/1/1996 inelastic design spectra at ULS for Amatrice (second category) (b)

Based on the above-reported considerations, a comparison is proposed between the current seismic demand and the capacity of existing buildings. It is assumed that the seismic capacity of structures designed according to old codes is equal to the seismic demand prescribed by these codes, in terms of inelastic acceleration spectra. The current seismic demand (and the minimum required capacity) can be represented by current inelastic acceleration spectra using the behavior factor values prescribed by NTC (2008) for the assessment of existing RC buildings. More specifically, current provisions prescribe that q varies between 1.5 and 3.0.

The minimum value is used for capacity checks of brittle mechanisms, whereas a value in the 1.5–3.0 range is prescribed in case of ductile mechanisms. Figure 5b displays the spectra for q = 1.5 and 1 = 3.0. As previously mentioned, the spectrum prescribed by the 1975 code (modified by the coefficient equal to 1.50 prescribed by the 1996 code in order to obtain a ULS spectrum comparable with current spectral demands) is characterized by a constant value of 0.105 g (= 0.07 × 1.50) for spectral ordinates between 0 and 0.8 s, which is the most likely range of interest for the RC buildings in Amatrice, based on the number of storeys (see Fig. 3). According to DM 3/3/1975, ε is 1.00 or 1.30, depending on the soil compressibility. Figure 5b reports both cases, since the soil type at the AMT station is non-stiff (namely type B soil).

Figure 5b clearly shows that in the 0–0.8 s period range the current seismic demand is generally significantly higher than the seismic capacity required by the older seismic code, for both q = 1.5 and q = 3.0, irrespective of the soil-dependent ε value.

Considering that from Fig. 5a it is reasonable to assume that in the same period range the demand deriving from the August 2016 earthquake significantly exceeds that of the current Italian code and, even more, it is likely to have largely exceeded the capacity required by the older codes. Thus, it can be roughly concluded that the RC buildings of Amatrice designed according to older codes most likely exceeded the Life Safety Limit State during the August 2016 earthquake. However, difficulties arise in this comparison mainly due to uncertainties in: (1) assessing failure mechanisms (brittle or ductile) controlling the seismic capacity due to the absence of capacity design principles in older seismic codes, and (2) selecting the proper q value. In the case of a ductile failure, moreover, the fact that the demand exceeds the capacity simply indicates that the expected ductility demand is higher than the ductility capacity implicitly assumed by the current code for existing buildings. This assumption may underestimate the actual ductility capacity of the building. Finally, it should be noted that the previous considerations may lead to a conservative evaluation of the capacity provided by codes since they do not consider:

  • The overstrength of buildings designed according to older codes;

  • The role of non-structural elements, such as masonry panels and their stiffness/strength contribution (see Sect. 4).

3.2 Examples of surveyed damage

In this section some examples of structural and non structural damage to RC structures in Amatrice, observed after the August 24 event, are reported. The authors carried out a reconnaissance survey in the municipality of Amatrice and gathered extensive photographic evidence of damage. Specifically, photographic documentation on 37 reinforced concrete buildings located outside the historical centre was collected in the days immediately following the August 24 mainshock (Santarsiero et al. 2016). In general terms, structural damage appears not so frequent and it seldom involves the whole structural system, while damage to non structural elements, mainly masonry infill panels, is heavy and widespread.

Two totally collapsed buildings were found in the surveyed area and are shown in Fig. 6 (top). The collapsed buildings are perfectly equal and, to the best of the Authors’ knowledge, were built at the same time, presumably during the ‘70s. A quick analysis of the collapsed buildings (Fig. 6, bottom, on the right) shows that the RC slabs were not well connected to the beams and the small size of one side of some column and beam members (i.e. 20 cm).

Fig. 6
figure 6

Images of two collapsed RC buildings before (top) and after (bottom, on the left) the August 2016 earthquake, with some details of buildings’ characteristics and damage (bottom, on the right)

As for the non-collapsed buildings, as already found in past earthquakes (e.g. L’Aquila 2009, Braga et al. 2011), damage frequently consisted of widespread cracking and/or collapse of the facade masonry infill panels (generally at the lower stories), sometimes accompanied by local damage in column members. Coherently with the design practice of the period (Braga et al. 2011), infills were generally made up of two layers (cavity walls), both of hollow brick masonry, having a total thickness of about 30 cm (external panel 12 cm, hollow space about 10 cm, internal panel 8 cm). Infills were inserted into the surrounding RC frame whilst paying scant attention to their connection to it. It was observed that in some cases the external layer was placed outside the structural frame and was not connected to the RC frame or to the internal masonry layer, also due to the presence of a thermally insulating panel between the two brick layers (this is a construction technique frequently found in older Italian RC buildings).

Figure 7 displays a damage scenario observed in several cases: infills totally collapsed at one level, with moderate damage to a limited number of beam-column joints (in some cases also due to inappropriate concrete casting).

Fig. 7
figure 7

Partial collapse of the masonry infills of the second level (left) and moderate damage to a beam-column joint (right)

Figure 8 shows a similar non-structural damage distribution for a taller building, where the infills are severely damaged at two levels (in the more flexible direction only).

Fig. 8
figure 8

Partial collapse of infill panels at the second and third storey

Figures 9 and 10 show another typical mechanism found in several buildings, with heavy damage at column ends to be partially ascribed to masonry infill-column interaction, particularly in the building in Fig. 10 where stone masonry infills are present. Generally, damage affects lateral columns (Fig. 9) and, in some cases, also internal columns (Fig. 10).

Fig. 9
figure 9

Damage to the brick masonry infill (left) and details of the column damage (right)

Fig. 10
figure 10

Damage to the stone masonry infill (left) and details of the column damage (right)

4 Building damage scenario and comparison with observed data

Due to the large number of structures that is analyzed when preparing damage scenarios, simplified methods are needed. Several mechanics-based models carry out a simplified evaluation of the nonlinear static response of the building. Among these, some are based on the displacement-based method (Priestley 1997), such as Calvi (1999). The development of this procedure led to the displacement-based earthquake loss assessment (DBELA) method (Pinho et al. 2002; Glaister and Pinho 2003; Crowley et al. 2004, 2006) and to the simplified pushover-based earthquake loss assessment (SP-BELA) method (Borzi et al. 2008). The two previous methods are based on the definition of a pushover (PO) curve using a simplified mechanics-based procedure. In Iervolino et al. (2007) the seismic risk of building classes is evaluated applying the capacity spectrum method (CSM), that relies on static PO analyses on building models generated through a simulated design procedure. In all of these methods, uncertainties are taken into account by treating several input parameters as random variables. The CSM method is implemented in HAZUS (FEMA 2001; Kircher et al. 1997a, b; Whitman et al. 1997) to compute fragility curves—including damage state (DS) threshold capacities and associated variability—based on capacity curves defined for different building typologies.

Several studies on damage scenario evaluations were published following the 2009 L’Aquila earthquake. Some studies report damage predictions for the whole building stock (e.g. Bernardini et al. 2010; Sabetta et al. 2013), while others present single-building damage scenarios. Among these, D’Ayala and Paganoni (2011) analyzed the response of residential masonry buildings in the historic city center of L’Aquila and in the villages of Paganica and Onna. They report an EMS-98-based damage classification for each building and compare the predicted collapse mechanism (D’Ayala and Speranza 2003) and the extent of damage (D’Ayala 2005). A good agreement between observed and predicted damage is found. Fiorini et al. (2012) applied the SP-BELA procedure to the 2009 L’Aquila earthquake to generate damage scenarios both at regional and at local scale, using census data or single-building data collected by Tertulliani et al. (2011), respectively. A correlation between the Limit States adopted in SP-BELA and the damage evaluation outcomes provided by the Italian Department of Civil Protection through the AEDES forms (Agibilità e Danno nell’Emergenza Sismica, usability and damage in post-earthquake emergency—Baggio et al. 2007) is assumed. In Biondi et al. (2012) a comparison of in situ post-earthquake survey (via AEDES forms) and Seismic Code Hazard was carried out showing a good correlation. In De Luca et al. (2015) empirical fragility curves for EMS-98 DSs were derived from a database of RC buildings located in Pettino (L’Aquila), and the simplified spectral-based mechanical procedure FAST (De Luca et al. 2013) was used to derive analytical fragility curves at the same DSs.

As for more recent Italian earthquakes, the damage scenarios presented by Verderame et al. (2014) for RC buildings hit by the Emilia 2012 earthquake were obtained through the analysis of benchmark structures assumed as representative of the whole building stock. A seismic capacity assessment is carried out on the benchmark structures within the N2 spectral assessment framework at different DSs defined according to a mechanical interpretation of the EMS-98 scale. The models explicitly include the infill panels’ contribution to the structural response. Finally, in Del Gaudio et al. (2016, 2017b) EMS-98-based damage scenarios were derived for the same database used in De Luca et al. (2013) and for a wider version, respectively, through the POST (Del Gaudio et al. 2015) simplified mechanical procedure. Fragility curves were derived for each single building in the database. A very good agreement is reported between predicted and observed damage. Since the POST procedure is used in this study, more details on this procedure are provided in the following section.

4.1 The POST method

The simplified mechanical method POST (PushOver on Shear Type models) for seismic vulnerability assessment of RC buildings is presented and briefly described; for further details, the reader is referred to (Del Gaudio et al. 2015, 2016). POST is based on the following steps (summarized in Fig. 11):

Fig. 11
figure 11

POST method: building model, non-linear static response and seismic capacity assessment

  1. 1.

    Definition of building model the structural model of the building is created through a simulated design procedure in compliance with design code prescriptions, professional practice and seismic classification of the selected area at the time of construction. Further details can be found in Verderame et al. (2010);

  2. 2.

    Non-linear static response the evaluation of the non-linear static response of the building is performed through a simplified shear-type frame model. RC columns and infill elements respond in parallel: a tri-linear shear-displacement envelope is used for the RC columns and the multi-linear model by Panagiotakos and Fardis (1996) describes the infill panels’ shear-displacement response. The PO curve is obtained from a force-controlled procedure up to the peak strength and using a displacement-controlled procedure thereafter. The storey with the largest interstorey shear demand to shear strength ratio will be the only one to reach its peak strength and to continue onto the softening post-peak behavior;

  3. 3.

    Definition of DSs the DSs are defined according to the damage classification proposed by the European Macroseismic Scale EMS98 (Grünthal 1998);

  4. 4.

    Seismic capacity assessment the SPO2IDA (Vamvatsikos and Cornell 2006) frame-work is applied to evaluate the seismic capacity at the performance levels of interest in terms of spectral intensity measures;

  5. 5.

    Evaluation of fragility curves depending on the knowledge level of the building, a few parameters (m) are treated as random variables (for details see Table 4 at Sect. 4.2). A Monte Carlo simulation is then performed to create a population of buildings. For each run, an n-vector with the n realizations of each random variable is extracted from the relevant distributions to generate a building model. In each run the non-linear static response of the building model is computed. The displacements corresponding to predefined DS values are determined and the seismic capacity assessment is performed in terms of spectral ordinates and PGA values. The PGA capacity at a given DS is calculated for all generated buildings, and the corresponding cumulative frequency distributions provide the fragility curves.

Different configurations of infill panels can be considered: (1) solid, (2) with window openings, and (3) with door openings. Depending on the opening sizes, the non-linear behavior of the infill panels is modified according to the model by Kakaletsis and Karayannis (2009). Internal partitions are modeled through a shear-displacement relationship modified from that of the external panels to consider the different boundary conditions. More specifically, the post-cracking hardening of the multi-linear model by Panagiotakos and Fardis (1996) is replaced by a constant branch. As for the internal partitions, only solid- and with door opening-panels are considered. The internal partitions’ thickness is set equal to 100 mm, while for external panels it varies randomly in the 200÷240 mm range (see Table 4).

A fundamental issue in the POST method is the DS definition. The qualitative description of the observational DSs reported by the EMS-98 damage classification are transformed into displacement thresholds—such as the interstorey drift ratio (IDR)—for the building structural model. The infill panels’ capacity (\({\text{IDR}}_{{{\text{IP}},{\text{DS1}}}}\), \({\text{IDR}}_{{{\text{IP}},{\text{DS2}}}}\), \({\text{IDR}}_{{{\text{IP}},{\text{DS}}3}}\)) is defined according to the IDR limits proposed in Colangelo (2013).

In order to evaluate the RC columns’ IDR capacity, the expected failure mode has to be determined through the comparison between the flexural plastic shear and the shear strength. The former is evaluated from the plastic moment My as Vy = My/0.5 h. The column shear strength Vn is computed according to the shear strength model proposed by Sezen and Moehle (2004). A coefficient k that expresses the maximum ductility-related shear strength decrease is defined. It is assumed to be equal to 0.7 according to the authors’ suggestion. Columns with (Vy/Vn) < k are expected to fail in flexure, while columns with (Vy/Vn) ≥ k are expected to fail in shear or flexure–shear.

Hence, different IDR capacities are evaluated based on the qualitative descriptions of the EMS-98 DSs, as a function of the expected failure mode of the columns (left column of Table 3 for F-columns and right column for S-columns):

Table 3 Displacement thresholds at the assumed DSs, based on the mechanical interpretation of the DSs described by EMS-98
  • DS1: IDR at the column cracking moment (\({\text{IDR}}_{{{\text{RC}},{\text{cr}}}}\));

  • DS2: IDR at the column yield moment (\({\text{IDR}}_{{{\text{RC}},{\text{y}}}}\));

  • DS3: IDR corresponding to concrete cover spalling (\({\text{IDR}}_{{{\text{RC}},{\text{s}}}}\)) or longitudinal reinforcement buckling, (\({\text{IDR}}_{{{\text{RC}},{\text{b}}}}\)) (for columns failing in bending) or shear failure (\({\text{IDR}}_{{{\text{RC}},{\text{SF}}}}\)) according to the Aslani and Miranda (2005) model;

  • DS4-5: IDR corresponding to the zero-strength point (\({\text{IDR}}_{{{\text{RC}},{\text{pc}}}}\)) of the first column on the degrading backbone curve of the Haselton et al. (2008) model (for columns failing in bending) or to the loss of the axial load carrying capacity (\({\text{IDR}}_{{{\text{RC}},{\text{A}} - {\text{SF}}}}\)) of the first column (for columns failing in shear).

The above DS definitions are summarized in Table 3. Note that, due to the assumed shear-type behavior, the IDR of each DS is the minimum between the values reported in Table 3 for infill panels and RC columns. The capacity in terms of spectral ordinate Sa(T) is assessed through an approximate IDA curve, evaluated according to the SPO2IDA framework (Vamvatsikos and Cornell 2006) for the IDR value corresponding to the assumed DS. The corresponding PGA capacity is evaluated as a function of the elastic pseudo-acceleration response spectrum following the procedure by Bird et al. (2004) already applied in Del Gaudio et al. (2017b). The spectral shape is obtained from the spectral ordinates provided by ShakeMap—PGA, Sa(0.3s), Sa(1s), Sa(3s)—at selected site.

The steps I to IV (i.e. up to the seismic capacity assessment) are repeated through a Monte Carlo simulation to generate a population of buildings. For each run a different building model is created and a non-linear static response is performed. DSs and corresponding IDR values are determined on the building response curve and seismic capacity assessment is carried out in terms of spectral ordinates and PGA values. At the end of the Monte Carlo simulation, the cumulative frequency distributions of PGA values for the different DSs provide the corresponding building fragility curves. The fragility curves, together with the PGA values obtained from the ShakeMap of the reference earthquake, allow to define the damage scenario for the investigated building dataset, as reported in Fig. 12. More specifically, the intersections between the fragility curves and the PGA values allow to compute the probabilities of having a given DSi (\(\Pr \left[ {{\text{ds}} = {\text{DS}}_{\text{i}} |{\text{PGA}}} \right]\)). This procedure is repeated for all DSi on all buildings of the dataset. Summing up all the probabilities of having a given DSi for all the buildings leads to the damage distribution for the considered building dataset:

  • The distribution of damage provides the number of buildings that fall in each DSi, i = 0:5, (\({\text{N}}\left[ {{\text{ds}} = {\text{DS}}_{\text{i}} } \right]\));

  • The cumulative distribution of damage provides the number of buildings with a damage state DSi or higher (\({\text{N}}\left[ {{\text{ds}} \ge {\text{DS}}_{\text{i}} } \right]\)).

Additional details on the procedure can be found in Del Gaudio et al. (2015, 2016, 2017b).

Fig. 12
figure 12

Conceptual representation of the procedure for deriving damage scenarios for the entire building dataset starting from the seismic fragility assessment of single buildings

4.2 Damage assessment of selected RC buildings using the POST method

The POST method was applied to the 37 RC buildings selected and surveyed in Amatrice. The geometric dimensions of the buildings (Lx, Ly and number of storeys) are evaluated from the survey and are considered deterministic. Coherently with the survey, the buildings result roughly symmetric in plan (in both horizontal directions). The buildings’ structural models are defined through a simulated design procedure that follows the design practice and seismic prescriptions at time of construction. The beam and column dimensions and the relevant transverse and longitudinal reinforcements are evaluated following the procedure proposed by Verderame et al. (2010). Since Amatrice was classified in seismic zone II by Regio Decreto Legge 431 (1927) all buildings were designed considering both gravitational and seismic loads, considering the different technical codes’ prescriptions throughout the years (see Sect. 3.1).

The random variables considered in this paper are listed in Table 4, in addition to the parameters of the distributions required for their definition. Specifically, the random variables considered in this study are: concrete compressive strength, fc; longitudinal and transverse reinforcement yield strength, fy; mechanical characteristics of infill panels, (Ew, sw); all the displacement thresholds of Table 3; spectral shape and record-to-record variability.

Table 4 Summary of median and CoV values for the selected random variables

Data collected from the in situ survey was processed to derive the distributions of the building main geometrical and typological parameters, as reported in Fig. 13. The database contains information about geometrical, typological and morphological characteristics of the surveyed buildings (number of storeys, building area, age of construction), in addition to information regarding damage observed in structural and non-structural components (namely RC columns and infill panels).

Fig. 13
figure 13

Distribution of: a number of storeys; b Lx/Ly ratio; c average plan surface

Damage levels are firstly evaluated following the approach reported at Sect. 4 (damage to structural elements and existing short term countermeasures) of the AEDES survey form separately for vertical structures (VSs) and infills/partitions (IPs). A four-level classification scale is considered: D0 no damage, D1 slight damage, D2–D3 mediumsevere damage, D4–D5 very heavy damage. Furthermore, information about the extent of damage is also considered, using the AeDES three level scale, based on the percentage of elements affected by a given damage level (< 1/3; between 1/3 and 2/3; > 2/3). This data is available for all 37 RC buildings. As a result, 86% of buildings have no damage in VSs, while 3 and 11% have a medium–severe (D2–D3) and severe damage (D4–D5), respectively. On the other hand, damage to IPs is more severe and widespread: 35% of buildings are characterized by no damage (D0), 30% by slight damage (D1), 16% by medium–severe damage (D2–D3) and 19% by severe damage (D4–D5). Assuming the damage level D as the higher between that of VSs and IPs, Fig. 14a displays the Ds distribution for the 37 Buildings, showing that 36% of buildings are affected by no damage (D0), 28% by slight damage (D1), 17% by medium–severe damage (D2–D3), and 19% by severe damage (D4–D5). It is worth noting that the damage distribution is substantially dependent on the damage to IPs, thus confirming the key role played by non-structural elements in assessing damage in RC frame buildings.

Fig. 14
figure 14

Distribution of surveyed damage for the 37 RC buildings under study: a damage levels (Ds) directly obtained from AeDES survey forms; b damage states (DSs) defined according to EMS-98 damage classification

Damage data collected according to the AeDES survey forms are further elaborated considering the six DSs given in the the EMS-98 scale (DS0 “No damage”; DS1 “Negligible to slight damage”; DS2 “Moderate damage”; DS3 “Substantial to heavy damage”; DS4 “Very heavy damage”; DS5 “Destruction”). To this end the approach proposed by Rota et al. (2008) for the VSs is followed, while the approach proposed by De Luca et al. (2013) and Del Gaudio et al. (2016) is used for the IPs. As a result, two different DSs, one for the VSs, the other for the IPs, are generally obtained for each building, therefore the higher one is assumed as the building DS. Figure 14b shows the related DS distribution for the 37 buildings. It should be noted that most of the buildings have damage between DS0 (35%) and DS1 (30%), while 16% of buildings has DS2, and lower percentages are found for DS3 (8%) and DS4-5 (11%).

Figure 15 shows the damage distribution estimated by the POST procedure on the basis of the seismic input reported in the ShakeMaps. In the same Figure the comparison with the observed damage distribution deriving from AeDES survey form evaluated according to the EMS-98 classification (see Fig. 14b) is reported. Large differences are found for no damage (DS0) and for heavy damage (DS3), while for the other DSs the agreement appears reasonably good, also taking into account the small number of buildings in the sample under study. Specifically, POST predicts a smaller number of buildings for the extreme damage states (DS0 and DS4-5), and a greater number of buildings for the intermediate DSs. With regard to the difference for DS4-5, it should be considered that the damage examples reported at Sect. 3.2 (see Fig. 6) show the presence of very poor details in collapsed buildings.

Fig. 15
figure 15

Comparison between observed (AeDES) and predicted (POST) damage distributions for the 37 RC buildings

A global comparison can be made on the basis of mean damage index DImed as defined in (Masi et al. 2015):

$$DI_{med} = \frac{{\sum\nolimits_{i} {(DS_{i} \cdot f_{i} } )}}{n}$$

where DSi is a generic damage state (DSi = 1–4), fi is the related frequency. The summation is carried out for n = 4, i.e. No damage state DS0 is not included. In this way, DImed varies between 0 and 1, where DImed = 0 means total absence of damage and DImed = 1 means total destruction.

A slightly higher DImed value is computed for POST results with respect to AeDES data, i.e. 0.42 versus 0.32. Therefore, globally, POST appears slightly conservative thus confirming the tendency of the analytically-derived models to be more conservative than the observed damage (e.g. Colombi et al. 2008; Masi et al. 2015).

5 Conclusions

Damage and vulnerability assessment of 37 RC buildings, located outside the historical centre of Amatrice, was carried out after the Mw6.0 August 24, 2016 Central Italy earthquake. Most buildings (86%) were reported to have slight or no structural damage according to the field survey based on AeDES forms (quick Italian Civil Protection Department survey form), while 3 and 11% had medium–severe (D2–D3) and severe (D4–D5) damage, respectively. Based on the same information, damage to infills and partitions is more severe and widespread. More specifically, 35% of buildings are characterized by no damage (D0), 30% by slight damage (D1), 16% by medium-severe damage (D2–D3) and 19% by severe damage (D4–D5).

The behavior of RC buildings during the Amatrice earthquake reflects the damage observed during recent Italian earthquakes: the infills frequently suffer heavy damage, mainly located at the lower stories, and there is a significant interaction with the surrounding RC structure that causes, in some cases, severe damage to column members. Considering the earthquake severity, as shown by the high spectral accelerations’ values discussed in the paper, it can be concluded that most of the 37 RC buildings generally behaved well with respect to the life safety requirements. Some exceptions have been found and pointed out in the paper.

Availability of post-earthquake damage survey data allowed the application of the POST method, a procedure developed by some of the Authors to predict damage scenarios. The comparison between observed and POST-estimated damage distributions shows an overall good agreement, with a slightly conservative estimation of damage by POST, as already found in other studies based analytical models (e.g. fragility curves proposed by Masi et al. 2015). The comparison shows, on the one hand, the need to enhance the prediction capabilities of the POST method for higher damage levels (DS4-5 is the only level in which POST underestimates damage). On the other hand, it points out the potential of the analytically-derived models, and specifically of POST method, in large scale vulnerability assessments, thus becoming powerful tools in predicting damage distributions over large areas in a seismic risk mitigation framework.