1 Introduction

Electric trains connected to the traction network will introduce lots of power electronics, which may cause low-frequency oscillation (LFO) in the train–network system due to the interaction between the network and the power electronics of the trains [1, 2]. Therefore, the modeling of the traction power supply system is very important for the LFO stability analysis. Traction power supply system widely adopts the unilateral power supply mode, which exists a sectioning post between two adjacent traction substations. Trains will lose power over the sectioning post, which is one of the weakest links of the traction power supply system, therefore making it not suitable for the electrified railways with long ramps [3,4,5]. Taking electrified railways at high altitude as an example, the short circuit capacity of the power grid along the line is small, and each feeding section is long. When multiple trains are pulling uphill and braking downhill, it is easy to cause the catenary voltage drop and the voltage overrun, respectively, which cannot make a safe and stable operation of the running trains [6,7,8]. Studies have shown that the bilateral power supply mode with the cancelation of the sectioning post has the ability to realize long-distance power supply, and can improve the power supply capacity, especially for the electrified railways which are often connected to the weak power grid in the high-altitude areas [9,10,11,12,13,14]. However, the adoption of bilateral power supply mode which increases the length of the feeding sections will increase the number of connecting trains, and then increase the risk of system oscillation. The existing unilateral power supply technology of traction power supply system is not suitable for the construction of high-altitude mountain railway. Therefore, it is necessary to study the stability of trains connected to the bilateral power supply system and compare it with the trains connected to the unilateral power supply system.

In the existing studies, the train–network system adopting the unilateral power supply mode has been modeled as a single-phase voltage source, an equivalent impedance and the trains in Refs. [15,16,17,18,19]. Lv et al. [20], considering the complete structure of the traction network, established the state space model of the train–network system and analyzed the stability by eigenvalue analysis method. In Ref. [21], based on the impedance-based method, which regarded the train–network system as a cascade system of the traction power supply system (source side) and the input impedance of the train (load side) [22], the dq impedance model of China CRH5 train considering the synchronous system, the current inner loop and the voltage outer loop has been established. Moreover, considering the second-order generalized integrator (SOGI) and phase-locked loop (PLL), a more accurate dq impedance model has been established, and the influence of different control links of CRH5 train on LFO has been analyzed in Ref. [23]. Chang et al. [24] built the single-input and single-output (SISO) impedance model of CRH5 train, which can express the relationship between the actual input voltage and current of the trains and has clear physical meaning. Then the SISO impedance has been used to establish the RLC circuit to analyze the influence of control parameters on impedance characteristics of the train. The existing studies based on the unilateral power supply mode have studied the mechanism of LFO and the influence of different parameters on oscillation, and many valuable conclusions have been obtained. However, the above models only have one source and are not suitable for the bilateral power supply system, in which the trains can take power from two adjacent traction substations at the same time. Moreover, most of LFO studies focuse on the situation that the trains raise pantograph at the same place, and only the on-board auxiliary equipment works, while stability under the situation of the trains running at different places also needs to be discussed. Especially for the bilateral power supply system, the increase in the number of running trains will increase the probability of LFO.

However, when trains are running, there is an impedance of the traction network between the two trains, so the topology of the network becomes complex. It should be noted that, the common impedance-based method is not suitable for the system with complex topology, due to the system cannot be easily equivalent to the source and load subsystems. To deal with it, the modal analysis method proposed in Ref. [25] has been used in power system stability analysis. The modal analysis method can analyze the stability of the system by establishing the system node admittance matrix, which can consider the actual network topology of the system and is suitable for the study of this paper. Qin and Xu [26] studied the multi-virtual synchronous machine grid-connected power–frequency oscillation by modal analysis. Moreover, modal analysis has also been applied to traction power supply system. In Ref. [27], based on modal analysis, the LFO of the traction power supply system connected to the three-phase power grid was analyzed, and the interaction between the two feeding sections and their interaction with the power grid was studied.

In order to analyze the LFO and its propagation characteristics of the train–network system under the actual network topology, the modal analysis method is applied in this paper to study the train–network system including the three-phase power grid, traction transformer, traction network and the trains, and different power supply modes are considered.

The contributions of this paper are as follows:

  1. (1)

    Based on the train–network topologies of bilateral power supply and unilateral power supply modes, the system node admittance matrices in frequency-domain including three-phase power grid, single-phase traction transformer, traction network and multiple trains are established.

  2. (2)

    The modal analysis method is adopted to study the LFO when multiple trains are running at different places, and the oscillation modes and propagation characteristics of the LFO under the bilateral and unilateral power supply modes are analyzed and compared.

  3. (3)

    For the bilateral power supply system, the influences of the equivalent inductance of the power grid, the length of the transmission line and the length of the traction network on the LFO mode are studied.

The rest of this paper is arranged as follows. In Sect. 2, based on the SISO impedance model of CRH5 train, the equivalent circuits and the node admittance matrices of the bilateral and unilateral power supply systems are established. In Sect. 3, the oscillation modes and propagation characteristics of bilateral and unilateral power supply systems are analyzed and compared by modal analysis. The influences of different parameters on the oscillation mode are studied. In Sect. 4, the simulation results in MATLAB/Simulink are analyzed to prove the feasibility and correctness of the modal analysis. Finally, the conclusion is summarized in Sect. 5.

2 Model of train–network system considering the network topology

2.1 Main circuit structure and control strategy of the train

The train studied in this work is the CRH5 train, which has five power units with the same structures. The main circuit structure of two gird-side converters of each unit is shown in Fig. 1, where es and is are the primary voltage and current of on-board transformer, respectively; e and i are the secondary voltage and current of on-board transformer, respectively; Rn and Ln are the equivalent impedances of on-board transformer; Cd and Rd are the DC-side capacitor and load, respectively; and Udc and idc are the DC-side voltage and current respectively.

Fig. 1
figure 1

The main circuit and control strategy of the grid-side converters

CRH5 train adopts dq decoupling control, which including second-order generalized integrator (SOGI), phase-locked loop (PLL), AC current controller (ACC), DC voltage controller (DVC) and pulse width modulation (PWM). θ is the phase of the converter input voltage; the subscript dq denotes the component in synchronous rotating frame; the subscript αβ denotes the component in stationary frame; the superscript s represents the system component; the superscript s' represents the component obtained through the SOGI; the superscript c represents the control component in the control system; idref is the reference current of the ACC.

2.2 SISO impedance model of the train

SOGI converts input voltage and current components into αβ components, as shown in Eq. (1):

$$\left\{ {\begin{array}{*{20}l} {\Delta u_{\alpha }^{\text s} = \Delta e} \\ {\Delta u_{\beta }^{\text s} = \frac{{\omega_{0} }}{s}\Delta e} \\ \end{array} } \right.,\,\,\,\,\left\{ {\begin{array}{*{20}l} {\Delta i_{\alpha }^{\text s} = \Delta i} \\ {\Delta i_{\beta }^{\text s} = \frac{{\omega_{0} }}{s}\Delta i} \\ \end{array} } \right..$$
(1)

where Δe, Δi, Δu sα , Δu sβ , Δi sα and Δi sβ are the small perturbations; and ω0 is the fundamental frequency.

According to the Park transformation, the dq components of the small signal components of the input voltage and current small signal components can be obtained as

$$\begin{aligned} & \left\{ {\begin{array}{*{20}l} {\Delta u_{d}^{\text s} = \cos \omega_{0} t \cdot \Delta u_{\alpha }^{\text s} + \sin \omega_{0} t \cdot \Delta u_{\beta }^{\text s} } \hfill \\ {\Delta u_{q}^{\text s} = - \sin \omega_{0} t \cdot \Delta u_{\alpha }^{\text s} + \cos \omega_{0} t \cdot \Delta u_{\beta }^{\text s} } \hfill \\ \end{array} } \right. ,\\ & \left\{ {\begin{array}{*{20}l} {\Delta i_{d}^{\text s} = \cos \omega_{0} t \cdot \Delta i_{\alpha }^{\text s} + \sin \omega_{0} t \cdot \Delta i_{\beta }^{\text s} } \hfill \\ {\Delta i_{q}^{\text s} = - \sin \omega_{0} t \cdot \Delta i_{\alpha }^{\text s} + \cos \omega_{0} t \cdot \Delta i_{\beta }^{\text s} } \hfill \\ \end{array} } \right. .\\ \end{aligned}$$
(2)

Reference [23] established the dq impedance model of the grid-side converter Zdq(s), which can be written in second-order matrix form:

$$\left[ {\begin{array}{*{20}c} {\Delta u_{d}^{\text s} } \\ {\Delta u_{q}^{\text s} } \\ \end{array} } \right] = \left[ {\begin{array}{*{20}c} {Z_{dd} \left( s \right)} & {Z_{dq} \left( s \right)} \\ {{Z}_{qd} \left( s \right)} & {Z_{qq} \left( s \right)} \\ \end{array} } \right]\left[ {\begin{array}{*{20}c} {\Delta i_{d}^{\text s} } \\ {\Delta i_{q}^{\text s} } \\ \end{array} } \right] \triangleq {\varvec Z}_{dq} \left( s \right)\left[ {\begin{array}{*{20}c} {\Delta i_{d}^{\text s} } \\ {\Delta i_{q}^{\text s} } \\ \end{array} } \right],$$
(3)

where Zdq(s) is an asymmetric matrix and has no practical physical meaning. In order to convert the impedance in the dq-frame to phase-domain, the second-order impedance matrix Zdq(s) needs to be firstly transformed into two transfer functions Gdq+(s) and Gdq-(s) [28], which can be expressed as

$$\begin{aligned} \Delta u_{d}^{\text s} + {\text j}\Delta u_{q}^{\text s} = & \,\underbrace {{\left( {\frac{{Z_{dd} (s) + Z_{qq} (s)}}{2} + {\text j}\frac{{Z_{qd} (s) - Z_{dq} (s)}}{2}} \right)}}_{{G_{dq + } (s)}}\left( {\Delta i_{d}^{\text s} + \text{j}\Delta i_{q}^{\text s} } \right) \\ & \, + \underbrace {{\left( {\frac{{Z_{dd} (s) - Z_{qq} (s)}}{2} + {\text j}\frac{{Z_{dq} (s) + Z_{qd} (s)}}{2}} \right)}}_{{G_{dq - } (s)}}\left( {\Delta i_{d}^{\text s} - \text{j}\Delta i_{q}^{\text s} } \right), \\ \end{aligned}$$
(4)

Due to \(\Delta u_{\beta }^{{}} = - {\text j}\Delta u_{\alpha }^{{}} \;,\;\Delta i_{\beta }^{{}} = - {\text j}\Delta i_{\alpha }^{{}}\), the relationship between the input voltage and current components in αβ-frame is

$$\begin{aligned} \Delta u_{\alpha }^{\text s} + {\text j}\Delta u_{\beta }^{\text s} = & \,\underbrace {{\text e^{{\text j\omega_{0} t}} G_{dq + } \left( s \right)\text e^{{ - \text j\omega_{0} t}} }}_{{G_{\alpha \beta + } \left( s \right)}}\left( {\Delta i_{\alpha }^{\text s} + \text j\Delta i_{\beta }^{\text s} } \right) \\ & \,+\underbrace {{\text e^{{\text j\omega_{0} t}} G_{dq - } \left( s \right)\text e^{{ - \text j\omega_{0} t}} }}_{{G_{\alpha \beta - } \left( s \right)}} \left( {\Delta i_{\alpha }^{\text s} - \text j\Delta i_{\beta }^{\text s} } \right).\\ \end{aligned}$$
(5)

According to Eq. (1), \(\Delta u_{\alpha }^{\text s}\), \(\Delta u_{\beta }^{\text s}\), \(\Delta i_{\alpha }^{\text s}\) and \(\Delta i_{\beta }^{\text s}\) can be represented by \(\Delta e\) and \(\Delta i\). Thus, the relation between \(\Delta e\) and \(\Delta i\) can be obtained [24]:

$$\Delta e = \frac{{(s + \text j\omega_{0} ) \cdot \left[ {Z_{aa} (s) + \text jZ_{ab} (s)} \right] + (s - \text j\omega_{0} ) \cdot \left[ {Z_{ba} (s) + \text jZ_{bb} (s)} \right]}}{{s + \text j\omega_{0} }}\Delta i \triangleq Z_{{{\text{unit}}}} \Delta i,$$
(6)

where Zunit is the SISO impedance model of the grid-side converter, Zaa (s), Zbb(s), Zba(s) and Zbb(s), respectively, are

$$\left\{ {\begin{array}{*{20}c} {Z_{aa} (s) = \frac{{Z_{dd} (s - {\text j}\omega_{0} ) + Z_{qq} (s - {\text j}\omega_{0} )}}{2}\;,{\kern 1pt} \quad Z_{ab} (s) = \frac{{Z_{qd} (s - {\text j}\omega_{0} ) - Z_{dq} (s - {\text j}\omega_{0} )}}{2}} \\ {Z_{ba} (s) = \frac{{Z_{dd} (s - {\text j}\omega_{0} ) - Z_{qq} (s - {\text j}\omega_{0} )}}{2}\;,{\kern 1pt} \quad Z_{bb} (s) = \frac{{Z_{qd} (s - {\text j}\omega_{0} ) + Z_{dq} (s - {\text j}\omega_{0} )}}{2}} \\ \end{array} } \right..$$
(7)

Therefore, the impedance of the CRH5 train can be expressed as

$$Z_{{{\text{CRH5}}}} = \frac{{k_{{{\text{CRH5}}}}^{2} }}{10t}Z_{{{\text{unit}}}} ,$$
(8)

where kCRH5 = 25,000/1770 is the transformation ratio of the on-board transformer, and t is the number of the trains at the same position.

2.3 Models of unilateral and bilateral power supply system

There is a sectioning post between two adjacent traction substations in unilateral power supply system, so that the train can only take current from one traction substation. However, due to the cancelation of the sectioning post, the train can simultaneously take current from two adjacent traction substations in the bilateral power supply system, as shown in Fig. 2. Because the research object of this paper is only a feeding section of a traction substation, rather than two feeding sections of a traction substation. Therefore, a relatively simple single-phase transformer can be selected to supply power to this feeding section when establishing the model.

Fig. 2
figure 2

Schematic diagrams of a the unilateral power supply system and b the bilateral power supply system

Figure 3 is the equivalent circuit of trains connected to the bilateral power supply system, which retains the actual network topology and considers the traction network impedance between two trains running at different places. Select nodes 1–8 as the nodes of three-phase grid side and U1U8 denote the voltage of each node. Select nodes A–F as the nodes of traction network side and UAUF denote the voltage of each node. UsA, UsB and UsC are the voltages of the three-phase 220 kV power system; Ls is the power grid equivalent inductance; ZL is the impedance of the 220 kV transmission line between two adjacent traction substations; ZJ is the power line equivalent impedance of the traction substations; T1 and T2 are single-phase traction transformers which represent traction substation 1 and traction substation 2, respectively; ZT is the equivalent impedance of the single-phase traction transformer; Zq1Zq5 are the impedances of different segments of the traction network, and ZlAZlF are the impedances of the trains connected at nodes A–F, respectively.

Fig. 3
figure 3

Equivalent circuit of the bilateral power supply system

In order to obtain the node admittance matrix of the bilateral power supply system, the nodes of the system are firstly divided into three types. Type I is nodes 1–4 of the high-voltage side of 220 kV transmission line, type II is nodes 5–8 of the high-voltage side of the single-phase traction transformers, and type III is nodes A–F of the low-voltage side of the traction network. The relationship between nodal voltages and currents is shown in Eq. (9):

$$\left[ {\begin{array}{*{20}c} {I_{{\text{I}}} } \\ {I_{{{\text{II}}}} } \\ {I_{{{\text{III}}}} } \\ \end{array} } \right] = \left[ {\begin{array}{*{20}c} {Y_{{{\text{I}},{\text{I}}}} } & {Y_{{\text{I,II}}} } & {Y_{{{\text{I}},{\text{III}}}} } \\ {Y_{{{\text{II}},{\text{I}}}} } & {Y_{{{\text{II}},{\text{II}}}} } & {Y_{{{\text{II}},{\text{III}}}} } \\ {Y_{{\text{III,I}}} } & {Y_{{{\text{III}},{\text{II}}}} } & {Y_{{{\text{III}},{\text{III}}}} } \\ \end{array} } \right]\left[ {\begin{array}{*{20}c} {U_{{\text{I}}} } \\ {U_{{{\text{II}}}} } \\ {U_{{{\text{III}}}} } \\ \end{array} } \right] \triangleq \varvec Y\left[ {\begin{array}{*{20}c} {U_{{\text{I}}} } \\ {U_{{{\text{II}}}} } \\ {U_{{{\text{III}}}} } \\ \end{array} } \right],$$
(9)

where \(I_{{\text{I}}}\), \(I_{{{\text{II}}}}\) and \(I_{{{\text{III}}}}\) are the nodal currents injection; \(U_{{\text{I}}}\), \(U_{{{\text{II}}}}\) and \(U_{{{\text{III}}}}\) are the nodal voltages; \(Y_{{{\text{I}},{\text{I}}\,}}\), \(Y_{{{\text{II}},{\text{II}}}}\) and \(Y_{{{\text{III}},{\text{III}}}}\) are the self-admittance matrices of these three types of nodes; \(Y_{{{\text{I}},{\text{II}}}} = Y_{{{\text{II}},{\text{I}}}}\), \(Y_{{{\text{I}},{\text{III}}}} = Y_{{{\text{III}},{\text{I}}}}\) and \(Y_{{{\text{II}},{\text{III}}}} = Y_{{{\text{III}},{\text{II}}}}\) are the mutual admittance matrices of these three types of nodes; and Y is the system node admittance matrix.

In the unilateral power supply system, there is a sectioning post between two adjacent traction substations. For easy to compare, the names of nodes in the unilateral power supply system are consistent with those in the bilateral power supply system, as shown in Fig. 4. It should be noted that the impedance of the traction network between node C and node D is regarded as infinite to simulate the state of two feeding sections disconnected. Similarly, the node admittance matrix of the unilateral power supply system can be obtained.

Fig. 4
figure 4

Equivalent circuit of the unilateral power supply system

3 LFO study of the bilateral and unilateral power supply systems

3.1 Modal analysis

This paper analyzes the LFO of the bilateral and unilateral power supply systems by modal analysis [25]. Firstly, the SISO impedance model of the train and the equivalent circuit model of the train–network system should be established, and the system node admittance matrix Y can be obtained. In Eq. (9), the matrix Y can be decomposed into the following form [25]:

$$\varvec Y = \varvec L \varvec{\varLambda} \varvec T,$$
(10)

where \(\varvec\varLambda\) is the diagonal eigenvalue matrix, L and T are the left and right eigenvector matrices, respectively, and L = T−1.

Defining V = TU as the modal voltage vector and J = TI as the modal current vector, respectively, and substituting Eqs. (10) into (9) yields

$$\left[ {\begin{array}{*{20}c} {V_{1} } \\ {V_{2} } \\ \vdots \\ {V_{n} } \\ \end{array} } \right] = \left[ {\begin{array}{*{20}c} {\lambda_{1}^{ - 1} } & 0 & 0 & 0 \\ 0 & {\lambda_{2}^{ - 1} } & 0 & 0 \\ 0 & 0 & \vdots & 0 \\ 0 & 0 & 0 & {\lambda_{n}^{ - 1} } \\ \end{array} } \right]\left[ {\begin{array}{*{20}c} {J_{1} } \\ {J_{2} } \\ \vdots \\ {J_{n} } \\ \end{array} } \right],$$
(11)

where the reciprocal of the eigenvalue \(\lambda_{n}^{ - 1}\) is defined as modal impedance, and the subscript number n represents the number of nodes.

According to Eq. (11), it can be seen that when \(\lambda_{1}^{ - 1}\) is much larger than other modal impedance, even a small current J1 can produce a large voltage V1. Therefore, the mode 1 is the critical oscillation mode. The left eigenvector Lni and the right eigenvector Tin represent the observability and controllability of node n to mode i oscillation, respectively. The participation factor of node n to mode i oscillation is defined as PFni = LniTin.

3.2 Comparison of oscillation modes between the bilateral and unilateral power supply systems

3.2.1 The bilateral power supply system with 6 trains connected

In the bilateral power supply system, 6 trains are connected to the traction network at different places, respectively, as shown in Fig. 3, which is called as bilateral power supply A1B1C1D1E1F1. Considering that trains on the same line depart at the same interval in actual railway operation, the impedances of the traction network between two trains are assumed to be the same value, that is Zq1 = Zq2 = … = Zq5 = Zq. The main parameters of the system are shown in Table 1. And the trains are operating at about 50% of the rated power. Based on modal analysis, the corresponding modal impedance frequency curve can be drawn, as shown in Fig. 5. The mode which has the largest modal impedance is the critical mode 1. It can be seen that the oscillation frequency of the critical mode 1 of the bilateral power supply A1B1C1D1E1F1 is 4.30 Hz, and the modal impedance of the critical mode 1 is 193.7 p.u.

Table 1 The main parameters of the system
Fig. 5
figure 5

The modal impedance frequency curve of bilateral power supply A1B1C1D1E1F1

3.2.2 The unilateral power supply system with 6 trains connected

In this case, the parameters of the system and the number of trains remain unchanged, and only a sectioning post is added between the two traction substations, which is the unilateral power supply system. This case is called as unilateral power supply A1B1C1D1E1F1. Similarly, the corresponding modal impedance frequency curve can be obtained, as shown in Fig. 6. It can be seen that the oscillation frequency of the critical mode 2 of the unilateral power supply A1B1C1D1E1F1 is 4.30 Hz, and the modal impedance is 208.6 p.u.

Fig. 6
figure 6

The modal impedance frequency curve of unilateral power supply A1B1C1D1E1F1

3.2.3 The unilateral and bilateral power supply systems with 3 trains connected, respectively

In order to further compare the difference of oscillation modes of the unilateral and bilateral power supply systems and analyze the influence of the number of trains on oscillation mode, 3 trains are connected to nodes A, B and C of the traction network, respectively. The rest of parameters remain the same as the above. These two cases are called as unilateral power supply A1B1C1 and bilateral power supply A1B1C1, respectively.

Figure 7 gives the comparison of the critical modal impedance frequency curves of unilateral power supply A1B1C1 and bilateral power supply A1B1C1. It can be seen that the oscillation frequency of the critical mode 2 of unilateral power supply A1B1C1 is 4.70 Hz, and the modal impedance is 10.83 p.u. The oscillation frequency of the critical mode 1 of bilateral power supply A1B1C1 is 5.40 Hz, and the modal impedance is 8.717 p.u.

Fig. 7
figure 7

The critical modal impedance frequency curve of unilateral power supply A1B1C1 and bilateral power supply A1B1C1

The modal impedances and oscillation frequencies of the critical oscillation modes under different power supply modes and different numbers of running trains are summarized in Table 2. It can be concluded that when the power supply mode changes from bilateral to unilateral power supply, the modal impedance of the critical mode will increase, which means the oscillation amplitude in the bilateral power supply system is smaller than that in the unilateral power supply system. When the number of running trains increases both in these two supply systems, the modal impedances of the critical modes will increase and the oscillation frequencies will decrease, which indicates that the increase in the number of running trains will increase the system oscillation amplitude and decrease the oscillation frequency.

Table 2 The critical oscillation modes of the train–network system under different power supply modes and different numbers of running trains

3.3 The propagation characteristics of the LFO in unilateral and bilateral power supply systems

In order to analyze the propagation characteristics of oscillation both in traction network and power grid, based on unilateral power supply A1B1C1D1E1F1 and bilateral power supply A1B1C1D1E1F1, the participation factors, observability and controllability of each node for the critical oscillation mode are studied by modal analysis, and the results are summarized in Tables 3 and 4, respectively. It can be concluded that the participation factors, observability and controllability of the midpoint of the traction network in the bilateral power supply system (node D) and the position near the sectioning post in the unilateral power supply system (node D) are the largest. Therefore, the midpoint of the traction network of the bilateral power supply system and the position near the sectioning post of the unilateral power supply system can be regarded as the oscillation center. Whether it is bilateral or unilateral power supply, the participation factors, observability and controllability of the nodes on the low-voltage side are greater than the nodes on the high-voltage side of the traction transformer, and on the low-voltage side, the farther the nodes from the traction substation, the greater the participation factors, observability and controllability are. That is, the oscillation of nodes close to the oscillation center is more obvious, and the oscillation can propagate from the low-voltage side to the high-voltage side.

Table 3 The participation factor, observability, controllability and harmonic content corresponding to the critical mode in the bilateral power supply system
Table 4 The participation factor, observability, controllability and harmonic content corresponding to the critical mode in the unilateral power supply system

3.4 Influence of parameters on the critical mode of bilateral power supply system

3.4.1 Equivalent inductance of the power grid

In this case study, the influence of the power grid equivalent inductance (Ls) on the LFO is analyzed. Figure 8 shows the modal analysis results of the bilateral power supply system when Ls changes. It is shown in Fig. 8 that the modal impedance of the critical oscillation mode obviously increases and the oscillation frequency slightly decreases as Ls increases. The analysis result shows that with the increase of Ls, the oscillation amplitude will increase and the system will be more prone to oscillate.

Fig. 8
figure 8

Modal analysis results of the bilateral power supply system when Ls changes

3.4.2 Length of 220 kV transmission line

In this case study, the influence of the transmission line length on the LFO is analyzed. Figure 9 shows the modal analysis results of the bilateral power supply system when the length of the transmission line changes. It is shown in Fig. 9 that the modal impedance of the critical oscillation mode slightly increases and the oscillation frequency remains unchanged as the length of the transmission line increases. The analysis result shows that with the increase in the length of the transmission line, the system is prone to oscillate; however, the influence is relatively smaller compared with the influence of the length of the traction network which will be discussed in next part.

Fig. 9
figure 9

Modal analysis results of the bilateral power supply system when the length of the transmission line changes

3.4.3 Length of the traction network

In this case study, the influence of the lengths of the traction network on the LFO is analyzed. Figure 10 shows the modal analysis results of the bilateral power supply system when the length of the traction network changes. It is shown in Fig. 10 that the modal impedance of the critical oscillation mode obviously increases and the oscillation frequency slightly decreases as the length of the traction network increases. The analysis result shows that with the increase in the length of the traction network, the oscillation amplitude will increase and the system will be more prone to oscillate.

Fig. 10
figure 10

Modal analysis results of the bilateral power supply system when the length of the traction network changes

4 Simulation and verification

In order to verify the correctness of the above theoretical analysis, the time-domain simulation model of the train–network system was built in MATLAB/Simulink. By observing the waveforms of the DC-side voltage and network voltage of the converter, it is intuitive to judge whether the LFO occurs. This paper will verify the correctness of the modal analysis from two aspects. On the one hand, the simulation results are analyzed by ESPRIT method [29], which can obtain the oscillation frequency and the damping ratio of the system to verify the critical oscillation mode. On the other hand, the harmonic content of each node corresponding to the critical mode is obtained by FFT to verify the propagation characteristics of LFO.

4.1 Influence of power supply mode

Figure 11 gives the simulation results of 3 trains are connected to node A, B and C, respectively, under the bilateral power supply mode and the unilateral power supply mode. It should be noted that, because the simulation results of the trains at different nodes are similar, this paper only shows the simulation results of the train at node A. Table 5 shows the ESPRIT analysis results under different power supply modes.

Fig. 11
figure 11

The simulation results of the train at node A when the power supply mode changes: a bilateral power supply A1B1C1; b unilateral power supply A1B1C1

Table 5 ESPRIT analysis results under different power supply modes

It is shown in Fig. 11 and Table 5 that, under the bilateral power supply mode, the waveform takes about 1 s to reach a stable state, while it takes about 1.5 s under the unilateral power supply mode. Moreover, the oscillation amplitude of the waveform under unilateral power supply mode is larger than that under bilateral power supply mode. This shows that when the number of running trains is the same, the bilateral power supply system is more stable than the unilateral power supply system. The simulation results are consistent with the theoretical analysis results in Table 2, which verifies the correctness of the theoretical analysis.

4.2 Influence of the number of running trains

Figure 12 shows the simulation results with 3 and 6 trains running, and Table 6 shows the ESPRIT analysis results under different numbers of running trains. It is shown in Fig. 12 and Table 6 that, when three running trains are connected to the system, the system is stable. While six running trains are connected to the system, the system has an oscillation with 4.12 Hz. The simulation results show that with the increase in the number of running trains, the oscillation frequency and damping ratio of the system will gradually decrease, and the stability of the system will be weakened. This is consistent with the theoretical analysis results in Table 2, which proves the correctness of the theoretical analysis.

Fig. 12
figure 12

The simulation results of the train at node A when the number of running trains changes: a bilateral power supply A1B1C1; b bilateral power supply A1B1C1D1E1F1

Table 6 ESPRIT analysis results under different numbers of running trains

4.3 Simulation of propagation characteristics of LFO

In this subsection, FFT analysis is applied to obtain the harmonic content of each node at oscillation frequency when 6 trains connected to unilateral and bilateral power supply systems, respectively. The results are summarized in Tables 3 and 4. It can be seen that the harmonic content and observability of each node have the same change rules. The simulation results verify the conclusions of theoretical analysis, which proves the correctness of the model and analysis method.

4.4 Influence of the equivalent inductance of the power grid

The simulation results and the ESPRIT analysis results are shown in Fig. 13 and Table 7, respectively. It can be seen that the system will be stable due to its positive damping ratio when Ls is 0.16 H, while the system will have LFO due to its negative damping ratio when Ls is 0.24 H. Therefore, it can be considered that with the increase of Ls, the oscillation frequency and the damping ratio both decrease, which verifies the correctness of the theoretical findings.

Fig. 13
figure 13

The simulation results of the train at node A when Ls changes: a Ls = 0.16 H; b Ls = 0.20 H; c Ls = 0.24 H

Table 7 ESPRIT analysis results under different Ls

4.5 Influence of the length of 220 kV transmission line

The simulation results and the ESPRIT analysis results are shown in Fig. 14 and Table 8, respectively. From Fig. 14 and Table 8, it can be seen that with the increase in the length of the transmission line, the oscillation frequency and the damping ratio both decrease slightly. Therefore, the waveforms obtained under different lengths of the transmission line are concatenated into one figure for easy comparison, which can also verify the correctness of the theoretical findings.

Fig. 14
figure 14

The simulation results of the train at node A when the length of the transmission line changes

Table 8 ESPRIT analysis results under different lengths of the transmission line

4.6 Influence of the length of the traction network

The simulation results and the ESPRIT analysis results are shown in Fig. 15 and Table 9, respectively. From Fig. 15 and Table 9, it can be seen that with the increase in the length of the traction network, the oscillation frequency and the damping ratio both decrease. Therefore, the waveforms obtained under different lengths of the traction network are concatenated into one figure for easy comparison, which can also verify the correctness of the theoretical findings.

Fig. 15
figure 15

The simulation results of the train at node A when the length of the traction network changes

Table 9 ESPRIT analysis results under different lengths of the traction network

5 Conclusions

In this paper, considering the actual topology of the traction power supply system with the power grid, traction transformer, and the traction network, the node admittance matrices of the system with two different power supply modes are established. Then, the oscillation modes and propagation characteristics of bilateral and unilateral power supply system, and the influence of different factors on LFO in the bilateral power supply system are analyzed by modal analysis. The main conclusions can be drawn as follows:

  1. (1)

    When the number of running trains is the same, the bilateral power supply system is more stable than the unilateral power supply system. The increase in the number of running trains will lead to the increase in the system oscillation amplitude, even cause system instability.

  2. (2)

    No matter whether the bilateral or unilateral power supply mode is adopted, the oscillation intensity of the nodes on the traction transformer low-voltage side is stronger than that on the high-voltage side, and on the low-voltage side, the further away from the traction substation, the more obvious the oscillation of the nodes.

  3. (3)

    For the bilateral power supply mode, the midpoint of the traction network is the oscillation center. For the unilateral power supply mode, the position near the sectioning post is the oscillation center. Therefore, installing the sensor at the midpoint of the traction network of the bilateral power supply system and the position near the sectioning post of the unilateral power supply system, respectively, will achieve great monitoring effect.

  4. (4)

    The equivalent inductance of the power grid and the length of the traction network have obvious influence on the LFO of the bilateral traction power supply system, while the length of the transmission line between two traction substations has little influence on the system LFO.

This paper only considers the LFO of multiple trains running with the same traction power. The LFO of the same type of trains under different operating conditions or different types of trains running at the same time under bilateral power supply mode can be further analyzed.