A study by the United Nations estimates that by the end of 2050, approximately 64% of developing countries and 86% of the population of developed countries will live in cities. To solve the increase in population density in urban areas, these must be expanded, or high-rise buildings built [1]. For this reason, in the last decade, Lima has experienced an increase in the verticality of its buildings. Therefore, it is necessary to use a structural system resistant to wind and earthquake forces. Based on this, several structural systems have been developed for high-rise buildings. The rigid core structural system constitutes such a solution and offers the advantage of faster construction, flexible architecture and open space availability [1,2,3,4,5,6,7,8]. To design these structures that resist earthquake loads, there are several numerical methods [2]. One of them is the response spectrum analysis (RSA) which is widely used in various seismic codes such as ASCE 7, UBC-97, FEMA-356 and ATC-40 to determine design forces and displacement demands [3]. In addition, must be taken into consideration that tall buildings are complex due to the numerous structural components and several vibration modes [4]. In the case of the Peruvian Code, this method is related to the Equivalent Lateral Force (EFL) by means of the dynamic amplification factor, which guarantees that the current base is not less than 80% of the value calculated by EFL for regular structures. To determine the shear force by means of the EFL, the Standard establishes a minimum C/R factor. The subject of this analysis is to corroborate this parameter in the case of tall buildings by comparing inelastic responses with the LRHA. In addition, few studies prove that the RSA established by the standard is adequate for high-rise buildings. The advantage of using an adequate value for this factor will avoid the design of the building with unnecessary robust elements that meet the seismic requirements, which would significantly increase the cost of such infrastructure since it would cause a lack of investment due to the cost overrun.

The methodology adopted in this work is proposed by our authorship and is described as follows:

  1. 1.

    The case studies are defined taking into consideration the following criteria: use of the building, dimensions, predominant material, mezzanine height, slab thickness and variation in compressive strength.

  2. 2.

    Selection of five seismic acceleration records according to soil type and moment magnitude range.

  3. 3.

    Proceed with the EFL and RSA, as established by the Seismic Resistant Design Code E.030.

  4. 4.

    The inelastic responses of the spectral modal dynamic analysis are compared with the linear time-history analysis to determine the adjustment of the C/R factor.

  5. 5.

    The results analysis is carried out and an adjusted C/R value is proposed for high-rise reinforced concrete building.

2 Methodology

2.1 Description of the Buildings

Twenty-eight tall buildings located in Lima, Peru, are considered in this study (Fig. 1). The number of floors of the cases analyzed is 24, 26, 28, 30, 32, 34 and 36 floors. Fourteen of these buildings correspond to a square plan and the other fourteen to a rectangular plan. Likewise, the structural configuration was modified considering frames and post-tensioned slabs.

Fig. 1
figure 1

Floor plans and 3D models. a PC-POR, b PR-POR, c PC-POS y d PR-POS

Each beam and column was modeled as an elastic frame element. The slabs and the cutting walls are modeled with a thin shell elastic element and the foundation was idealized as recessed base support. For all buildings, the columns on each floor resistless than 30% of the total lateral force; therefore, the structural system is considered as structural walls in accordance with Code E.030. The P ∆ effects are included in all the methods [5] (Table 1).

Table 1 Coding of the square and rectangular floor model

2.2 Selected Seismic Records

In this study, a set of five seismic records was selected and the information was obtained from the Japanese Peruvian Center for Seismic Research and Disaster Mitigation (CISMID) [7]. The selection of these registers took into consideration the type of soil where the building is to be cemented (Very rigid soil) and with magnitude in the range of 6–8.5-moment magnitude. In addition, these were scaled to 0.45 g cm/s2 (Fig. 2).

Fig. 2
figure 2

The response spectrum of selected earthquakes with a damping of 5%

2.3 Methods of Analysis for Earthquake Resistant Design

2.3.1 Equivalent Lateral Force Procedure (ELF)

The ELF procedure in Code E.030 is adopted in this study [6]. This method represents the seismic solicitations as a set of lateral forces that act in the center of mass of each level of the building. It consists of determining five seismic parameters that are: zone factor (Z), soil factor (S), use factor (U), seismic amplification factor (C), seismic force reduction coefficient (R). The determination of the shear force at the base of the structure for each direction considered is calculated as follows:

$$V = \frac{ZUCS}{R} \cdot P; \frac{C}{R} \ge 0.11$$
(1)

This methodology cannot be applied to structures of reinforced concrete bearing walls for buildings with a height greater than 30 m. However, it is necessary to carry out this analysis in the design of reinforced concrete elements by what establishes the norm as a minimum base shear force.

2.3.2 Response Spectrum Analysis (RSA)

The RSA method in Code E.030 is adopted in this study [6], where the elastic response is combined for several vibration modes to obtain the total elastic response, using the complete quadratic combination (CQC), which is then reduced by a force reduction factor (R) to obtain the design forces of the structure.

3 Results

3.1 Comparison of Design Demands Between RSA and LRHA

The following graphs represent the base shear through different types of analysis in both directions. The first bar represents the RSA analysis with the C/R factor calculated, while the second bar depicts the base shear obtained with the RSA analysis with the minimum C/R factor proposed by the Peruvian Code. Addition-ally, the other bars represent the base shear calculated from LRHA analysis with the seismic records mentioned above (Figs. 3, 4, 5, 6, 7, 8, 9 and 10).

Fig. 3
figure 3

Base Shear for PC-POR in the X-direction

Fig. 4
figure 4

Base Shear for PC-POR in the Y-direction

Fig. 5
figure 5

Base Shear for PC-POS in the X-direction

Fig. 6
figure 6

Base Shear for PC-POS in the Y-direction

Fig. 7
figure 7

Base Shear for PR-POR in the X-direction

Fig. 8
figure 8

Base Shear for PR-POR in the Y-direction

Fig. 9
figure 9

Base Shear for PR-POS in the X-direction

Fig. 10
figure 10

Base Shear for PR-POS in the Y-direction

The shear forces calculated from the LRHA are significantly lower than those calculated from RSA established by the Peruvian Standard of Seismic-Resistant Design E.030, only a few exceptions for the seismic record of Surco1974 for the N34PC_POR model. Therefore, it can be deduced that the C/R value is lower than what is established in the regulations. The results of the LRHA were reduced by a factor R. There are greater requests in terms of cut in square and rectangular plants of 36 levels.

The general procedure to determine the value of C/R for high-rise buildings consists of computing ratios that are based on the base shear obtained by the RSA and the LRHA. Then the ratios are multiplied by the C/R values obtained from the LRHA. Finally, the most critical values were chosen as the final value (Tables 2 and 3).

Table 2 Summary of proposed C/R values in the X-direction
Table 3 Summary of C/R proposed values in the Y-direction

4 Discussions

This work incentive the design of buildings that meet the seismic requirements and is economically feasible, besides that it was resolved the lack of information regarding high-rise reinforced concrete buildings in Peru and investigates the advantages of regular seismic buildings as seen in other international buildings such as the case of Burj Khalifa.

The range of periods found for the PC-POR and PR-POR buildings is between 1.5 and 3 s, while for the PC-POS and PR-POS structures their range corresponds to 2.5–4 s, being the largest period, the cross-section that is slenderer.

5 Conclusions

The value of C/R is analyzed in the case of tall reinforced concrete buildings by comparing the design shears indicated by Peruvian seismic regulations with the base shear obtained from an LRHA, which have been scaled to 0.45 g.

It was found lower drifts of the LRHA smaller than what is indicated in Code E.030, except for specific cases, but all are less than 0.7%, which establishes said norm. The dynamic amplification factor is sensitive to the C/R value. It was noticed that for PC-POR and PR-POR buildings, considering the minimum C/R equal to 0.11, the shear does not need to be amplified for buildings smaller than 30 floors, however, for larger buildings the factor of amplification would be in the order of 150%. On the other hand, for PC-POS buildings, it is not necessary to amplify the shear, and for PR-POS it is amplified from the 32-story buildings, in the order of 250%.

The main finding of this paper proposes a minimum value of C/R less than 0.11 for each of the 4 studied cases of the high-rise building. It was obtained due to the regularity in the plan and height of the building and the use of a rigid core structural system. As for PC-POR buildings, it is established that C/R values are much lower than 0.08 for buildings with up to 32 levels, for buildings with a higher number of levels this value is close to 0.08; something similar happens for structures type PR-POR. In addition, for PC-POS and PR-POS buildings, the value of C/R is less than 0.08 at all levels. Two C/R values differentiated by the structural system are proposed, C/R equal to 0.075 for PC-POS and PR-POS and for 0.10 for PC-POR and PR-POR.

There is a pressing need to extend the research to study the implications of the wind force due to the predominant effect for high-rise buildings such as this one because of its high natural period. It is suggested to study it. Furthermore, the value of R must be improved or studied, being able to be less than 6, for this, it is suggested to perform a nonlinear response history analysis (NLRHA).