Abstract
The growing technology of solid-state circuit breakers (SSCBs) has been reported as one of the driving factors in developing MVDC systems. This chapter deals with the capacitive couple-based transient current commutation technique in SSCBs. The state-of-the-art active injection circuits are introduced, and their applications in wide bandgap-based SSCBs are illustrated. In addition, the technology of capacitive coupling interface in transient current commutation is explained, and the advantages are highlighted. Along with developing mathematical investigations, MVDC experiments are also presented. Applying transient current commutation in SSCBs achieves a soft turn-off in the main switch during DC current breaking. Eliminating the transient power on solid-state switches and mitigating the gate voltage oscillations are two significant outcomes, which help to enhance the reliability and lifetime of the breakers in long term.
Access provided by Autonomous University of Puebla. Download chapter PDF
Similar content being viewed by others
Keywords
1 Introduction
Medium-voltage DC (MVDC) systems are growing worldwide [1]. Compared with alternative current (AC) counterparts, DC systems eliminate the need for frequency synchronization and reactive power compensation, facilitate using renewable energies, present potential advantages for integration of distributed generations and energy storage systems, and reduce the number of energy conversion stages [2, 3]. Besides, in recent years, a massive expansion of DC loads such as data centers and electric vehicle charge stations has been reported [4]. This highlights the significance of research in this field for both academia and industry.
However, the progress of MVDC systems faces technical limitations. Among many factors, circuit breakers are under early development [1, 5,6,7]. On one hand, due to the lack of zero crossing points in DC currents and the low inertia of DC systems, AC circuit breakers are not effective in interrupting large DC currents [8]. On the other hand, downsized versions of high-voltage DC (HVDC) circuit breakers do not lead to compact and efficient topologies [9]. Therefore, it suggests an urgent need to develop reliable, efficient, fast, and compact circuit breakers targeting MVDC applications.
Compared with mechanical and hybrid circuit breakers, SSCBs present remarkable advantages. They benefit from a fast response speed within microseconds, high compactness, and scalability [10,11,12]. Also, recent developments in wide bandgap semiconductor devices have resulted in more efficient circuit breakers as the result of smaller on-state resistance and extended electrical ratings [13, 14]. In contrast, achieving high efficiency in SSCBs leads to an expensive design [13]. According to the survey conducted in [15], most of the design cost of an SSCB is related to solid-state switches. Therefore, the reliability of the solid-state switches in circuit breakers is of great importance.
Energy-absorbing components are inseparable from DC circuit breakers. DC systems include line inductors to slow down the rising rate of short circuit fault currents [16]. The corresponding inductive energy needs to be dissipated during DC current breaking. However, solid-state switches have a limited energy dissipation capability [17]. To overcome this difficulty, energy absorption components are employed. Metal oxide varistors (MOVs), paralleled MOVs, MOV and resistor-capacitor (MOV-RC), and MOV and resistor-capacitor-diode (MOV-RCD) snubbers are commonly used in conjunction with solid-state switches [14].
Passive snubbers have limitations in SSCBs. MOV-based snubbers clamp voltage oscillations well, but they bring extremely high dv/dt across the main switch. MOV-RC and MOV-RCD snubbers overcome this problem as snubber capacitance helps effectively during the transient; MOV-RCD has better current capability compared with the RC snubbers; however, they suffer from a conflict between the response speed and power shock reduction during DC current interruption [18]. That is, increasing the snubber capacitance decreases the power shock on the solid-state switches, but it elongates the reaction time interval in the breakers. The situation is worsened when ultrafast SSCBs aim to be optimally coordinated in DC systems [19].
This chapter deals with the application of auxiliary active injection circuits in eliminating power shock on solid-state switches in SSCBs. Active injection circuits have been reported in mechanical and hybrid breakers to alleviate the arcing problem in mechanical disconnectors during DC current interruption [20,21,22]. In mechanical breakers, the countercurrent pulse is generated by a resonant LC circuit, and it is controlled by an injection switch. The injection capacitor in the auxiliary branch can be charged by an external charger [22] or through the DC system itself [23]. The former gives the flexibility of adjusting the injected pulse current’s amplitude and duration, while the latter benefits from simplicity. The injection capacitor and inductor are chosen regarding the fastness of the main switch Sm, the maximum fault current aimed to be interrupted in the system, the maximum voltage value on the injection capacitor, and the power density limitation of the targeted design.
The capacitive coupling interface is also introduced in this chapter, where it helps to enhance reliability in active injection-based breakers. In DC breakers where the auxiliary branch is directly connected to the main branch, they are prone to short circuit faults in the auxiliary injection circuits. This puts the reliability of DC systems at serious risk. To avoid this issue, capacitive couplers are introduced which act as the interface between the main and auxiliary branches and block short circuit fault currents. The operation of MVDC SSCBs based on a capacitive coupling interface will be demonstrated throughout the chapter.
2 Soft Turn-Off Operation in SSCBs
Even though solid-state switches in DC breakers undergo a limited number of switching, they experience large dv/dt and di/dt values. These result in high gate voltage oscillations leading to device failure or false turn-on operation during DC current interruption. MOV-RCD snubber circuits are considerably effective in mitigating the mentioned phenomenon; however, they are not able to fully solve the problem [24, 25].
High power shock on solid-state switches during the dc current interruption is another critical reliability issue. In SSCBs, solid-state switches are responsible for interrupting large DC currents. In this case, depending on fault currents amplitude and the snubber circuits, a relatively large transient power may appear on the solid-state switches [24]. Accordingly, high transient energy produces in the switches during a very short period [18].
This transient energy could be the source of two major separate failures including gate degradation and thermal runaway [26]. These two failures are the result of the fast growth rate of the temperature inside the device. The temperature dynamic and its growth rate are proportional to the transient power and energy in which the device is subjected to. Degradation and thermal runaway temperatures are two distinct boundaries in solid-state switches. The degradation of the gate structure occurs when the surface is exposed to degradation temperature for a sufficient time. This results in partially or entirely losing current conduction capability. In case the temperature reaches the thermal runaway boundary, the drain current increases exponentially followed by a permanent device failure.
Gate voltage oscillations and transient power are current-dependent. Meaning that reducing the current amplitude in solid-state switches during DC current interruption helps to mitigate the pointed challenges. The soft turn-off is a promising solution in this matter [22, 24], which will be elaborated in the following.
Soft turn-off operation refers to the situation in which the DC current in the switch is forced to zero during dc current breaking. To achieve this, active injection circuits with precharge injection capacitors are utilized. The general structure of the presented concept is shown in Fig. 6.1a. The breaker includes three branches connected in parallel: main branch, auxiliary branch, and energy-absorbing branch, illustrated in the following.
The critical current and voltage waveforms of the soft turn-off breaker are shown in Fig. 6.1b. In normal operating mode, the main branch conducts the load current through the main switch Sm, and current in the auxiliary and energy-absorbing branch is zero. It is assumed that a short circuit fault occurs at t = t0, and the system current begins to increase. The current interruption process includes three main stages: the current reaction process, soft turn-off operation, and energy absorbing stage.
During the reaction time interval (t1 ≤ t < t2), a countercurrent pulse is created by the auxiliary branch, and it is injected into the main branch to cancel the fault current in the main switch. Next, at t = t2, when the current in the main switch Sm reduces to zero, Sm is triggered to be OFF. Then, the commutated fault current in the auxiliary branch is interrupted, forcing the fault current to the energy-absorbing branch (t3 ≤ t < t5). Finally, the energy-absorbing elements dissipate the stored inductive energy of the line inductor.
The operation of the breaker shown in Fig. 6.1 reveals the soft turn-off during the DC current interruption. First, at the time of turning off the main switch, the current in the main switch is almost zero, which helps to mitigate the gate voltage oscillations. Also, as labeled in Fig. 6.1b, when the voltage across the solid-state switch begins rising, the current in the switch is zero, meaning zero power shock in the solid-state switch. All of these features are effective in enhancing the reliability of the breaker and extending its lifetime [24].
There are two kinds of modularity in the soft turn-off SSCBs. Regarding Fig. 6.2a, multiple solid-state switches can be connected in parallel to achieve higher efficiency and current interruption capability [14]. In this case, to achieve a soft turn-off operation, each solid-state switch is accompanied by its auxiliary and energy storage branches. In addition to simplicity during the design procedure, this kind of modularity results in current scalability, which is highly useful for the future development of DC systems. Also, it is highly effective in addressing any possible glitch between digital signals received by multiple solid-state switches in the main branch. In other words, if one of the switches in the main branch turns off sooner, the provided modularity prevents any damage to other switches due to resulted uneven current distribution.
Figure 6.2b indicates the second type of modularity, where multiple active injection auxiliary branches are connected in parallel to the main branch [22]. The goal is to obtain injection countercurrent pulses with different amplitudes for fault currents under different fault resistances. Each auxiliary branch could involve a unique injection inductor, resulting in a unique injection countercurrent pulse. Modularity can be achieved by activating different combinations of auxiliary branches during DC current interruption. Each auxiliary branch may include its precharge injection capacitor, or all the auxiliary branches can share one injection capacitor as shown in Fig. 6.3 [22]. For both cases, the SSCB only consists of one MOV branch directly connected in parallel to the main branch.
On the other hand, DC circuit breakers with active injection circuits shown in Fig. 6.1 are prone to short circuits in the auxiliary branch. This practical issue could reduce the reliability of the implemented protection systems and result in safety challenges. Figure 6.4 shows two general structures of DC circuit breakers with auxiliary circuits in DC systems. In Fig. 6.4a, the precharge injection capacitor is fully charged through an external charger; while in the topology of Fig. 6.4b, the injection capacitor is charged by the DC system itself controlled by a charging switch.
In both structures of Fig. 6.4, the potential failures are shown [27]. In Fig. 6.4a, the short circuit failure path creates its way through the injection inductor La, the injection switch Sa, and the external charger VCh-SCh. In such a short circuit failure, the circuit breaker is bypassed, leaving the DC system without protection. In the second scenario of Fig. 6.4b, the failure path leads to a short circuit close to the DC source; the fault is created through the injection inductor La, the injection switch Sa, and the charging switch SCh. Although a residual current mechanical disconnector can separate the circuit breakers from the DC source during the OFF-state, it is not practical when multiple SSCBs are in the DC systems [28, 29]. Therefore, solving the problem inside the circuit breakers is more effective.
3 Capacitively Coupled Soft Turn-Off SSCBs
A capacitive couple-based interface is a promising solution to prevent the potential failures described in Fig. 6.4. The general topology is shown in Fig. 6.5a [27]. The auxiliary branch is connected to the main branch through two coupling capacitors. The couplers allow the transient pulse currents during DC current interruption, but they prevent short circuit faults in the case of any failure. The coupling capacitance is in the range of hundreds of nano-Farad, which can be easily built using couplers with enough airgap for the sake of voltage isolation. As the capacitance is low, it does not reduce the power density of the final design.
Regarding Fig. 6.5, a few points can be highlighted below:
-
1.
As coupling capacitors are in the range of hundreds of nano-Farad, the injected pulse current during DC current interruption should be short with sufficient flat-top profile (Δtβ in Fig. 6.5b) to achieve soft turn-off operation.
-
2.
The auxiliary branch is completely isolated from the DC power system; in this case, an external charger is used to charge the injection capacitor Ca in the auxiliary branch.
-
3.
When the main switch Sm is ON, the voltage across the coupling capacitors is almost zero. During the turn-off process, coupling capacitors share the DC bus voltage. Also, overshoot voltages across the couplers can be clamped as will be further described in the section.
-
4.
A well-defined digital communication is required between the main and auxiliary branches during DC current interruption.
-
5.
Both modular topologies illustrated in Fig. 6.2 can be applied to the capacitively coupled SSCBs.
-
6.
Energy-absorbing elements can be directly connected in parallel to the main branch, and it does not interfere with the operation of the auxiliary branch and the capacitive couplers.
With respect to Fig. 6.5a, the auxiliary active injection branch should generate a pulse current with a short duration to optimize the coupling capacitors. That is, Δtβ of Fig. 6.5b aims to be decreased as much as possible, which helps to reduce charge currents flowing through the coupling capacitors. To achieve this goal, the Boost converter-based current pulse generator of Fig. 6.6 is highly applicable [30].
The current pulse generator mainly includes an auxiliary low voltage DC source Vaux, an injection precharge capacitor Ca, an injection inductor La, an injection controlling switch Sa, a snubber capacitor Cs, an MOV element for protecting the injection switch, and an output diode Da. The auxiliary branch is connected in parallel to the main branch through the capacitor couplers. The main branch consists of MOSFET switches whose body diodes help achieve soft turn-off operation.
Figure 6.7 indicates the operating modes of the Boost converter-based current pulse generator in injecting a countercurrent pulse current to the main switch Sm. The operation is explained in the following.
Mode I
The auxiliary switch Sa turns on, and the energy stored in the precharge injection capacitor Ca is transferred to the injection inductor La. The inductor current begins to increase whose slope depends on the pre-charge voltage on the injection capacitor Vaux, the injection capacitance Ca, and the injection inductance La. During this mode, no current flows through diode Da and capacitive couplers. Also, as the injection switch Sa is ON, the voltage across the snubber capacitor Cs, the MOV, and coupling capacitors remains zero.
Mode II
The amplitude of the injection inductor current reaches a threshold value specified in the SSCB; then, the control algorithm triggers the injection switch Sa to be OFF. In this case, the snubber capacitor Cs, connected in parallel to Sa, starts charging. The value of Ca is chosen optimally to protect Sa from high dv/dt during the turn-off process. The voltage across Ca continues increasing; the current in the injecting diode Da is still zero.
Mode III
The voltage across the snubber capacitor Cs reaches the auxiliary voltage Vaux. The injection diode Da turns ON, where it begins to conduct the countercurrent pulse and inject it to the main branch through the capacitive couplers. Simultaneously, the current in the main switch Sm reduces to zero, obtaining a current zero-crossing point in the main switch. As the current approaches zero in Sm, the main branch’s control board turns Sm off, meaning a soft turn-off operation, e.g., Fig. 6.1b. It is noted that the body diodes of the main switch Sm are effective, highlighted in the next section.
Mode IV
As the pulse current flows through the capacitive couplers, the coupler’s voltage rises. As the voltage reaches the clamping voltage of the snubber MOV, the MOV switches to the clamping mode. The MOV’s resistance reduces significantly and conducts the tail of the injection inductor current La. In this case, the current in the injection diode Da and the coupling capacitors reduces to zero. The MOV continues in the conduction mode till it absorbs all the energy of the injection inductor La. Finally, the MOV returns to the leakage current mode and blocks the auxiliary voltage Vaux.
The design procedure of the current pulse generator has been well described in [30]. The primary aim is to obtain a countercurrent pulse with sufficient amplitude and profile to implement a reliable soft turn-off during DC current interruption. The next design objective is minimizing the capacitance of the couplers, as it helps to achieve a compact and low-cost design. Therefore, the auxiliary source voltage Vaux, the injection capacitor Ca, the injection inductor La, and the clamping voltage of the snubber MOV along with all the parasitic components are included in the design procedure.
Regarding the soft turn-off technique, the capacitive couple-based interface, and the Boost converter-based pulse current generator, an MVDC soft turn-off SSCB with the capacitive couple interface is developed and analyzed. Figure 6.8 indicates the capacitively coupled MVDC SSCB [27]. The dc bus voltage is Vdc, LLine emulates the line inductor, and the load is assumed to be resistive RLoad. The main branch is constructed from SiC power MOSFET modules. The auxiliary branch follows the same topology as the current pulse generator in Fig. 6.6. Capacitive couplers are labeled as C1 and C2 whose values are assumed to be the same, meaning C1 = C2 = C.
As indicated in Fig. 6.8, the current pulse generator also includes the couplers reset resistor Rreset and the damping resistor Rdamp. The couplers’ reset resistor is used to discharge the capacitive couplers when the main switch Sm turns on, but small values of Rreset result in leakage currents during the breaker OFF-state. Therefore, a tradeoff should be made in selecting Rreset. Also, the damping resistor Rdamp damps the ringing flat-top of the injected countercurrent pulse, but large values of Rdamp lead to a small Δtβ shown in Fig. 6.5b.
The operating modes of the capacitively coupled soft turn-off SSCB are shown in Fig. 6.9, where the closing process, normal operating mode, and fault current interruption are indicated. Also, the corresponding critical electrical waveforms of Fig. 6.9 are displayed in Fig. 6.10. Regarding Figs. 6.9 and 6.10, the operation of the breaker is explained below.
During mode I (before t0), the circuit breaker is OFF. The DC bus voltage places on the main branch vSm = Vdc. In the auxiliary branch, the injection capacitor Ca charges to Vaux using an auxiliary voltage source VCin = Vaux. As the current in the injection inductor La is zero, the injection switch Sa holds the same Vaux voltage, meaning vSa = Vaux. Each capacitive coupler holds half of Vaux + Vdc. It is noted that both coupling capacitors are assumed to be the same; in this case, vC1 = vC2.
The circuit breaker turns on during modes II and III (t0 ≤ t < t1) and undergoes its closing stage and capacitive couplers’ reset process. Sm turns on at t = t0 and conducts the load current. The capacitive couplers begin discharging on the reset resistor Rreset, where their voltage finally reaches vC1 = vC2 = Vaux/2. The current in the auxiliary branch remains zero. There is a leakage current in resistor Rreset, but it is negligible.
A short circuit fault with the fault resistance Rf occurs at t = t1 during mode IV. The circuit breaker reacts to the fault during mode V by turning on the injection switch Sa (t2 < t < t3). Consequently, the pulse current in the injection inductor La increases. As shown in mode VI, at t = t3, Sa turns off, and the current of the injection inductor La flows through the capacitive couplers as also described in Fig. 6.7.
In mode VII, at t = t4, the main switch Sm current reduces to zero, and Sm is triggered to be OFF. A soft turn-off operation is achieved, where Sm turns off under zero power shock. During mode VIII (t4 < t < t5), the fault current commutates to the auxiliary branch, and it finally reduces to zero. Also, the remaining inductive energy of the injection inductor La is dissipated in the snubber MOV (refer to Fig. 6.7). The interruption completes, and the circuit breaker goes back to mode I. The voltage on Sm stabilizes on Vdc, and the voltage on each coupler is (Vaux + Vdc)/2.
4 Experimental Study of Capacitively Coupled-Based SSCBs in MVDC Systems
To further analyze the proposed capacitively coupled soft turn-off SSCB, it is experimentally studied [30, 31]. Figure 6.11 shows the experimental setup. The SSCB is shown in Fig. 6.11. In the main branch, 12 CAB-450M12XM3 SiC MOSFET power modules are connected in a 4 × 3 matrix. MOV-RCD snubber circuits include MOV V661HA40, the snubber diode C4D20120, and 100 Ω and 200 nF as the snubber resistor and capacitor, respectively. The main branch gate drivers are supplied by an inductive wireless power transfer system to obtain voltage isolation between four layers. The main branch is controlled by a TMS320F28335 DSP from TI.
Two 280 nF/10 kV film capacitors are used as the coupling interface between the main and auxiliary branches. In the auxiliary branch, two 5SNG-0300Q170300 IGBT power modules are used for the injection switch Sa. The injection inductor is La = 314 μH; the injection capacitor Ca = 200 μF, where its voltage is kept at 600 V using a series-parallel inductive wireless power transfer converter. The injection diodes are C4D20120, and the Rreset and Rdamp resistors are 3 kΩ and 15 Ω, respectively. The breaker is tested in a 4 kV DC system, where the line inductor is 7 mH and the resistive load is 285 Ω. To emulate a short circuit fault, four MCNA650P2200CA thyristors are connected in series, where a bilateral wireless power relay system is used to trigger the thyristors reliably.
Figure 6.12 shows the experimental results. The line current, capacitive coupler currents, and the main branch voltage are indicated. In steady-state, the circuit breaker supplies 14 A load current. A short circuit fault is created at t = 550 μs through the thyristor switches. The breaker interrupts the fault current within 77 μs, where the peak of system current reaches 97 A and Sm experiences 5.36 kV overshoot voltage.
Figure 6.13 reveals one of the promising advantages of the soft turn-off SSCB based on a capacitively coupled interface. The main switch current and the main branch voltage waveforms are displayed in Fig. 6.13. According to the operation of the capacitive couple-based SSCB, the main switch Sm turns off when the current in Sm reduces to zero. That is, the main switch voltage rises when there is no current in Sm, leading to a zero transient power on the main switch. This point has been highlighted in Fig. 6.13. The achieved zero power shock in the main switch Sm obtains a safe operation, improves its current interruption capability, and helps to enhance reliability.
Furthermore, Fig. 6.14 shows the transient voltage balance between the top and bottom layers during DC current interruption, which verifies the effectiveness of the implemented symmetrical and efficient structure in the main branch. As is clear in Fig. 6.14, the voltage of the top two layers and the bottom two layers are evenly balanced during the transient and steady-state operation.
5 Conclusions
Applying transient current commutation to DC SSCBs achieves a soft turn-off operation during current interruption. For soft turn-off SSCBs, in the main branch, the voltage and current waveforms of the main switch have no overlaps during the turn-off process, leading to zero transient power and energy. Also, reducing the main switch current to zero mitigates the gate’s voltage oscillations, resulting in a higher degree of reliability. When the main switch experiences a high change in its drain-source voltage, its gate voltage has already stabilized at zero or negative values, which reduces the possibility of a false turn-off. All these advantages improve the reliability of the SSCBs and extend the lifetime in the long term. Meanwhile, the active injection branch is fast and compact under modularity and scalability.
A capacitive couple-based interface between the main and auxiliary branches enhances the reliability of the DC system under operation. It prevents short circuits in the DC link close to the upstream breakers. In the meantime, a Boost converter-based current pulse generator allows transient current commutation through capacitive couplers. The current pulse generator works with a low-voltage auxiliary source, its generated pulse current is adjustable in terms of amplitude and duration, and it communicates synchronously with the main branch in a reliable manner. As the injected pulse current is short, the coupling capacitors’ values are small, resulting in a compact design. The capacitively coupled soft turn-off MVDC SSCBs are a promising solution for implementing a robust protection system in MVDC power networks.
References
CIGRE, Medium voltage direct current (MVDC) grid feasibility study. Technical Brochure 793, WG C6.31 (2020)
S. Zheng, R. Kheirollahi, J. Pan, L. Xue, J. Wang, F. Lu, DC circuit breakers: A technology development status survey. IEEE Trans. Smart Grid 13, 3915–3928 (2021). https://doi.org/10.1109/TSG.2021.3123538
F. Ornelas-Tellez, J. J. Rico-Melgoza, E. Espinosa-Juarez, E. N. Sanchez, Optimal and robust control in DC microgrids. IEEE Trans. Smart Grid 9(6), 5543–5553 (2018)
K. Sun, H. Xiao, J. Pan, Y. Liu, A station-hybrid HVDC system structure and control strategies for cross-seam power transmission. IEEE Trans. Power Syst. 36(1), 379–388 (2021)
X. Xu, W. Chen, C. Liu, R. Sun, Z. Li, B. Zhang, An efficient and reliable SSCB based on mixture device. IEEE Trans. Power Electron. 36(9), 9767–9771 (2021). https://doi.org/10.1109/TPEL.2021.3067316
Z. J. Shen, Y. Zhou, R. Na, T. Cooper, M. A. Ashi, T. Wong, A series-type hybrid circuit breaker concept for ultrafast DC fault protection. IEEE Trans. Power Electron. 37(6), 6275–6279 (2022)
R. Kheirollahi, S. Zhao, H. Zhang, F. Lu, Fault current bypass-based DC SSCB using TIM-pack switch. IEEE Trans. Ind. Electron. 70, 4300–4304 (2022). https://doi.org/10.1109/TIE.2022.3174304
C.M. Franck, HVDC circuit breakers: A review identifying future research needs. IEEE Trans. Power Deliv. 26(2), 998–1007 (2011)
G.F. Reed, B.M. Grainger, A.R. Sparacino, Z. Mao, Ship to grid: Medium-voltage DC concepts in theory and practice. IEEE Power Energy Mag. 10(6), 70–79 (2012). https://doi.org/10.1109/MPE.2012.2212613
Z.J. Shen, Ultrafast SSCBs: Protecting converter-based AC and DC microgrids against short circuit faults. IEEE Electrif. Mag. 4(2), 72–70 (2016). https://doi.org/10.1109/MELE.2016.2544058
R. Kheirollahi, S. Zhao, F. Lu, Fault current bypass-based LVDC SSCBs. IEEE Trans. Power Electron. 37(1), 7–13 (2022)
D. Marroquí, J. M. Blanes, A. Garrigós, R. Gutiérrez, Self-powered 380 V DC SiC SSCB and fault current limiter. IEEE Trans. Power Electron. 34(10), 9600–9608 (2019)
R. Rodrigues, Y. Du, A. Antoniazzi, P. Cairoli, A review of SSCBs. IEEE Trans. Power Electron. 36(1), 364–377 (2021)
S. Zhao, R. Kheirollahi, Y. Wang, H. Zhang, F. Lu, Implementing symmetrical structure in MOV-RCD snubber-based DC SSCBs. IEEE Trans. Power Electron. 37(5), 6051–6061 (2022). https://doi.org/10.1109/TPEL.2021.3133113
R. Kheirollahi, X. Zan, S. Zhao, Y. Wang, H. Zhang, X. Lu, A.T. Avestruz, F. Lu, A trade-off between cost and efficiency in SSCBs, in 2022 IEEE Energy Conversion Congress and Exposition, Detroit, Michigan, October 2022
J. Hafner, B. Jacobson, Proactive Hybrid HVDC Breakers-A Key Innovation for Reliable HVDC Grid (CIGRE, Bologna, 2011)
Z.J. Shen, Z. Miao, A.M. Roshandeh, SSCBs for DC microgrids: Current status and future trends, in Proceedings of IEEE 1st International Conference DC Microgrids, Atlanta, GA, USA (2015), pp. 228–233
S. Zhao, R. Kheirollahi, Y. Wang, H. Zhang, F. Lu, Investigation of limitations in passive voltage clamping-based solid-state DC circuit breakers. IEEE Open J. Power Electron. 3, 209–221 (2022). https://doi.org/10.1109/OJPEL.2022.3163072
L. Qi, P. Cairoli, Z. Pan, C. Tschida, Z. Wang, V. R. Ramanan, L. Raciti, A. Antoniazzi, SSCB protection for dc shipboard power systems: Breaker design, protection scheme, validation testing. IEEE Trans. Ind. Appl. 56(2), 952–960 (2020)
X. Pei, O. Cwikowski, D. S. Vilchis-odriguez, M. Barnes, A. C. Smith, R. Shuttleworth, A review of technologies for MVDC circuit breakers, in IECON 2016 – 42nd Annual Conference of the IEEE Industrial Electronics Society (2016), pp. 3799–3805, https://doi.org/10.1109/IECON.2016.7793492
Y. Zhou, Y. Feng, N. Shatalov, R. Na, Z. J. Shen, An ultraefficient dc hybrid circuit breaker architecture based on transient commutation current injection. IEEE J. Emerg. Sel. Top. Power Electron. 9(3), 2500–2509 (2021)
R. Kheirollahi, H. Zhang, S. Zhao, J. Wang, F. Lu, Ultrafast SSCB with a modular active injection circuit. IEEE J. Emerg. Sel. Top. Ind. Electron. 3, 733–743 (2022). https://doi.org/10.1109/JESTIE.2021.3087952
A. Ray, K. Rajashekara, S.N. Banavath, S.K. Pramanick, Coupled inductor-based zero current switching hybrid DC circuit breaker topologies. IEEE Trans. Ind. Appl. 55(5), 5360–5370 (2019)
R. Kheirollahi, H. Zhang, S. Zhao, F. Lu, A DC SSCB based on transient current commutation. IEEE J. Emerg. Sel. Top. Power Electron. 10, 4614–4625 (2022). https://doi.org/10.1109/JESTPE.2021.3116605
P. Nayak, M.V. Krishna, K. Vasudevakrishna, K. Hatua, Study of the effects of parasitic inductances and device capacitances on 1200 V, 35 A SiC MOSFET based voltage source inverter design, in 2014 IEEE International Conference on Power Electronics, Drives and Energy Systems (PEDES) (2014), pp. 1–6
G. Romano, A. Fayyaz, M. Riccio, L. Maresca, G. Breglio, A. Castellazzi, A. Irace, A comprehensive study of short-circuit ruggedness of silicon carbide power MOSFETs. IEEE J. Emerg. Sel. Top. Power Electron. 4(3), 978–987 (2016)
R. Kheirollahi, X. Zan, S. Zhao, H. Zhang, S. Zheng, X. Lu, A-T. Avestruz, F. Lu, Capacitive couple-based transient current commutation in SSCBs. IEEE Trans. Power Electron. 37(5), 4973–4978 (2022). https://doi.org/10.1109/TPEL.2021.3134461
A. A. Solangi, Y. Zhou, M. Mohammadi, R. Na, Z. J. Shen, Selective coordination of GaN-based SSCBs, in 2021 IEEE Applied Power Electronics Conference and Exposition (APEC) (2021), pp. 1140–1145, https://doi.org/10.1109/APEC42165.2021.9487323
R. Kheirollahi, S. Zhao, H. Zhang, X. Lu, J. Wang, F. Lu, Coordination of ultrafast SSCBs in radial DC microgrids. IEEE J. Emerg. Sel. Top. Power Electron. 10, 4690–4702 (2022). https://doi.org/10.1109/JESTPE.2021.3109483
X. Zan, D. Roman, R. Kheirollahi, X. Lu, S. Zheng, F. Lu, A-T. Avestruz, Medium voltage pulse power generator for accurate current interruption. IEEE Trans. Ind. Electron. 70, 3604–3615 (2022). https://doi.org/10.1109/TIE.2022.3174234
R. Kheirollahi, S. Zhao, X. Zan, H. Zhang, X. Lu, A-T. Avestruz, F. Lu, A 4kV/100A DC SSCB with soft turn-off and 99.97% efficiency, in 2022 IEEE Transportation Electrification Conference & Expo (ITEC+EATS), Anaheim, CA, June 15–17, 2022
Author information
Authors and Affiliations
Corresponding author
Editor information
Editors and Affiliations
Rights and permissions
Copyright information
© 2023 This is a U.S. government work and not under copyright protection in the U.S.; foreign copyright protection may apply
About this chapter
Cite this chapter
Lu, F., Kheirollahi, R. (2023). Soft Turn-Off Capacitively Coupled SSCBs for MVDC Applications. In: Kizilyalli, I.C., Shen, Z.J., Cunningham, D.W. (eds) Direct Current Fault Protection. Power Systems. Springer, Cham. https://doi.org/10.1007/978-3-031-26572-3_6
Download citation
DOI: https://doi.org/10.1007/978-3-031-26572-3_6
Published:
Publisher Name: Springer, Cham
Print ISBN: 978-3-031-26571-6
Online ISBN: 978-3-031-26572-3
eBook Packages: EnergyEnergy (R0)