1 Introduction

Underwater tunnels cross rivers, lakes or seas with a large gradient and height difference between the both sides and the middle part, and thus form a V-shaped structure. While underwater tunnels perform their functions, their fire characteristics are different from those of general tunnels due to their geographical location and V-shaped slope structure, which are mainly reflected in the fact that the traffic accident rate and the probability of fire in slope tunnels are much higher than those in horizontal tunnels [1,2,3]. In addition, under the influence of the chimney effect in inclined tunnels, the smoke will spread uphill [4], which makes it difficult to determine the direction of smoke movement and smoke control in V-tunnels. At the same time, the slope of the tunnel reduces the average escape velocity of personnel [5], which will increase the difficulty of emergency evacuation. Stable high smoke stratification can reduce the impact of fire smoke on the evacuation of trapped tunnel personnel [6]. The rapid cooling ability of water spray system is exactly suitable for tunnel fires, and water spray system has been adopted in many tunnels in China, such as the Wuhan Yangtze River Tunnel and the Xiamen Xiang'an Undersea Tunnel [7]. However, it can also disturb the stable smoke layer to a certain extent, causing smoke settlement and endangering the safety of evacuees. Therefore, it is of great significance to study the effect of water spray system on smoke stratification in V-tunnel fires for effective fire smoke control and optimization of system parameters.

Due to geographical factors, existing tunnels are often not completely horizontal. When a fire breaks out in an inclined tunnel, the superimposed effect of the height difference between the exits at the two ends of the tunnel and the difference between the internal and external temperatures will produce a chimney effect, accelerating the diffusion and spread of high-temperature smoke uphill, and the movement of the smoke therefrom will be altered. Kang [8] also proposed that in the case of inclined tunnels with shafts for natural smoke evacuation, the smoke transport mechanism will be more complicated. Morlon [9] investigated both the thermal and the optical effects through the interaction of the water mist with the smoke layer produced by a fire, and concluded that, in order to provide the environmental complete characterization, both opacity measurements and temperature measurements should be made. Fan [10] used FDS to investigate the impact of roadway slope and length on smoke movement, and obtained a critical value of 100 for the number of Ri. Kong [11] proposes a non-dimensional empirical correlation of fire backing lengths for tilted tunnels with different slopes, where the dimensionless smoke backing lengths are logarithmically correlated with the cubic power of the downstream lengths. Cano-Moreno [12] proposes a quantitative method, based on linear multiple regression, that can account for the number of fatalities as a function of the delay in the start of evacuation and the slope of the tunnel, thus combining the consideration of the evacuation of tunnels as well as the effect of the slope of tunnels on the dispersion of gases and fumes. It should be noted that the above research work only focuses on single-slope tunnels, but the actual underwater tunnels often present multi-slope structures similar to the V, U, and W shapes due to the limitation of topography and other factors. These multi-slope tunnels have one or more variable slope points with up and down slopes, and the change of the relative positions of the fire source and the variable slope points will make the direction of thermal buoyancy complex, and its fire smoke transport characteristics are more special.

Some researchers have investigated water spray system effects on tunnel fire smoke control. Bullen [13] initially elucidated the impact of water mist on the stability of smoke stratification, attributing it to a delicate equilibrium between the resistance of water spray and the buoyancy of hot smoke. Bu [14] demonstrated that fine water spray controls smoke temperature and that the use of longitudinal ventilation significantly improves the fire stopping effect of water-spray fire suppression systems. Li [15] focused their research on studying the interaction between fine water spray and fire sources in tunnel configurations, utilizing both experimental and numerical methods. Luan [16] obtained that the smoke layer flow pattern may be disrupted by matching the sprinklers with the ventilation system. Wang [17] used simulations to examine the effects of water spray jet flow rate and spray angle on the critical velocity of longitudinal ventilation tunnels to obtain a unified correlation model for the critical velocity of such tunnels. Deng [18] suggest a hierarchical model of tunnel smoke and demonstrated that the correlation between the drag effect of water spray and the size of droplets. Wang [19] used numerical simulation to introduce water spray intensity and momentum ratio to clarify the smoke barrier and thermal insulation effect. Obviously, the water spray will weaken the fire thermal buoyancy, change the mechanical ventilation, bilateral chimney effect, so that the smoke flow in multi-slope tunnels between the multiple driving forces of this and that produce a competitive relationship, resulting in the smoke flow in the bi-directional flow, transitional flow, unidirectional flow between the turning uncertainty; and the current research focuses on the influence of a single or two factors on the flow of the smoke, such as: natural and longitudinal ventilation under the single-slope tunnels, horizontal tunnels, etc., did not take into account the complexity of the coupling role of the water spray-multi-slope structure of the multifactor, and is also not in line with the actual application of the engineering situation.

A stable smoke layer during the expansion period of a one-dimensional plume can guarantee the safety of evacuation in case of fire, and is an important basis for the design of tunnel fire protection system parameters. Some researchers have investigated fire smoke stratification behavior and its stability criteria in a horizontal tunnel. For example, Newman [20] discovered an obvious smoke-air stratification related to a Froude (Fr) number especially under windless condition in ventilated duct fires, and divided fire smoke on fire source downstream into three regions according to Froude number values. Nyman and Ingason [21] conducted large-size experiments to verify the accuracy of Newman's smoke stratification Fr (< 0.9), and found critical Fr 0.55. Ingason [22] found that thermal pressure and fire plume buoyancy contributed to stable smoke stratification and proposed the relationship correlation between thermal stratification and smoke concentration distribution. Huang [23] applied Newman's smoke stratification theory to a building corridor and proposed that smoke stratification is evident when Fr is less than 0.58. Tang [24] obtained that buoyancy stratification can be divided into stable stratification, stable stratification by some vortices, and unstable stratification where the upper buoyant smoke stream is strongly mixed with the lower stream. Li [25] explored the relationship between the height of the fire source and the hot smoke stratification upstream of the tunnel and found that the hot smoke stratification matched Newman's measurements regardless of the height of the fire source.

Most of the above domestic and international studies have been carried out in horizontal tunnels with water spray systems or slope tunnels without water spray systems, and have not yet dealt with the study of the influence of smoke layer characteristics under the combination of the two. When a fire occurs at different locations in a naturally ventilated underwater V-tunnel, the smoke is subject to the bilateral chimney effect and thermal buoyancy competing with each other to present three flow behaviors: bidirectional, transitional and unidirectional flow [26]. The V-slope of underwater tunnels is more complicated in smoke movement under the coupling effect of the two slopes, and the randomness of the position of the fire source also increases the uncertainty of the smoke movement, which, together with the cooling, dragging and blocking effects of the water spray, will make the smoke control more complicated. When a vehicle catches fire in a tunnel, its location is difficult to be exactly at the point where the tunnel changes slope due to the uncertainty of the accident. When the location of the fire is not in the tunnel slope change point, because the location of the fire source and the tunnel exit on both sides of the elevation difference and density difference, both sides of the existence of the chimney effect, the fire smoke movement to produce competition, this time is called “double-slope stack effect”, high temperature and high toxicity of smoke spreading situation is more complex. In the event of a fire, the uphill section of a V-slope tunnel becomes the main channel for the rise of hot air and smoke. Due to the change in gradient, hot air rises more rapidly in the uphill section, creating a pronounced chimney effect. Concurrently, cold air from the downhill section or the tunnel entrance is drawn into the tunnel due to the lower pressure in the uphill section, supplementing the heated and rising air. In single-slope tunnels, smoke typically spreads uphill, with the chimney effect being directly proportional to the slope; that is, a larger slope results in a more pronounced chimney effect. In a fully symmetrical V-slope tunnel, where the slopes are reversed, smoke may exhibit different spreading patterns on either side, potentially competing against or offsetting the chimney effect.

Therefore, this paper comprehensively analyzes the effects of the symmetrical V-shaped double slope gradient, water spray flow rate and angle on the maintenance of stable fire smoke stratification when the water spray system is employed. The aim is to determine the stability law of tunnel smoke stratification and put forward the theoretical support for the prevention and control of smoke in the tunnel.

2 Theoretical Analysis

2.1 Smoke Stratification Mechanism

The purpose of this study was to better understand the smoke deposition phenomena that may occur in a fully symmetrical V-slope tunnel fire using water spray system. Smoke thermal stratification refers to the phenomenon where the fire approximates the tunnel into two distinct layers: the upper part, which is high-temperature smoke, and the lower part, which is cold air. High-temperature smoke exhibits stratification due to the combined effects of thermal buoyancy and horizontal inertia forces during a fire [27, 28]. To effectively control smoke, the water spray system must be activated promptly. The sprayed water droplets can disrupt the relatively stable smoke layer, potentially leading to significant smoke settling. Previous studies [13, 29, 30] have identified two fundamental mechanisms by which water droplets induce smoke settling: the downward drag force exerted on the surrounding gas, and the cooling effect that reduces the buoyancy of the smoke.

Within the direct-action area of the water spray system (i.e., within 30 m of the fire source), the smoke is subjected to a drag force from the water spray system. Additionally, the lower temperature of the water droplets compared to the smoke leads to heat exchange, which reduces the smoke's temperature and, by the principles of ideal gas behavior, increases its density. In areas not directly affected by the water spray, the interaction between the water and smoke is minimal. This results in the high-density smoke in these regions experiencing downward buoyancy relative to the lower-density smoke in the surrounding environment. As the smoke settles under the dual influence of the water spray's drag force and its own downward buoyancy, the settled smoke, despite having increased in density due to cooling by water droplets, remains lighter than the lower layer of cold air. Consequently, the smoke will begin to exhibit upward buoyancy. As the settling smoke accumulates and its volume increases, the upward buoyancy also increases. Once the upward buoyancy balances the downward forces, the smoke will cease to settle and stabilize at a certain height. Tang [31] proposed a new combined force equilibrium system considering the downward drag force exerted by the water particles on the surrounding gas and the cooling effect of the water particles on the smoke resulting in the reduction of the smoke buoyancy. In conjunction with this paper, taking the double slope stack effect induced by the V-shaped tunnel structure into consideration, a new driving force balance relationship (the drag force of the water spray Fd, the stack effect of left tunnel Ps,l, the stack effect of right tunnel Ps,r, and the thermal buoyancy Pf) for fire smoke in a V-shaped tunnel is given in Fig. 1.

$$F_{d} = \mathop {m_{w} }\limits^{.} (v_{z,in} - v_{z,out} ) + m_{w} g\cos i$$
(1)

where \(\mathop {m_{w} }\limits^{.}\) and \(m_{w}\) are the mass flow rate and the total water particle mass interacting with fire smoke respectively, kg/s and kg; \(v_{z,in}\) and \(v_{z,out}\) are the vertical velocities of water droplets entering and leaving the smoke layer respectively, m/s; i is the inclination angle of the tunnel.

Figure 1
figure 1

Driving forces for fire smoke in a V-shaped tunnel

PA is the buoyancy of the smoke in the region where the water droplets interact with the original smoke layer, N; PB is the buoyancy in the region of the smoke that descending to the lower layer of cold air, N. So a total thermal buoyancy can be expressed [32] by

$$P_{f} = P_{A} - P_{B} = (\Delta \rho_{i,a} V_{i,a} - \Delta \rho_{i,s} V_{i,s} )g{\text{ cos}}i$$
(2)

where \(\Delta \rho_{i,a}\) and is the density difference between smoke settling into the cool air layer air and the cool air, kg/m3; \(V_{i,a}\) is the settling smoke volume into the cool air layer, m3; \(\Delta \rho_{i,s}\) is the density difference between the smoke layer interacting with water droplets and that without water droplets, kg/m3; \(V_{i,s}\) is the smoke volume interacting water droplets, m3.The total driving force caused by the double slope stack effect of left and right tunnel part is:

$$P_{s} = \Delta \rho \Delta hg\cos i$$
(3)

where \(\Delta \rho\) is the density difference between smoke front and air, kg/m3; \(\Delta h\) is the smoke spreading height, m.

2.2 Dimensionless Analysis

In tunnel, the smoke layer thickness is related to the following factors: fire heat release rate Q, tunnel height H, symmetrical V-shaped tunnel gradient i, ambient air temperature \(T_{\infty }\), ambient air density \(\rho_{\infty }\), constant pressure specific heat capacity of air \(c_{p}\), gravitational acceleration g, and water spray flow rate q. Then the following relationships can be listed:

$$f\left( {Q,h{,}H,i,T_{\infty } ,\rho_{\infty } ,C_{p} ,g,q} \right) = 0$$
(4)

According to the π-theorem, H, ρ, T, and g as the basic parameters, a new expression for Eq. (4) is given:

$$f\left( {\pi_{1} ,\pi_{2} ,\pi_{3} ,\pi_{4} ,\pi_{5} } \right) = 0$$
(5a)

where

$$\left\{ {\begin{array}{*{20}l} {\pi _{1} = H^{{\alpha _{1} }} \rho _{\infty }^{{\beta _{1} }} T_{\infty }^{{\gamma _{1} }} g^{{\varepsilon _{1} }} h} \hfill \\ {\pi _{2} = H^{{\alpha _{2} }} \rho _{\infty }^{{\beta _{2} }} T_{\infty }^{{\gamma _{2} }} g^{{\varepsilon _{2} }} Q} \hfill \\ {\pi _{3} = H^{{\alpha _{3} }} \rho _{\infty }^{{\beta _{3} }} T_{\infty }^{{\gamma _{3} }} g^{{\varepsilon _{3} }} i} \hfill \\ {\pi _{4} = H^{{\alpha _{4} }} \rho _{\infty }^{{\beta _{4} }} T_{\infty }^{{\gamma _{4} }} g^{{\varepsilon _{4} }} C_{p} } \hfill \\ {\pi _{5} = H^{{\alpha _{5} }} \rho _{\infty }^{{\beta _{5} }} T_{\infty }^{{\gamma _{5} }} g^{{\varepsilon _{5} }} q} \hfill \\ \end{array} } \right.$$
(5b)

The following 5 dimensionless terms are obtained through dimensional analysis:

$$\left\{ {\begin{array}{*{20}l} {\pi _{1} = h/H} \hfill \\ {\pi _{2} = Q/(\rho _{\infty } g^{{3/2}} H^{{7/2}} )} \hfill \\ {\pi _{3} = i} \hfill \\ {\pi _{4} = T_{\infty } C_{p} /(gH)} \hfill \\ {\pi _{5} = q/(H^{{5/2}} g^{{1/2}} )} \hfill \\ \end{array} } \right.$$
(6)

Expressing Eq. (5) can be achieved by the following equation:

$$f\left( {\frac{h}{H},\frac{Q}{{\rho_{\infty } g^{3/2} H^{7/2} }},i,\frac{{T_{\infty } C_{P} }}{gH},\frac{q}{{H^{5/2} g^{1/2} }}} \right) = 0$$
(7)

By the similarity principle, Eq. (7) can be converted to:

$$\frac{h}{H} = f\left( {\frac{Q}{{\rho_{\infty } g^{3/2} H^{7/2} }},i,\frac{{T_{\infty }^{{}} C_{p} }}{gH},\frac{q}{{H^{5/2} g^{1/2} }}} \right)$$
(8)

Equation (8) is also expressed as:

$$h^{*} = f(Q^{*} {, }i, \, q^{*} )$$
(9)

where \(h^{*} = \frac{h}{H}\), \(Q^{*} = \frac{Q}{{\rho_{\infty } T_{\infty }^{{}} C_{p} g^{1/2} H^{5/2} }}\), \(q^{*} = \frac{q}{{g^{1/2} H^{5/2} }}\).

Calculations show that the tunnel gradient i, dimensionless fire heat release rate Q*, and dimensionless water spray system flow rate q* are the factors influencing the dimensionless smoke layer thickness in a symmetrical V-shaped tunnel.

2.3 Froude Number for Smoke Stratification

Smoke stratification criteria Fr is related with the smoke temperature stratification and can be calculated by [21]:

$$Fr = \frac{{u_{avg} }}{{\sqrt {\frac{{\Delta T_{cf} }}{{T_{avg} }}Hg} }}$$
(10)

where, \(u_{avg}\) and \(T_{avg}\) represent the average flow velocity and average smoke temperature of the tunnel cross-section, respectively; \(\Delta T_{cf}\) is the smoke temperature difference between beneath ceiling (0.88 × H) and under floor (0.12 × H),°C; H is the tunnel height, m; take g = 9.81 m/s2.

For a given tunnel, Fr is determined by the smoke flow rate and temperature which can be changed by water spray system directly. Therefore, Fr values for smoke stratification would be different from those without water spray system.

3 Numerical Methods

3.1 Fire Scenarios

In this paper, fire simulation calculations using Fire Dynamics Simulator (FDS) version 6.6.0 have been carried out to investigate fire scenarios in tunnels with natural ventilation systems. Smoke layer height is an important indicator of the safety of people in the flow of smoke from a road tunnel fire. In FDS, the smoke layer height is predicted and calculated using the method proposed by Janssens [33]. based on the cross-sectional vertical smoke temperature distribution, which has been widely used in previous studies [34,35,36]. In this method, the temperature Tz is considered to be a continuous function between the floor (z = 0) and (z = H) the ceiling with respect to the height z. Tlow is assumed to be a constant equal to the value of the temperature of the cell closest to the floor, and Tup varies as a vertical gradient with height. The formulae for these two temperatures are given below:

$$\left( {H - h} \right)T_{up} + hT_{low} = \int \begin{gathered} H \hfill \\ 0 \hfill \\ \end{gathered} T\left( z \right)dz = I_{1}$$
(11)
$$\left( {H - h} \right)\frac{1}{{T_{up} }} + h\frac{1}{{T_{low} }} = \int \begin{gathered} H \hfill \\ 0 \hfill \\ \end{gathered} \frac{1}{T\left( z \right)}dz = I_{2}$$
(12)
$$h = \frac{{T_{low} \left( {I_{1} I_{2} - H^{2} } \right)}}{{I_{1} + I_{2} T_{low}^{2} - 2T_{low} H}}$$
(13)

where Tup is the upper layer temperature, K; Tlow is the lower layer temperature, K; H is the ceiling height, m; and h is the smoke layer interface height, m.

FDS can simulate and solve all kinds of fire scenarios flexibly by using the above set of equations, and can predict the changes and flow patterns of smoke temperature, co and other substances during the dynamic development of fire. More information on the theory and algorithms of the numerical simulation method and validation can be found in the FDS User Guide [37].

As shown in Fig. 2(a), the tunnel foundation model, built by FDS [38], measures 600 m in length, 13.2 m in width, and 8.1 m in height. Based on this model, three different scenarios with tunnel gradients of 0%, 3%, and 5% are studied. The fire source in the simulation uses n-heptane as fuel, with dimensions of 4.5 m × 3 m × 2 m, and the fire type is set as a constant fire source. The rate of heat release is set to 5 MW, 10 MW, 15 MW, and 20 MW, respectively, and does not change with time. The two ends of the tunnel are defined as ‘OPEN’, and the boundaries of the roof, side walls, and floor of the tunnel are defined as ‘CONCRETE’. The thermophysical properties are based on those of actual concrete materials [39, 40]. The specific heat is 1.04 kJ/(kg·K), the density is 2280 kg/m3, and the thermal conductivity is 1.8 W/(m·K). The entire tunnel is naturally ventilated, with an ambient temperature of 20 °C.

Figure 2
figure 2

V-shaped slope tunnel fire simulation schematic

According to the results of previous studies, the vertical location of the maximum temperature in the tunnel is 0.02H below the roof, where H is the tunnel height [41]. Therefore, a series of temperature measurement points were arranged along the longitudinal center line of the tunnel at 0.16 m below the roof, with a distance of 1.5 m. Vertical temperature and velocity measurement points were set up from 3 m away from the fire source, with a spacing of 0.2 m. The temperature and velocity measurement points were set up at 0.2 m apart, with a spacing of 1.5 m from the fire source. Water spray nozzles were installed at a distance of 5 m on both walls at a height of 4.5 m. The flow rate and angle of the water jets were adjustable from 0 L/min to 250 L/min and from 0° to 150°, respectively.

Considering that fires can occur at various locations within the tunnel, the distance of the fire source from the slope change point is defined as the ‘fire source location’. This distance is specified at 0 m, 10 m, 20 m, 40 m, 60 m, 80 m, 100 m, and 120 m. The fire source is uniformly positioned along the left side of the tunnel at these locations. In total, there are 315 groups of working conditions, with detailed parameters provided in Table 1. The output data, including smoke temperature and visibility, reach a stable state at about 300 s. Therefore, the analysis presented below utilizes the mean values of the output data recorded between 300 s and 400 s.

Table 1 Tunnel Model Working Condition Table

3.2 Grid Independence Analysis

FDS user guide recommends to adopt the grid size from 1/16D* to 1/4D* [37], where the fire characteristic diameter D* is defined by:

$$D^{*} = \left( {\frac{Q}{{\rho_{\infty } c_{p} T_{\infty } \sqrt {\text{g}} }}} \right)^{2/5}$$
(14)

where Q is fire heat release rate, kW; \(\rho_{\infty }\) is ambient air density, 1.02 kg/m3; \(c_{p}\) is air constant pressure specific heat capacity, 1.004 J/(kg·K); \(T_{\infty }\) is the ambient air temperature, 293.15 K; g is gravity acceleration, 9.81 m/s2. From Eq. (14) it can be seen that for fire heat release rates of 5 MW to 25 MW, grid sizes are calculated from 0.15 m to 0.60 m.

Four grid sizes, 0.15 m, 0.20 m, 0.30 m and 0.60 m, were selected to verify their accuracy by comparing the maximum smoke temperatures along the length of the tunnel without and with water spray in Fig. 3(a, b). The variation curves of the smoke and its temperature for the grid size of 0.3 m is basically the same as those for the grid sizes of 0.15 m and 0.2 m were found to be the same. Many studies [42, 43] have shown that the FDS model can be validated based on the differences in maximum smoke temperatures at different locations. Meanwhile, the construction of Li [44] model mainly relies on the size and magnitude analysis, which is exactly the same in this paper. The Li model is simulated in this paper without longitudinal ventilation at velocity less than 0.19, and the numerical comparison of the simulation is shown in Fig. 3, the simulated tunnel roof smoke temperature at 0.3 m grid size is consistent with the experimental results of Li. Therefore, a 0.3 m grid is chosen in this paper.

Figure 3
figure 3

Grid independence and simulation accuracy analysis

4 Results and Discussion

4.1 Water Spray Flow Rate Effect on Smoke Stratification

When a fire occurs in the tunnel, fire smoke driven by thermal buoyancy flows vertically, continuously impinges the tunnel ceiling into horizontal flow, and then turns into a one-dimensional longitudinal flow due to the sidewall restriction [33]. The average smoke layer thickness values between 10 m to 30 m from fire source in water spray zone are analyzed here [45].

Figure 4. shows the smoke layer thickness changes with increasing water spray flow rates in the V-shaped tunnel with different slopes. Overall, the smoke layer thickness decreases with the increase of the water spray flow rate. In the case of the same tunnel gradient and the same water spray flow rate, the fire heat release rate is high, the amount of fire smoke produced is large, and the smoke layer thickness becomes thicker accordingly. In the case of the same fire heat release rate and the same water spray flow rate, the smoke layer thickness tends to decrease with the increase of the tunnel gradient. This is due to the slope of the tunnel stack effect is more obvious, the tunnel smoke force is greater, so that the thin smoke layer below the stable smoke further upward cohesion. And in the case of the same tunnel slope, the same fire heat release rate, high water spray flow rate than low water spray flow rate smoke layer thickness is smaller. That is, it indicates that more toxic smoke settles into the air layer, thus affecting the evacuation of people in the tunnel.

Figure 4
figure 4

Variation curve of smoke layer thickness with water spray flow in the V-shaped tunnel with different slopes

Since the smoke layer thickness is proportionate to smoke yield which is a power function relationship with fire heat release rate based on classical fire plume mass flow rate model [31], Eq. (15) can be given as:

$$\frac{h^{*}}{{Q^{*0.33} }} = f(i, \, q^{*} {) }$$
(15)

According to simulation data and Eq. (15), The dimensionless smoke layer thickness in the symmetric V-shaped tunnel is illustrated in Fig. 5 as follows:

$$h^{*} = [(2.50i - 0.35)q^{*} + ( - 2.69i + 1.08)]Q^{{*0.33}}$$
(16)
Figure 5
figure 5

Correlation for smoke layer thickness in the V-slope tunnel considering water spray flow rate effect

Figure 6 plots average Fr values for smoke flow within 10 m to 30 m from fire source in the V-shaped tunnel fires with different fire heat release rates and slopes versus normalization water spray flow rate. Obviously, Fr initially decreases and then steadily increases as the water spray flow rate increases. When the water spray flow rate is less than 50 L/min (q* = 0.6), its effect on the thermal buoyancy force Pf and drag force Fd is weak. And because Pf > Fd, that is, the upward driving force is stronger than the downward driving force, smoke gathers beneath the ceiling and settles little. At these conditions, Fr gradually decreases as the water spray flow rate increases, and the smoke layer thickness changes little. After the water spray flow rate increases to 50 L/min (q*= 0.6), Pf decreases and Fd increases because of the stronger cooling effect. Overall Pf < Fd, that is, the upward driving force is weaker than the downward driving force, the temperature of the tunnel ceiling decreases, and the fire smoke gradually sinks. At this time, Fr increases with the increase of spray flow, and the smoke layer thickness gradually decreases.

Figure 6
figure 6

Fr for smoke stratification in the V-shaped tunnel fires with different fire heat release rates and slopes versus normalization water spray flow rate

Regarding this one, the tendency for the Fr number to show a decreasing and then increasing trend with increasing flow in horizontal tunnels is relatively less pronounced. It is because the increase in tunnel slope enhances the stack effect force Ps, so fire smoke flows faster. From Sect. 2.3, Fr is proportional to the average smoke flow velocity through tunnel cross-section, so corresponding Fr is larger in larger sloped tunnel in Fig. 6.

To investigate the turning point of Fr with the increase of water spray flow rate, a fitted straight line of the falling and rising segments of Fr values for 10 MW tunnel fires is plotted in Fig. 7(a). When Fr is less than turning point, smoke flow is dominated by Pf. While Fr is larger than turning point, the dominated factor of smoke flow changes into Fd. Figure 7(b) gives Fr values at turning points (Critical Fr) for all V-shaped tunnel fires of various heat release rates and slopes. Clearly, critical Fr increases as fire heat release rate increases, and Fr’s corresponding water spray flow rate increases. Because larger fire heat release rate enhances smoke temperature and flow rate and leads to smoke settling at a larger water spray flow rate. Critical Fr values for 5% sloped tunnel is larger than those for 3% now in Fig. 7(b). Critical Fr line for 3% sloped tunnel would intersect with that for 5%, when heat release rate increases continuously, indicating that the stack effect on smoke stratification is outplayed by thermal buoyancy effect of higher fire heat release rate.

Figure 7
figure 7

Fr and critical Fr values for V-shaped tunnel fires of different heat release rates and water spray flow rates

4.2 Water Spray Angle Effect on Smoke Stratification

Figure 8 shows the smoke distribution of 10 MW 3% slope tunnel fires with various angles from 0° ~ 150°of the water spray system. For tunnel fires without water spray system, the fire smoke appears as one-dimensional longitudinal flow within the middle zone of the V-shaped tunnel right and left side. Smoke flow stratification in the tunnel can be approximately classified into three layers including the upper layer with high-temperature smoke, the middle layer with smoke-air mixing and the lower layer with cold air as shown in Fig. 9(a). After the activation of the water spray system, fire smoke moves downward gradually under the action of drag force Fd, and blends with the cold air to form smoke-air mixing layer. The original three layers in the tunnel without water spray are disturbed by the water spray system, and the cold air layer gradually disappears. Finally there are only the upper high-temperature smoke layer and lower smoke-air mixing layer as shown in Fig. 9(b). By comparing smoke distribution in Fig. 8, it is not intuitively apparent that the increase of water spray angle has obvious influence on fire smoke spread process.

Figure 8
figure 8

Smoke distribution of 3% sloped tunnel fires with 10 MW under different water spray angles (a) 0, (b) 30°, (c) 60°, (d) 90°, (e) 120°, f 150°

Figure 9
figure 9

Schematic diagram of smoke stratification in the V-shaped tunnel: (a) without water spray, (b) with water spray

Figure 10 plots Fr values for V-shaped tunnel fires of different heat release rates and water spray flow rates, which fluctuates little and have a little bit of a downward trend as water spray angle increases in sloped tunnels. Because the action area of water spray droplets on smoke is enhanced, the drag force Fd on the same volume smoke becomes less. And then the smoke subsidence degree is reduced, thus forming more stable smoke layer. Fr values in 0%, 3%, 5% slope tunnel fluctuate within 0.007, 0.009, 0.011 respectively, and the overall fluctuation is basically within 5%. Therefore, in the V-shaped tunnel fires, the effect of water spray angle on Fr is very small, which is basically the same as its effect on smoke layer thickness in Sect. 4.1, that is, the angle of water spray system in a V-shaped tunnel has little effect on Fr.

Figure 10
figure 10

Fr values for V-shaped tunnel fires of different heat release rates and water spray angles

4.3 Fire Source Location Effect on Smoke Stratification

In this paper, when considering the increase in the distance between the fire source and the variable slope point of the tunnel, the influence on the smoke layer thickness of the tunnel is divided into three phases: (I) double-slope control phase, where the distance between the fire source and the variable slope point of the tunnel is 0 m to 10 m; (II) transition phase, where the distance between the fire source and the variable slope point of the tunnel is 20 m to 80 m; and (III) single-slope control phase, where the distance between the fire source and the variable slope point of the tunnel is 100 m to 120 m. The fire source and the variable slope point of the tunnel are divided into three phases.

Figure 11 depicts smoke spread in 10 MW V-shaped tunnel fires at various slopes, with the fire source located 120 m away from the grade change point (fire source moves to the left from the centre at 0% gradient). Obviously, fire smoke in 0% slope tunnel spreads to the right tunnel opening, and that in 3% slope tunnel spreads to the middle zone of the right tunnel, while fire smoke in 5% slope tunnel still does not spread to the grade change point. In other words, fire smoke spreads downstream slower from fire source location to the grade change point, as the tunnel slope increases. Because the coupling right and left stack effect force Ps increases in a large slope tunnel, blocks smoke spreading to the grade change point.

Figure 11
figure 11

Smoke spread of 10 MW V-shaped tunnel fires when fire source is 120 m from the grade change point (a) 0% slope, (b) 3% slope, (c) 5% slope

To examine how the distance between the fire source and grade change point affects the smoke layer thickness, Fig. 12 plots smoke layer thickness in V-shaped tunnel fires with various heat release rates and tunnel slopes. The three regions, labeled as I, II, and III, represent different stages: the double-slope control stage, the transition stage, and the single-slope control stage, respectively [26]. Different from the temperature change in previous study, on the double-slope control stage, there is considerable difference of the smoke layer thickness between the left and right of fire source. Because a large amount of smoke gathers between tunnel grade change point and fire source location, when fire source moves 10 m to the left of the tunnel grade change point, the smoke layer thickness on the tunnel right side decreases. on the single slope control stage, the smoke layer thickness changes less and basically stabilize.

Figure 12
figure 12

Smoke layer thickness of V-shaped tunnel fires sources with different heat release rates and slopes versus the distance between fire source and grade change point

Figure 13 shows Fr values of 3%, 5% V-shaped tunnel fires with different heat release rates versus the distances from fire source to grade change point. On the double-slope control stage, Fr changes a little, which is consistent with the smoke layer thickness trend. On transition phase, Fr increases on the left and decrease on the right of fire source, and eventually both levels off. On the single slope control stage, Fr for the same heat release rate tends to be stable, when the distance from fire source location to the tunnel grade change point increase. The average Fr values are summarized in Table 2.

Figure 13
figure 13

Fr curve of the distance of fire source from the variable slope point in tunnels with different slopes

Table 2 Average Fr Values on the Third Stage (Single-Slope Control Stage)

5 Conclusions

The influence of water spray system parameters (flow rate and angle) and fire source location on smoke spread in V-shaped tunnel fires are investigated through theoretical and numerical simulation analysis. The smoke layer thickness and Fr values are obtained to explain the change law. The conclusions include as follows:

An increase in water spray flow rate causes a decrease of the smoke layer thickness. A correlation for smoke layer thickness considering the flow rate of water spray system and tunnel slope is proposed through the dimensionless analysis and simulation data analysis. Correspondingly, Fr shows an increasing and then decreasing trend with the increase of the flow rate of the sprinkler system, and the critical Fr at the turning point of the dominant effect of thermal buoyancy and drag is linearly related to the rate of fire-heat release. However, the influence of fire-heat release rate on Fr can gradually exceed the superposition effect of V-tunnel.

  1. 1)

    Decreases with the increasing flow rate of water spray system, and the critical Fr for turning point of the dominant effect of thermal buoyancy and drag force is linearly related to fire heat release rate. The effect of fire heat release rate on Fr can gradually overtake the stack effect of V-shaped tunnels.

  2. 2)

    Water spray system flow rate is certain, the atomization angle increases, the smoke layer thickness decreases, the Fr number becomes smaller, but the fluctuations are small. The water spray flow with a large atomization angle reduces the smoke temperature and attenuates the radiant heat feedback, which can indirectly inhibit the combustion reaction. Therefore, when the water flow rate is certain, increasing the atomization angle is conducive to reducing the concentration of smoke in the downwind direction of the fire source, and the phenomenon of smoke layer settling and turbulence is relatively light.

  3. 3)

    Smoke spread in a V-shaped tunnel can be divided into three stages on the basis of the change of dominant driving force, as the distance between the tunnel grade change point and fire source location increases. Due to coupling effects of double-slope stack effects, thermal buoyance and drag force induced by water spray system, Fr changes a little on first double-slope control stage, increases on the left and decreases on the right of fire source, and eventually both levels off on second transition phase stage, thus tends to be stable on third single slope control stage.