Introduction

With decades of mineral mining operations, surface mineral resources in major mining areas are starting to become scarce, prompting a shift toward deeper sources. However, mining at greater depths introduces challenges such as longer, deeper, and more intricate mine tunnels [1, 2]. The increased heat generation in the surrounding rock makes ventilation and heat dissipation more challenging, leading to a prominent heat damage issue in mines. This, in turn, results in a higher incidence of occupational diseases and safety accidents [3,4,5].

In addressing the heat damage problem, some researchers have suggested employing small cooling fans to reduce temperatures in key underground areas. This approach involves creating designated cooling zones to establish microenvironments with comfortable temperatures. Notably, this method boasts a straightforward structure, easy installation and implementation, and proves to be cost-effective and energy-efficient [6, 7]. The cooling heat exchanger, typically installed at the end of the fan, commonly employs a finned-tube circulation tube as its core cooling structure. This configuration offers advantages such as a compact size and high cooling efficiency [8,9,10,11,12]. However, the fin-and-tube heat exchanger (FTHXs) often encounters challenges related to the complexity of its cooling medium flow path and uneven fluid flow. These issues serve as constraints that hinder the potential enhancement of its heat transfer performance. Consequently, there is a current emphasis on addressing and optimizing the flow path structure of heat exchangers [13,14,15,16].

The optimization of the flow path in finned-tube heat exchangers has been a subject of extensive research. Zhang [17] developed the Generalized Simulation Platform for Refrigeration and Air Conditioning Systems (GREATLAB) in 2010. This simulation platform offers robust technical support for simulating, optimizing, and controlling heat pump and air conditioning units. Given the similarities between mine fan heat exchangers and air conditioning systems, this study draws inspiration from the principles of GREATLAB and its related literature.

Mario Petrovic et al. [18] introduced topological concepts for optimizing the local structure of fins in a parallel plate heat exchanger using a genetic algorithm. Unlike the symmetrical and homogeneous configuration of conventional fin structures, the final optimized structure exhibits a slightly different shape for each row of fins within the airflow path. Validation experiments using 3D printed models demonstrated that the optimized structure outperformed the conventional counterpart.

In a study by Ishaque et al. [19], a dual-mode optimization algorithm was employed to enhance the performance of the heat exchanger's cooling water flow path, resulting in a performance improvement of up to 9.64%. The authors considered the inhomogeneity of air velocity in the heat exchanger and introduced knowledge-based (KBCM) and arrangement (PBCM) calculation modules to determine the optimal number of tubes and their arrangement while minimizing computational costs. The study utilized a program to align the flow paths, combining accurate heat transfer calculations for all paths with high precision but requiring substantial computational effort.

Domanski et al. [20] explored the application of an intelligent optimization module (ISHED) in optimizing refrigerant circuits. Their findings indicated that an intelligent automatic optimization system can yield comparable or even superior results compared to manual optimization [21].

Genetic algorithms provide a means to establish optimization objectives within a program, granting the algorithm a degree of autonomy, automating certain aspects of the optimization process, thereby saving time in the flow path optimization [22]. Jiang [23] employed genetic algorithms by transforming the heat exchanger tubes and their connections into a matrix and its units, optimizing their flow paths through this approach.

Wu et al. [24] utilized genetic algorithms to optimize refrigerant flow paths in heat exchangers, aiming for maximum heat transfer with the minimum pipe length as the objective. The optimized structure achieved a remarkable up to 40% reduction in the length of the heat exchanger header pipe and up to a 7.8% improvement in heat transfer performance. However, the iterated heat exchanger structure generated by the algorithm, while theoretically offering higher heat transfer performance, encountered challenges such as cross and far-span connections, thereby increasing manufacturing difficulty and costs. Human-imposed constraints and rules are often required to mitigate these issues.

In recent years, the rapid development of machine learning and artificial intelligence has opened up new possibilities. Large language models of artificial intelligence have demonstrated their potential, and these computational approaches can also be applied to the optimization design of heat exchangers [25, 26]. Mohammad Ghalandari et al. [27] mentioned that the application of various artificial intelligence techniques can be used to model and predict the performance of different heat exchangers. For example, these techniques can predict heat exchanger performance, processing costs, and fouling conditions during operation. The authors discussed the applications of different types of heat exchangers, such as shell-and-tube heat exchangers, which are suitable for high-pressure environments and offer design flexibility and low maintenance costs. Plate-type heat exchangers have a more compact structure and are suitable for low-pressure operating environments compared to shell-and-tube heat exchangers. Maunu Kuosa et al. [28] conducted a study on the application of plate heat exchangers in the field of district energy-efficient heating. In plate heat exchangers, the two fluids involved in heat exchange are both waters. Low-temperature water and high-temperature water exchange heat through alternating heat exchange plates. The authors proposed a novel mass flow control model that improves the heat transfer performance of the plate heat exchanger while reducing pressure loss.

In conclusion, the majority of studies on flow path optimization for heat exchangers have focused on air conditioning systems, with relatively fewer investigations into the optimization of flow paths for small cooling heat exchangers in mining applications. The finite unit method, which discretizes the continuous structure to facilitate optimal design for specific micro-units, has been commonly employed in this research domain.

In this work, a mining fan heat exchanger unit optimization method based on previous research is proposed. This method involves the segmentation of the heat exchanger into units, the measurement and calculation of the working characteristics of individual units, and the utilization of a software program. By setting optimization objectives and instructing the program, the heat exchanger units are arranged and combined to find the optimal structure for the flow path arrangement. The ultimate aim is to enhance efficiency and address heat damage issues in mines, providing valuable technical support for mining operations. This approach utilizes the concept of finite element analysis to simplify the optimization of the heat exchanger flow path. This method is relatively novel, with few similar studies available in the existing literature.

Theoretical analysis

At the termination point of the mining fan, hot air is conveyed to the heat exchanger, facilitating heat exchange with the cooling water within. Assuming no consideration for the phase change of water vapor in the air, the energy exchanged per unit time can be expressed using Newton's law of cooling [29]:

$$\Delta Q={A}_{\text{f}}\cdot {u}_{\text{in}}{\cdot \rho \cdot {C}_{\text{p}}(T}_{\text{in}}-{T}_{\text{out}})=\dot{m}\cdot C\cdot ({t}_{\text{out}}-{t}_{\text{in}})$$
(1)

where \(\Delta Q\) is the total heat transfer, \({A}_{\text{f}}\) is the airflow inlet area, \({u}_{\text{in}}\) is the average air flow velocity, \(\rho\) is the air density, \({C}_{\text{p}}\) is the air constant pressure specific heat capacity, \(\dot{m}\) is the mass flow of water, \(C\) is the specific heat capacity of water, \({T}_{\text{in}}\), \({t}_{\text{in}}\) is the inlet temperature of air and water, respectively, \({T}_{\text{out}}\), \({t}_{\text{out}}\) is the outlet temperature of air and water, respectively.

This method operates on the principle of calculating the temperature and flow rate differences before and after fluid heat exchange per unit time, enabling the determination of the heat exchange quantity. Given the relatively small change in the flow rates of air and cooling water coupled with significant temperature differences, this mathematical model can be conceptualized as a system. In this system, the initial temperature of the fluid serves as the input at one end, and the temperature of the fluid after heat exchange serves as the output at the other end [5]. Refer to Fig. 1 for a visual representation of this system.

Fig. 1
figure 1

Schematic diagram of micro-unit heat transfer characteristics

In the context of a quadratic equation, obtaining solutions for two unknowns necessitates a minimum of two mathematical relationships. Similarly, in the domain of heat exchangers, the heat exchange volume can be determined through the fin efficiency and the heat transfer coefficient [30]. This relationship can be expressed as follows:

$$\Delta Q={A}_{\text{total}}\cdot {\Delta T}_{\text{ln}}\cdot h$$
(2)

where \({A}_{\text{total}}\) is the effective area of the fins [31], which can be expressed as:

$${A}_{\text{total}}={A}_{\text{tube}}+{A}_{\text{fin}}\cdot \eta$$
(3)

where \(\eta\) is the fin efficiency, which is derived from simulation experiments and is calculated by assuming that the temperature of the fins is the same as the water pipe and does not change, and deriving the heat exchange in that case and comparing it with the heat exchange of the fins for normal heat dissipation. It can be expressed as:

$$\eta =Q/{Q}_{\text{ideal}}$$
(4)

where \(Q\) is the heat exchange per unit time of the normal fin; \({Q}_{\text{ideal}}\) represents the ideal maximum heat transfer rate per unit time, which is obtained through numerical simulation by artificially adjusting the fins to be isothermal with the water pipes. The mathematical expressions for \(Q\) and \({Q}_{\text{ideal}}\) are as follows [29, 32]:

$$Q{=\sum A}_{\text{ij}}({T}_{\text{f}}-{T}_{\text{ij}}){h}_{\text{ij}}$$
(5)
$${Q}_{\text{ideal}}{=\sum A}_{\text{ij}}({T}_{\text{f}}-{T}_{\text{tube}}){h}_{\text{ij}}$$
(6)

Equations 5 and 6 express the calculation methods for the heat exchange rate, \({T}_{\text{f}}\) represents the air temperature. The difference between the two equations is that \({T}_{\text{ij}}\) represents the temperature of the fin, which varies with changes in \(ij\) during the integration process, while \({T}_{\text{tube}}\) is the fin temperature, but its value is equal to the temperature of the water pipe and remains constant. In the experiments conducted in this paper, the value of \({Q}_{\text{ideal}}\) is derived from simulation experiments.

\({\Delta T}_{\text{ln}}\) is the logarithmic temperature difference, and its calculation can be expressed as:

$${\Delta T}_{\text{ln}}=\frac{\left({T}_{\text{in}}-{t}_{\text{out}}\right)-({T}_{\text{out}}-{t}_{\text{in}})}{\text{ln}\frac{{T}_{\text{in}}-{t}_{\text{out}}}{{T}_{\text{out}}-{t}_{\text{in}}}}$$
(7)

The heat transfer coefficient (\(h\)) signifies the effectiveness of overall heat transfer performance and is influenced by the shape and material of the heat exchanger, as well as the flow rate and flow state of the fluid. In a given model, when the aforementioned parameters remain constant, the heat transfer coefficient tends to be relatively fixed. Experimental investigations for different heat exchangers allow the determination of heat transfer coefficients [27].

If the inlet temperatures of air and water are considered as the primary characteristics of heat transfer, the heat transfer coefficient (\(h\)) can be expressed as a function of these characteristics. The values of the heat transfer coefficient for various cases are determined through simulation or experimentation and are often fitted using polynomials to establish a functional relationship. This relationship can be expressed as:

$$h={A}_{1}+{{A}_{2}T}_{\text{in}}+{A}_{3}{t}_{\text{in}}+{A}_{4}{T}_{\text{in}}{t}_{\text{in}}+{A}_{5}{T}_{\text{in}}^{2}+{A}_{6}{t}_{\text{in}}^{2}$$
(8)

In the second method of calculating \(\Delta Q\), all parameters can be obtained either directly or indirectly, with the exception of the inlet and outlet temperatures of air and water. Given that the two calculation methods are founded on different physical principles, they can be amalgamated into a system of binary equations. In this system, the independent variables are the inlet temperatures of air and water (\({T}_{\text{in}}\), \({t}_{\text{in}}\)), while the dependent variables are the outlet temperatures of air and water (\({T}_{\text{out}}\), \({t}_{\text{out}}\)). This relationship can be expressed as:

$$\left\{ {\begin{array}{*{20}l} {A_{{\text{f}}} \cdot u_{{{\text{in}}}} \rho \cdot C_{{\text{p}}} (T_{{{\text{in}}}} - T_{{{\text{out}}}} ) = \dot{m} \cdot C \cdot \left( {t_{{{\text{out}}}} - t_{{{\text{in}}}} } \right)} \hfill \\ {A_{{\text{f}}} \cdot u_{{{\text{in}}}} \cdot \rho \cdot C_{{\text{p}}} (T_{{{\text{in}}}} - T_{{{\text{out}}}} ) = A_{{{\text{total}}}} \cdot \Delta T_{{{\text{ln}}}} \cdot h} \hfill \\ {h = f\left( {T_{{{\text{in}}}} ,t_{{{\text{in}}}} } \right)} \hfill \\ {\Delta T_{{{\text{ln}}}} = \frac{{\left( {T_{{{\text{in}}}} - t_{{{\text{out}}}} } \right) - \left( {T_{{{\text{out}}}} - t_{{{\text{in}}}} } \right)}}{{{\text{ln}}\frac{{T_{{{\text{in}}}} - t_{{{\text{out}}}} }}{{T_{{{\text{out}}}} - t_{{{\text{in}}}} }}}}} \hfill \\ \end{array} } \right.$$
(9)

Physical model and numerical method

Heat exchanger flow path micro-unit optimization method introduction

In the cooling heat exchanger situated at the end of the mine fan, the arrangement of cooling water pipes within the internal space significantly influences the heat exchanger's efficiency. However, the three-dimensional spatial arrangement of cooling water pipes is inherently complex, making the identification of the optimal structure challenging through manual methods. To address this challenge, this paper introduces a micro-unit optimization method for the heat exchanger flow path. The method involves partitioning the fin-and-tube heat exchanger into several independent micro-units [33], interconnected as depicted in Fig. 2.

Fig. 2
figure 2

Schematic diagram of heat exchange micro-unit temperature relationship

In Fig. 2, the cooling water sequentially passes through finned tube micro units B, A, C, and D. Consequently, the water flow outlet temperature from the preceding unit serves as the water flow inlet temperature for the subsequent finned tube unit. Additionally, considering the air flow direction, finned tube unit A is positioned upwind of unit B. The air flow outlet temperature from unit A can thus be used as the air flow inlet temperature for unit B.

Viewing the heat exchanger comprehensively, it can be segmented into distinct unit sections. The relationship between a unit and its neighboring units can be approximated as temperature iterations in both the air flow and water flow directions. This method, particularly effective for intricate heat exchanger flow structures, allows for small-scale experiments to fine-tune mathematical model parameters before applying them to more complex heat exchangers. By simplifying the computational process, this method ensures accuracy while reducing experimental costs and facilitating the application of computer algorithms for adjusting the heat exchanger flow path.

Heat exchanger flow path unitization optimization method mathematical model

Dividing the heat exchanger into several units introduces four key parameters within a given unit: the inlet temperature of air and water (\({T}_{\text{in}}\), \({t}_{\text{in}}\)), and the outlet temperature of air and water (\({T}_{\text{out}}\), \({t}_{\text{out}}\)). If a heat exchanger unit is denoted as A, its key parameters can be represented as \({T}_{\text{A in}}\). To integrate these parameters with the previously discussed theory, the circulating heat exchange process of air and water inside the heat exchanger can be articulated using mathematical language.

Referring to Fig. 2 for the heat exchanger, there are four heat exchange units (A, B, C, D), and they can be expressed in terms of a mathematical model as:

$$\left\{ {\begin{array}{*{20}l} {A_{{\text{f}}} \cdot u_{{{\text{in}}}} \cdot \rho \cdot C_{{\text{p}}} (T_{{{\text{in}}}} - T_{{{\text{out}}}} ) = \dot{Q} \cdot \rho \cdot C \cdot \left( {t_{{{\text{out}}}} - t_{{{\text{in}}}} } \right)} \hfill \\ {A_{{\text{f}}} \cdot u_{{{\text{in}}}} \cdot \rho \cdot C_{{\text{p}}} (T_{{{\text{in}}}} - T_{{{\text{out}}}} ) = A_{{{\text{total}}}} \cdot \Delta T_{{{\text{ln}}}} \cdot h} \hfill \\ {\Delta T_{{{\text{ln}}}} = \frac{{\left( {T_{{{\text{in}}}} - t_{{{\text{out}}}} } \right) - \left( {T_{{{\text{out}}}} - t_{{{\text{in}}}} } \right)}}{{{\text{ln}}\frac{{T_{{{\text{in}}}} - t_{{{\text{out}}}} }}{{T_{{{\text{out}}}} - t_{{{\text{in}}}} }}}}} \hfill \\ {h = f\left( {T_{{{\text{in}}}} ,t_{{{\text{in}}}} } \right)} \hfill \\ {T_{{\text{A out}}} = T_{{\text{B in}}} } \hfill \\ {T_{{\text{C out}}} = T_{{\text{D in}}} } \hfill \\ {t_{{\text{B out}}} = t_{{\text{A in}}} } \hfill \\ {t_{{\text{A out}}} = t_{{\text{C in}}} } \hfill \\ {t_{{\text{C out}}} = t_{{\text{D in}}} } \hfill \\ \end{array} } \right.$$
(10)

Heat transfer coefficient solution

As mentioned earlier, \(h\) represents the overall heat transfer coefficient, reflecting the efficiency of heat transfer performance. Its value is interconnected with the shape and material of the heat exchanger, as well as the flow rate and flow state of the fluid [6]. Within the same model, the heat transfer coefficient remains relatively constant when the above parameters are held steady. Experimental determination is typically required to find the heat transfer coefficients for different heat exchangers.

The simple model employed for the simulation experiments, along with its primary parameters and boundary conditions, is illustrated in Fig. 3.

Fig. 3
figure 3

Micro-unit model used to solve for the heat transfer coefficient

By modeling the micro-elements using SolidWorks, separate models were created for the water pipes, fins, and air domain. Then, COMSOL multiphysics was used for meshing and simulation. The inlet was set as a velocity inlet, and the outlet was set as a pressure outlet, with backflow suppressed. Except for the heat exchange boundaries and inlets/outlets, all other boundary conditions were set to thermal insulation.

A series of orthogonal experiments were devised to determine the heat transfer coefficient \(h\) of the heat exchanger. This involved substituting various air inlet temperatures and water inlet temperatures and creating a contour plot of the heat transfer coefficient. The solution results and schematic diagram are presented in Fig. 4.

Fig. 4
figure 4

Distribution of heat transfer coefficient

Utilizing the heat transfer coefficients obtained from different temperature combinations, a function is fitted employing the least squares method. In this fitting process, the temperatures of air and water serve as dependent variables. The resulting heat transfer coefficient function within the given interval is derived as:

$$h=140.16+(-0.57){T}_{\text{in}}+0.59{t}_{\text{in}}+(-{5.81}^{-4}){T}_{\text{in}}{t}_{\text{in}}+{6.66}^{-6}{T}_{\text{in}}^{2}+(-{5.98}^{-6}){t}_{\text{in}}^{2}$$
(11)

The heat transfer coefficient function symbolizes the heat transfer performance of this specific heat transfer micro-unit under the specified boundary conditions. In the event of alterations to the boundary conditions or the replacement of the heat transfer micro-unit, it becomes necessary to recalculate the heat transfer coefficient function.

Heat exchanger flow path unitization optimization method validation

Simulation Validation

To assess the feasibility and accuracy of the micro-unit optimization method for heat exchangers, simulation software was utilized. Experimental methods and assumptions used, same as in the previous subsection. Verification of this approach took place under the primary boundary conditions depicted in Fig. 5.

Fig. 5
figure 5

Model used to validate numerical simulations

The validation experiments for simulation were performed using a total of four heat transfer micro-units. These were solved using both software numerical simulation and the micro-units method mathematical calculation. The experiments employed identical boundary conditions, and detection points were set along the air and water flow paths. The specific locations of the two solution models and their corresponding detection points are illustrated in Fig. 6.

Fig. 6
figure 6

Micro-unit method solution model and numerical simulation model

Temperature detection points are strategically positioned in both the micro-unit method solution model and the numerical simulation model. The measured temperature data from these points are then graphically represented, as depicted in Fig. 7.

Fig. 7
figure 7

Temperature at the detection point for the micro-unit method solved model and numerical simulation model

The results obtained from the micro-unit method and numerical simulation indicate that the micro-unit method yields an average air outlet temperature of 316.55 K, whereas the numerical simulation results show 316.98 K, resulting in a difference of 0.43 K. For the average water outlet temperature, the micro-unit method provides 287.14 K, while the numerical simulation results in 287.05 K, resulting in a difference of 0.90 K. The temperature changes in the process exhibit a relatively small discrepancy between the two methods, and the temperature difference between the calculation methods is lower than the overall temperature difference at the outlet throughout the entire process. In summary, the temperature prediction and simulation difference for a basic heat exchanger comprised of four micro-units is minimal between the micro-unit method and numerical simulation. This can be attributed to the incorporation of crucial parameters, such as heat transfer coefficient and effective heat transfer area, from the numerical simulation into the micro-unit method. Consequently, the temperature change parameters exhibit similarities between the two methods.

In conclusion, the heat exchanger micro-unit optimization method represents a mathematical calculation approach grounded in numerical simulation. When applied to the flow path arrangement of the heat exchanger, it streamlines the computation for adjusting the heat exchanger flow path and contributes to enhancing the efficiency of this process. Additionally, the heat exchanger micro-unit optimization method can extract the heat transfer characteristics of the physical heat exchanger. Both the micro-unit optimization method based on physical heat transfer characteristics and the micro-unit method based on numerical simulation share the same underlying principle. Combining the micro-unit method, numerical simulation, and actual experiments can further enhance the efficiency of optimizing the heat exchanger flow path arrangement.

Heat transfer micro-units randomly arranged

The randomized arrangement of heat exchanger microcells is achieved through the utilization of software code. This subsection employs an example featuring 12 heat exchanger microcells, illustrated in Fig. 8.

Fig. 8
figure 8

Schematic diagram of heat exchanger division unit

In Fig. 8, the heat exchanger plumbing must identify the first heat exchanger micro-unit to serve as the entry point for the water flow and act as the inlet for the heat exchanger. Among the 12 heat exchanger micro-units depicted in Fig. 9, the 1st micro-unit can be chosen from 12 options. After determining the first heat exchanger micro-unit, the 2nd micro-unit needs to be selected from the remaining 11, resulting in (12 * 11) 132 possible combinations. This process continues, with the 3rd heat exchanger micro-unit having 10 choices, and so forth, until all 12 heat exchanger micro-units are selected, generating a total of (12!) 479,001,600 combinations. Many of these combinations are duplicates or hold no meaningful permutations, such as symmetrical ordering and confusing, unrealistic sequences. To exclude these irrelevant calculations, it is essential to sift through all the combinations.

Fig. 9
figure 9

Schematic diagram of representative flow path structure

Analysis and discussion

In Fig. 9a, the typical current-flow structure is illustrated; Fig. 9b depicts the typical counter-flow structure, while Fig. 9c showcases the optimized counter-flow structure obtained through program solutions. The cooling water path is equipped with 12 detection points, each capturing the water flow temperature at its respective location. Additionally, 4 detection points are strategically placed along the wind flow path, where the average temperature of the wind flow is detected at the outlet of the heat exchange layer composed of heat exchange micro-units at each point. The resulting temperature curves are presented in Fig. 10.

Fig. 10
figure 10

Process temperature for different flow path structures

To assess the process temperature difference among the three structures, the temperature variance between the typical current-flow and counter-flow structures and the optimized counter-flow structure at each detection point is graphically represented in line graphs. Figure 11 illustrates the air and water flow temperature difference graphs, respectively.

Fig. 11
figure 11

Temperature difference between typical current-flow and counter-flow structures and optimized structures

Upon examining Fig. 11a, it becomes evident that during air temperature changes, as the air and water flow in the same direction in the current-flow structure, the air is initially exposed to the colder water flow. This results in a faster temperature reduction in the early stage. However, the temperature difference between air and water diminishes in the later stages, causing a decrease in heat transfer rate. Ultimately, this leads to a higher air outlet temperature compared to the other two flow structures and a less effective overall heat transfer. On the other hand, both the counter-flow structure and the optimized counter-flow structure, with water flowing in the opposite direction to the air, exhibit a larger average heat transfer temperature difference. Consequently, the final heat transfer effect is superior to that of the current-flow structure.

Analyzing Fig. 11b reveals that the water flow in the current-flow structure experiences a rapid temperature increase during the initial heat exchange process, followed by a gradual decrease in speed, mirroring the air temperature change in Fig. 11a). At the outlet of the water stream in the heat exchanger, the end stream temperatures are comparable for all three flow structures.

Comparatively, the optimized structure, in contrast to the typical counter-flow structure, undergoes a similar heat transfer process, resulting in a temperature difference curve that follows a similar trend. However, the optimized structure exhibits a higher average water flow temperature and a lower average air temperature, contributing to a more effective heat transfer. This suggests that a more rational flow path arrangement can yield improved heat transfer efficiency.

Within the flow path optimization algorithm, certain unique flow paths with distinct characteristics are generated. Resembling Fig. 9a, these current-flow structures exclusively select the first layer of heat transfer micro-units as the inlet. After traversing all the micro-units in the first layer, they then select the second layer of heat transfer micro-units as the path. All such structures are collectively referred to as current-flow structures. Consequently, a total of 216 types each of down-flow and counter-flow structures are generated. The air outlet temperatures for all these structures are compiled into a statistical graph, as depicted in Fig. 12.

Fig. 12
figure 12

Comparison of outlet temperature of downstream and counterflow structure

Upon analyzing Fig. 12, it becomes evident that, across all counterflow structures, the air outlet temperature is lower than that of the downflow structure. This suggests a more efficient heat transfer for the counterflow structure. The average air outlet temperature for the counter-flow structure is 313.680 K, which is lower than the 313.907 K of the current-flow structure. This implies that the counter-flow structure should be prioritized in the design of the heat exchanger flow path, as it offers superior heat transfer efficiency.

Upon analyzing Fig. 12, it becomes evident that, across all counterflow structures, the air outlet temperature is lower than that of the downflow structure. This suggests a more efficient heat transfer for the counterflow structure. The average air outlet temperature for the counter-flow structure is 313.680 K, which is lower than the 313.907 K of the current-flow structure. This implies that the counter-flow structure should be prioritized in the design of the heat exchanger flow path, as it offers superior heat transfer efficiency.

Conclusions

This paper studies mine heat exchangers and proposes a novel method for optimizing the flow path structure of heat exchangers. Through this method, the heat exchanger is divided into multiple micro-units, and numerical simulations are used to determine their heat transfer characteristics. Subsequently, a computer program is employed to comprehensively calculate the sequence of micro-units in the cooling water flow path. The research findings are summarized as follows:

  1. 1.

    A comprehensive arrangement of the 12 heat exchanger micro-units, as designed in this paper, resulted in the generation of a total of 479,001,600 flow path structures. Among these, the optimal structure exhibits an average air outlet temperature of 311.65 K. This value is lower than the air outlet temperatures of 311.88 K for a typical current-flow structure and 311.68 K for a typical counter-flow structure, demonstrating a superior heat transfer effect.

  2. 2.

    In the typical current-flow structure, the overall flow direction of the water stream aligns with the air flow direction. Although its air temperature experiences a faster initial drop during the heat transfer process compared to the counter-flow structure, the final outlet temperature is higher, indicating poorer heat transfer performance due to a lower temperature difference throughout the entire process. Notably, the heat transfer performance of all 216 counter-flow structures generated by the algorithm surpasses that of an equal number of current-flow structures. The average air outlet temperature for all counter-flow structures is 311.68 K, which is lower than the average air outlet temperature of 311.90 K for the current-flow structures. Therefore, in designing the heat exchanger flow path, optimizing the overall flow direction of the water to be opposite to the air flow direction as much as possible is recommended for achieving enhanced heat transfer results.

  3. 3.

    In this study, only 12 heat transfer micro-units are employed. In practical engineering heat exchangers, the number of micro-units post-division will be greater, resulting in a more intricate flow path structure. The substantial increase in calculation volume can pose challenges for the exhaustive algorithm. Additionally, this paper does not account for radiation and contact heat transfer between micro-units, contributing to a decrease in the algorithm's reliability.