1 Introduction

Heat exchanger is an equipment facilitating heat transfer (HT) involving two or more fluids. In numerous industries, likely as chemical dispensations, refrigerating systems, air handling units, thermal power plants, air conditioning apparatus, and radiators for space shuttles in addition to automobiles, etc., heat exchanger (HE) is extensively utilized. To increase the performances of heat exchangers, heat transfer enhancement (THE) techniques have been developed. A method for heat transfer enhancement is the insertion of structures into the flow path that favorably alter the flow pattern (Tiwari and Saha 2015; Ghajar et al. 2010; Roy and Saha 2015; Meyer and Abolarin 2018; Saha 2010; Meyer and Olivier 2011; Saha 2011; Rahimi and Soran 2017; Sabet et al. 2017; Bhattacharyya et al. 2018). One of the practical means to this purpose is introducing swirl in a pipe flow by the insertion of a twisted tape (TT) as shown in Fig. 1. This is investigated in the present study.

Fig. 1
figure 1

a Full-length twisted tape, b sketch of diameter and tape thickness ratio configuration, c sketch of FLTT and SLTT and d photographic view of FLTT and SLTT

TT swirl generators are generally engaged for manufacturing compact heat exchangers and increasing the thermal enhancement performance (TEP) of the existing HE due to their low cost and ease of installation. Swirl generators assist in moving fluid from channel core to near wall region and vice versa. Earlier studies have shown that heat transfer enhancement with different working fluids is strongly dependent on different swirl generators geometric factors (Balachandar et al. 2018; Mohammadiun et al. 2017; Sheikholeslami and Ganji 2016a, b; Sheikholeslami et al. 2018; Sheikholeslami and Shehzad 2018; Sheikholeslami 2018a, b; Sheikholeslami and Rokni 2018; Sheikholeslami and Seyednezhad 2018).

In many heat exchanger relevancies, transitional flow conditions may prevail, the modeling of which is more demanding compared to fully turbulent flow, and still not exhaustively explored. In the present study, enrichment of heat transfer in a pipe flow by a twisted tape is experimentally investigated, within a range of Reynolds numbers between 6000 and 20,000.

Early investigations on the channel with twisted tape configurations were performed by Manglik and Bergles (1994) and AI-Fahed and Chakroun (1996). Suresh et al. (2004) studied the theory of the thermohydraulic affectivity of twisted-tape inserts within a bulky hydraulic diameter annulus. Bhattacharyya and Saha (2012), Bhattacharyya et al. (2013) and Saha et al. (2012) noted down that the center-clearing twisted tapes in amalgamation with rib roughness execute extensively better than the standalone enhancement technique acting single-handedly for laminar flow throughout a duct involving circular geometric cross section up to a convincing range of twisted-tape center-clearance. Sivashanmugam and Suresh (2006, 2007a, b, c) investigated experimentally on the characteristics of the heat transfer and friction factor of the laminar and turbulent flows throughout a circular tube fitted with full-length helical screw tapes involving different twist ratios, including the increasing and decreasing order of twist ratio sets. Eiamsa-ard and Promvonge (2005) reported enrichment of heat transfer in a channel involving helical tape swirl generator having regular-spacing with the variation of Reynolds number ranging between 2300 and 8800 utilizing water as working fluid, and accomplished that the full-length helical tape with rod provides the highest rate of heat transfer of about 10% improvement than that of without rod.

The justified adjustment between the enhanced HT and minimum friction penalty can be attained by using twisted tape swirl generators with proper length ratio, tape thickness ratio, twist ratios, etc. So, in this paper, the results of experimental study of the effect of twisted tapes with different diameter, thickness and twist ratios have been presented and discussed. Heat transfer, pressure drop characteristics and performance have been presented. One of the chief objectives of this paper is to report on the combined effect of the thickness, twist and diameter ratios.

2 Experimental Setup and Procedure

The experimental setup is shown in Fig. 2. The test section consists of a circular channel with 22 mm inside diameter and a length of 2.0 m. The atmospheric air with a temperature of about 300 K was sucked in by a 7.0-kW blower. A U-tube manometer is employed to determine the pressure drop across the test section. Also, a rotameter is used to measure the flow rate of the working fluid. Using an adjustable valve, the mass flow rate of the air was varied.

Fig. 2
figure 2

a Schematic diagram of experimental setup and b photographic view

Test section for the current study of heat transfer was heated using an electrical nichrome heater. Nichrome wire heater consists of porcelain bead insulation over it. There exists no direct contact between that heater wire and the channel wall. Insulation of fiber glass tape was provided on the channel wall, and then, it was wrapped by the porcelain-bead-insulated nichrome wire. The heat transfer test section was insulated using asbestos rope and glass wool on the heater wire. Finally, the test section was covered with jute bag.

A selector switch box is used to determine the temperature of the inlet and outlet sections of the test section and also to measure the channel wall temperatures of the test channel. The temperatures of inner and outer walls of the test channel were recorded at seven axial locations, each station having four thermocouples along the channel periphery. This was done with the help of copper–constantan thermocouples and a digital multi-meter. The high thermal conductivity of the channel wall out of brass (k = 125 W/mK) was facilitated to achieve a quite uniform inner wall temperature with variations that remain below ± 4% around a mean value of about 340 K. Thus, in the modeling, the assumption of an isothermal condition for the channel wall is found to be reasonable. The measurements of the temperature at peripheral outside wall, at the two locations in an axial station, showed a maximum variation of about 4% at all Reynolds numbers. This variation in the peripheral wall temperature is expected to be principally due to buoyancy and secondary flows.

Uncertainties analyses of the major experimental variables are given in Table 1. The uncertainty in Reynolds number, friction factor and Nusselt number was estimated as ± 3.9%, ± 6.2% and ± 7.1%, respectively, following the procedure of Bhattacharyya et al. (2013).

Table 1 Experimental uncertainty of major parameters

3 Data Reduction

The problem consists of a channel of diameter D and a twisted tape of thickness (δ = t/D = 0.0417 and 0.0458). The length ratio of the twisted tape is about (L/D = 90.0 and 54.0), where L/D = 90.0 is the full-length twisted tape (FLTT) and L/D = 54.0 is the short-length twisted tape (FLTT). Diameter ratios are considered, namely d = W/D = 0.83, 0.75, 0.66. The ‘twist ratio’ is defined as y = H/D = 15.0 and 45.0 (Fig. 1).

The bulk fluid temperature (Tb) is calculated as the arithmetic average of fluid and inlet (Ti) outlet (To) temperatures. The wall heat flux is deduced \(\left( {q_{\text{w}} } \right)\) from the difference in the energy flow rates of the inflowing and outflowing fluids, with the respective temperatures of Ti and To.

Heat transferred to the air, Q can be written by

$$Q = m_{\text{a}} C_{{{\text{p}},{\text{a}}}} \left( {T_{\text{o}} {-}T_{\text{i}} } \right)$$
(1)

where ma is the mass flow rate of air, Cp,a is the specific heat of air, and Ti and To are the inlet and outlet air temperatures, respectively.

In the experiments, the heat equilibrium test showed that the heat absorbed by the air (Q) was within 2–4% lower than the heat supplied by electrical winding; this was due to the heat leakage from the duct wall.

The heat flux rate was calculated by

$$q_{\text{w}} = \frac{Q}{A}$$
(2)

where A is the internal surface area of the channel.

The bulk fluid temperature was obtained by

$$T_{\text{b}} = \frac{{T_{\text{o}} + T_{\text{i}} }}{2}$$
(3)

All the fluid properties were calculated at the average of the inlet and outlet bulk temperatures, Tb.

The average wall temperature was calculated from

$$T_{\text{wall, Avg}} = \sum \frac{{T_{\text{wall}} }}{7}$$
(4)

where Twall is the wall temperature of the channel. The average wall temperature was calculated from seven points of wall temperatures lined between the inlet and the outlet of the test section.

The average heat transfer coefficient was obtained from

$$h = \frac{q}{{T_{\text{wall, Avg}} - T_{\text{b}} }}$$
(5)

The Nusselt number was calculated according to

$$Nu = \frac{{hD_{\text{i}} }}{K}$$
(6)

where k is the thermal conductivity of air.

The Reynolds number based on the channel hydraulic diameter is given by

$$Re = \frac{{\rho vD_{\text{i}} }}{\mu }$$
(7)

The friction factor is evaluated by

$$f = \frac{2}{{\frac{L}{{D_{\text{i}} }}}}\frac{{\Delta P}}{{\rho v^{2} }}$$
(8)

where ΔP is the pressure drop across the test section and v is the mean air velocity of the duct channel.

4 Results and Discussion

In this division, results of the present experimental investigation are presented and discussed.

Firstly, plain channel without twisted tape is investigated experimentally as shown in Fig. 3. Here, the results are compared with the empirical correlations by Gnielinski (1985) for the Nusselt number, and friction factor in the turbulent region. A quite good agreement with the present predictions and the present experiments is observed in Fig. 3a, b. Also, the results of the present study are very close to those reported by the same research group (Bhattacharyya et al. 2018; Eiamsa-ard and Promvonge 2005; SEiamsa-ard et al. 2009) and are shown in Fig. 3c, d. The considerable deviation of the present study from those reported in the other works may relate to the difference of the geometric parameters of the turbulator channels.

Fig. 3
figure 3

a Verification of Nusselt number of plain channel, b verification of friction factor of plain channel, c comparison with the literature of forced convection Nusselt numbers for different swirl generators and d comparison with the literature of forced convection friction factor for different swirl generators

Gnielinski correlation (Ozisik 1985) is as follows:

$$Nu = \frac{{\left( {f/8} \right)\left( {Re - 1000} \right)Pr}}{{1 + 12.7\left( {f/8} \right)^{1/2} \left( {Pr^{2/3} - 1} \right)}}$$
(9)
$$f = \left( {0.79\ln \left( {Re} \right) - 1.64} \right)^{ - 2}$$
(10)

The friction factor and Nusselt number are solid functions of twist ratios. The effect of twist ratio with y = 15.0 and 45.0 at constant t/D = 0.0417, d = 0.75 and 0.66 of the twisted tape has not been presented separately since the results with y = 15.0 and 45.0 at constant t/D = 0.0458 and d = 0.83 were similar as shown in Fig. 4. Twisted tape of twist ratio y = 15.0 promisingly enhances the heat transfer rate than the tape of twist ratio y = 45.0; this is due to the increased turbulence intensity (TI) which helps in disrupting a thermal boundary layer thickness. Furthermore, the interaction among the secondary flows made by the swirl generators also facilitates the disruption of the viscous sub-layer near channel wall resulting in greater heat transfer enhancement. The flow wavering due to the change of tape twist ratio causes the formation of vortices which further enhance turbulence and thus convective heat transfer rate. The result is expected and it is explained by the fact that, in case of twisted tape of twist ratio y = 45.0, it cannot provide much of swirl flow and mixing of fluids; hence, there is the disturbance of the boundary layer formation in a dominant manner.

Fig. 4
figure 4

a Effect of twist ratio on friction factor, full-length twisted tape: at constant tape thickness ratio δ = 0.0458 and diameter ratio d = 0.83 and b effect of twist ratio on Nu, full-length twisted tape: at constant tape thickness ratio δ = 0.0458 and diameter ratio d = 0.83

Tape thickness is an important parameter in this study. Tape thickness plays a major role in enhancing heat transfer. There are both pressure drop and heat transfer decrease with the decrease in the value of tape thickness ratio as shown in Fig. 5. Whether the geometry of the channel is circular or non-circular, the effect of twisted tape thickness on friction factor is almost the same; this is correct for all sorts of twisted tapes. The friction factor and Nusselt number increase with the increase in tape thickness ratio.

Fig. 5
figure 5

a Effect of tape thickness ratio on friction factor, full-length twisted tape: at constant twist ratio y = 15.0 and diameter ratio d = 0.83, b effect of tape thickness ratio on Nu, full-length twisted tape: at constant twist ratio y = 15.0 and diameter ratio d = 0.83

The experimental results of heat transfer of the channel fitted with SLTT and FLTT under constant heat flux condition are shown in Fig. 6. The FLTT (L/D = 90) shows some promising results in terms of heat transfer compared with the SLTT (L/D = 54). This is due to continuous swirl flow throughout the test section; also it destroys the thermal boundary layer more than that of SLTT. The stronger swirl flow causes higher TI, better fluid mixing and thus superior heat transfer. So, this can clarify the FLTT prompts swirling flow more than SLTT which is beneficial to stimulating the fluid mixing inside the channel. As a result, FLTT increases the mixing rate of the fluids. Although both the tapes (SLTT and FLTT) provide strong swirl flow at the channel entry. Similarly, it is observed that for the channel with both twisted tapes (SLTT and FLTT) there is a considerable rise in the flow friction than for the channel without twisted tape. The flow friction of SLTT is found to decrease in comparison with FLTT. This is due to the decrease in length ratio (L/D) which provides lower swirling strength, which leads to low pressure penalty.

Fig. 6
figure 6

a Effect of diameter ratio and twist ratio on friction factor, full-length twisted tape: at constant twist tape thickness ratio δ = 0.0458, b effect of diameter ratio and twist ratio on Nu, full-length twisted tape: at constant tape thickness ratio δ = 0.0458

Diameter ratio also plays an important role in enhancing heat transfer inside a channel. For large diameter ratio, d = 0.83 in Fig. 7, an improvement of heat transfer is observed throughout the varied Reynolds numbers range than the other two tested diameter ratios (0.75 and 0.66). However, friction factor increases with the increase in Reynolds number. This is due to the increase in the tape friction in the initial stages.

Fig. 7
figure 7

a Effect of diameter ratio and twist ratio on friction factor, short-length twisted tape: at constant twist tape thickness ratio δ = 0.0458, b effect of diameter ratio and twist ratio on Nu, short-length twisted tape: at constant tape thickness ratio δ = 0.0458

Performance of the present duct geometry has been evaluated on the basis of performance criteria defined by Bergles et al. (1974). Bergles et al. (1974) have suggested several criteria for the performance evaluation of enhancement devices. The performance of the present geometry has been evaluated on the basis of the following two important criteria:

  • Criterion 1 Basic geometry fixed, pumping power fixed—increase heat transfer—performance ratio R1.

  • Criterion 2 Basic geometry fixed, heat duty fixed—reduce pumping power—performance ratio R2.

The subscripts ‘SLTT’ and ‘FLTT’ refer to short-length twisted tape and full-length twisted tape, respectively

$$R_{1} = \frac{{Nu_{\text{FLTT}} }}{{Nu_{\text{SLTT}} }}$$
(11)
$$R_{2} = \frac{{\left( {fRe^{3} A_{\text{c}} } \right)_{\text{FLTT}} }}{{\left( {fRe^{3} A_{\text{c}} } \right)_{\text{SLTT}} }}.$$
(12)

The pumping power reduces up to 27% for full-length twisted tape cases compared to short-length twisted tape at constant heat duty. Similarly, heat duty increases up to 33% as shown in Table 2 at constant pumping power.

Table 2 Performance ratios of R1 and R2

5 Conclusion

The thermohydraulic characteristics of turbulent flow of air through circular channels with twisted tape turbulators inserts have been investigated experimentally. For the SLTT and FLTT arrangement, three different diameter ratios (d), two different twist ratios (y) and two different tape thickness ratios (δ) are studied for Reynolds numbers (Re) varying from 6000 to 20,000.

Thus, among the considered arrangements, the highest Nusselt number values are obtained for the case d = 0.83, y = 15 (applicable for both FLTT and SLTT), compared to the other tested tape and plain channel, over the considered range of Re. The case d = 0.66, y = 45 (applicable for both FLTT and SLTT) gives the minimum Nusselt number values, which are, however, still larger than those of the plain channel. For all Re, heat transfer is observed to increase with the increasing tape thickness ratio and diameter ratio but decrease with increasing twist ratio. FLTT was found considerably superior than SLTT.