Keywords

1 Introduction

The deep beam is a beam when effective span-to-depth ratio (a/d) is 4 or less as defined by ACI code [1, 2]. The Euro-International Concrete Committee defined deep beam if span length to hole depth (L/H) < 2 for simply supported beam and (L/H) < 2.5 for continuous beam [3], As shown in Fig. 1. Deep beam has various uses such as transfer deep girders, wall footing, foundation pile caps, bunkers, foundation beams, floor diaphragms, and shear walls. It fails usually by shear, there are two types of shear failure [4] (1-diagonal compression failure: occur nearly along the line joining the load point and the support point, 2-diagonal tension failure: occur by clean fracture near along the line joining support with the nearest loading point) as shown in Fig. 1.

Fig. 1
figure 1

Strut and Tie method details [5]

High temperature has significant effects on behavior and strength of deep beams. When temperature increases, in ultimate load and failure deflection are clearly decreasing [68]. In this paper, the deep beam models were analyzed by finite element analysis using ANSYS package, then the parametric study was carried out for the models (i.e., some factors are changed with respect to others) where three different factors are varying. The first one is temperature (T), and seven temperatures are considered (20, 100, 300, and 500) °C. The second factor is compressive strength \(\text{(}f_{c}^{{\prime }} )\), and five strengths are considered (30, 50, and 70) MPa. The third factor is load span-to-length (a/d) ratio, and three values are considered (1, 2, and 3). One hundred and five (105) samples are investigated to evaluate these changes.

2 Modeling

The model dimensions were the width (b = 100) mm, height (h = 225) mm, and length varied as (750, 1150, and 1550) mm, for a/d ratios (1, 2, and 3) respectively. The concrete cover was (25) mm in all specimens. The reinforcement configurations are the same for all the samples as shown in Fig. 2. Tables 1 and 2 show the details of the analyzed samples. Their results showed clearly the deterioration in properties and ultimate load with high temperature. Theoretical model is adequate by comparing it with experimental works from the literature research [9].

Fig. 2
figure 2

Deep beam specimen details

Table 1 Sample properties
Table 2 Thermal properties of tested specimen

3 Parametric Study of Elevated Temperature Effect

Seven stages in temperature are made in this study to evaluate the concrete behavior under different degrees of temperature for each compressive strength and (a/d) ratio. These temperatures are (20, 100, 300, and 500) °C. From Figs. 3, 4, 5, 6, 7, 8, 9, 10, and 11, the results show that by increasing the temperature for the samples, the load capacity and deflection at failure are decreased. Each curve shows the load–deflection relation for constant compressive strength and (a/d) ratio. Also, from these curves, it can be noticed that for a/d = 1, curves are not distinguished like curves with a/d = 3. That means with increasing length, deep beam samples will be more clear in the behavior [10, 11].

Fig. 3
figure 3

Load–deflection behavior for DT(#).30.1

Fig. 4
figure 4

Load–deflection behavior for DT(#).30.2

Fig. 5
figure 5

Load–deflection behavior for DT(#).30.3

Fig. 6
figure 6

Load–deflection behavior for DT(#).50.1

Fig. 7
figure 7

Load–deflection behavior for DT(#).50.2

Fig. 8
figure 8

Load–deflection behavior for DT(#).50.3

Fig. 9
figure 9

Load–deflection behavior for DT(#).70.1

Fig. 10
figure 10

Load–deflection behavior for DT(#).70.2

Fig. 11
figure 11

Load–deflection behavior for DT(#).70.3

The sample of specimens included as DT (temp. a/d), where DT means deep beam exposed to elevated temperature, (temp.) is the value of temperature (°C), (compressive strength of concrete (MPa), (a/d) shear span-to-effect depth ratio. The mark (#) means various values of a parameter which is studied.

For specimens having concrete compressive strength more than 40 MPa, the behavior of samples with a/d = 1 will be more distinguished just like a/d = 2 and a/d = 3. This means that for high-strength concrete, the effect of high temperature had less effect on concrete, not as for normal concrete.

4 Effect of Concrete Compressive Strength

In this study, five types of models are considered to evaluate the behavior of concrete with respect to different temperature strengths. The five strengths are (30, 50, and 70) MPa. They are selected to show the behavior of normal, moderate, and high-strength concrete. Figures 12, 13, 14, 15, 16, 17, 18, 19 and 20 show this behavior. The results show that by increasing the compressive strength for the samples, the load capacity and deflection at failure are increased with the same (a/d) ratio and same temperature (Figs. 21, 22 and 23).

Fig. 12
figure 12

Load–deflection behavior for DT20.(#).1

Fig. 13
figure 13

Load–deflection behavior for DT20.(#).2

Fig. 14
figure 14

Load–deflection behavior for DT20.(#).3

Fig. 15
figure 15

Load–deflection behavior for DT100.(#).1

Fig. 16
figure 16

Load–deflection behavior for DT100.(#).2

Fig. 17
figure 17

Load–deflection behavior for DT100.(#).3

Fig. 18
figure 18

Load–deflection behavior for DT300.(#).1

Fig. 19
figure 19

Load–deflection behavior for DT300.(#).2

Fig. 20
figure 20

Load–deflection behavior for DT300.(#).3

Fig. 21
figure 21

Load–deflection behavior for DT500.(#).1

Fig. 22
figure 22

Load–deflection behavior for DT500.(#).2

Fig. 23
figure 23

Load–deflection behavior for DT500.(#).3

For (a/d = 1) and temperature (20) °C, the increase of compressive strength about (3.5) times leads to an increase in ultimate load about (1.90) times. But for temperature (250) °C, the ultimate load increases to about (2.61) times. And for a temperature of (500) °C, the ultimate load increases to about (2.2) times.

That means by increasing the temperature, the percentage of ultimate load increases and then decreases as shown in Fig. 24. Because, at first, the water in the open voids is drying, so the disjoining pressure is going away and increase the strength of the concrete that leads to the increase in the ultimate load [8, 1214]. Then with temperature raises, the water in closed voids is drying leading to thermal shrinkage and the strength decreases that reduces the ultimate load.

Fig. 24
figure 24

Ultimate load percentage with temperature

5 Effect of Length to Effective Depth Ratio (a/d)

For this study, three types of models are evaluated for analyzing the behavior of deep beams for different (a/d) ratios. These ratios are (1, 2, and 3). Figures 25, 26, and 27, show that the load capacity decreases and deflection at failure increases with the increase in the (a/d) ratio. This means that deep beams behave like normal beams with increasing in length. In addition, increase in midspan deflection can be noticed when the length increases [5].

Fig. 25
figure 25

Load–deflection behavior for deep beams have fc′ = 30 MPa

Fig. 26
figure 26

Load–deflection behavior for deep beams have fc′ = 50 MPa

Fig. 27
figure 27

Load–deflection behavior for deep beams have fc′ = 70 MPa

6 Artificial Neural Networks by MATLAB and SPSS for the Proposed Model

6.1 Introduction

Due to the difficulty of analytical solutions for thermal analysis of concrete members, the results of parametric study are simulated using artificial neural networks (ANNs) to evaluate the proposed model that can be used to estimate the ultimate load of R.C. deep beams subjected to elevated temperature. The ANNs model is worked using MATLAB and SPSS facilities.

6.2 Neural Network by MATLAB of Proposed Model

In order to find the percentage of error and the efficiency of the proposed model, the results are divided into input matrix and output matrix, then dealing with neural network (ANN) with training (80%), testing (10%), and validation (10%). The error (R) was (0.99) and the square value was (R2 = 0.98). So, the model is efficient and the error is very small. So that, the models from the parametric study can be used for making the relation curves between inputs (temperature, compressive strength, and a/d ratio) and output (ultimate load) [1518]. Figures 28 and 29 show neural network results.

Fig. 28
figure 28

Error histogram for the models

Fig. 29
figure 29

Regression for the models

6.3 Proposed Model of R.C. Deep Beams Including Temperature Effect

The results of the parametric study for (105) specimens have been given as input in SPSS Skelton, eight properties that were changed in the specimens were taken and analyzed in neural networks simulations. The output window shows the results for the models with different details as well as the error percentage, and the weights (this is the most important in this study). From the weights, the equation for the ultimate load can be written. The figures show the results as shown in Tables 3, 4, 5, and 6; also, the Figs. (30, 31, and 32). All these results are illustrated and summarized the validated data for a proposed model of this study.

Table 3 Case processing summary
Table 4 Model summary
Table 5 Independent variable importance
Table 6 Parameter estimates
Fig. 30
figure 30

Finite element versus predicted results of max flexural capacity loads

Fig. 31
figure 31

Normalized importance of ANN Model

Fig. 32
figure 32

The skeleton of the modeling

The most important result is the last figure that shows the skeleton of the modeling and the last table that shows the parameter weights that are given as input in the equation. The equation is

$$y = \frac{1}{{1 + e^{{ - \theta_{2} + w_{7} \tan h\left( x \right)}} }}$$
(1)

where

$$x = \theta_{1} + \sum\limits_{n}^{i = 1} {w_{i} v_{i} }$$
(2)

In this study, x is

$$\begin{aligned} x & = 0.232 + \left( {0.172\text{ * }f_{c}^{'} } \right) + \left( {0.182\text{ * }E_{c} } \right) - \left( {0.641\text{ * }f_{t} } \right) + \left( {0.182\text{ * }\frac{a}{d}} \right) \\ & \quad - \left( {0.359\text{ * }T} \right) + \left( {0.17\text{ * }E_{\text{sl}} } \right) - \left( {0.042\text{ * }E_{\text{sv}} } \right) \\ \end{aligned}$$
(3)

where

\(f_{t}\) :

splitting strength of concrete (MPa)

\(\frac{a}{d}\) :

effective length span-to-depth ratio

\(T\) :

temperature (°C)

\(E_{\text{sl}}\) :

modulus of elasticity for longitudinal steel reinforcement (MPa)

\(E_{\text{sv}}\) :

modulus of elasticity for vertical steel reinforcement (MPa)

So Eq. (1) is

$$y = \frac{1}{{1 + e^{0.004 - 1.367\tan h\left( x \right)} }}$$
(4)

The values of ultimate load (y) from Eq. (4) are between (0–1) and not the real values. For getting the real values, variable weights must be corrected by using Eq. (5) as follows:

$$x = \frac{{x - x_{ \hbox{min} } }}{{x_{ \hbox{max} } - x_{ \hbox{min} } }}$$
(5)

So, the real ultimate load will be calculated from Eqs. (6) and (7) as follows:

$$y = \frac{230}{{1 + e^{0.004 - 1.367\tan h\left( x \right)} }} + 50$$
(6)

where y = Pestimate, and x is

$$\begin{aligned} x & = 0.232 + \left( {0.172\text{ * }\frac{{f_{c}^{\prime} - 20}}{50}} \right) + \left( {0.182\text{ * }\frac{{E_{c} - 21{,}153}}{{18{,}421}}} \right) - \left( {0.641\text{ * }\frac{{f_{t} - 2.77}}{2.41}} \right) \\ & \quad + \left( {0.182\text{ * }\frac{{\frac{a}{d} - 1}}{2}} \right) - \left( {0.359\text{ * }\frac{T - 400}{100}} \right) + \left( {0.17\text{ * }\frac{{E_{\text{sl}} - 117{,}090}}{{19{,}515}}} \right) - \left( {0.042\text{ * }\frac{{E_{\text{sv}} - 122{,}910}}{{20{,}485}}} \right) \\ \end{aligned}$$
(7)

The mean absolute percentage error (MAPE) is

$${\text{MAPE}} = {\text{ABS}}\left( {\frac{{P_{\text{actual}} - P_{\text{estimate}} }}{{P_{\text{actual}} }}} \right)$$
(8)

And, average accuracy percentage (AA%) is

$$\text{AA} = 100 - \text{MAPE}$$
(9)

The coefficient of correlation (R) and the coefficient of determination (R2) are shown in Table.

Name

Percentage

MAPE

76.20

AA

99.23

R

96.83

R 2

93.76

This means that the comparison between finite element models and ANN models are so good. This can be seen in Fig. 33.

Fig. 33
figure 33

Comparison between load from FEA and loads from SPSS

7 Conclusions

The following conclusions are drawn based on the numerical analysis:

  1. 1.

    Nonlinear finite element procedure using ANSYS features to simulate reinforced concrete deep beams subjected to elevated temperature is used.

  2. 2.

    For checking the efficiency of the models, using neural network error R was about (99%) and square error R2 (98%).

  3. 3.

    The deep beam samples that have compressive strength more than 40 MPa with a/d = 1, their behavior is more distinguished when a/d = 2 and a/d = 3. This means that for high-strength concrete, the effect of high temperature had less effect on concrete.

  4. 4.

    Deep beams having a/d = 1 and temperature (20) °C, compressive strength that increase by about (3.5) times lead to increase in ultimate load about (1.9) times. But for temperature (250) °C, the ultimate load increase about (2.61) times. And for temperature (500) °C, the ultimate load increase by (2.2) times.

  5. 5.

    This study takes deep means for behavior of concrete with temperature changes in seasons, or in the same day between day and night, and even in the same hour between outside and inside the room if (cooling/heating) turned on. In ACI code take the large factor of error as 40%, the results from these samples exceed half of it. That makes the temperature change an important factor for concrete durability.

  6. 6.

    For deep beams behavior, when the length increased lead to increase in midspan deflection. And by increasing the length the deep beams behave like normal beams.

Notations

Symbol

Descriptions

\(\beta_{t}\)

Open shear transfer coefficient

\(\beta_{c}\)

Closed shear transfer coefficient

\(f_{c}^{{\prime }}\)

Compressive strength (MPa)

\(f_{y}\)

Yield stress (MPa)

\(E\)

Young’s modulus (MPa)

\(E_{T}\)

Tangent modulus (MPa)

A

Area (mm2)

K

Thermal conductivity (W/m °C)

C

Specific heat (J/kg °C)

ρ

Density (kg/m3)