Abstract
European seismic design codes do not take into account the strength and stiffness of the secondary frame action provided by bracing gusset plates of concentrically braced frames (CBFs). This is an attractive assumption for practicing engineers, as it provides simplifications during the analysis and design phases. However, when efficiency and economy are concerned, especially in low-to-moderate seismic regions, this normally neglected frame resource may be interesting to consider in design. Gusset plates can provide a certain degree of stiffness and strength following the bracing failure, and may even prevent global collapse. In particular, when the shear deformation demand of the braced cell remains limited, as in the case of low-to-moderate seismic actions, it may become reasonable to take this extra stiffness and strength into account. Ongoing research project RFSR-CT-2013-00022 MEAKADO investigated this phenomenon by means of experimental and numerical studies with the perspective of setting new inputs for the design rules of the future generation of Eurocodes. This paper presents the results of full scale tests performed inside this research project, which characterized resistance, stiffness, and ductility resources of CBF systems designed for moderate seismicity. The paper also quantifies the effective contribution of the frame action, provided by gusset plate connections, to the global performance of CBF frames.
Similar content being viewed by others
Avoid common mistakes on your manuscript.
1 Introduction
Concentrically braced frame (CBF) configuration (Fig. 1) is very effective to resist horizontal loads. Indeed, 80–90% of the existing steel structures are laterally braced by CBF at least in one direction (Degée et al. 2015). Under earthquake actions, its high lateral strength and stiffness provide an abundant safety for steel buildings. For these structures, current European design recommendations define the seismic resistant system as a combination of primary (bracings) and secondary (non-structural walls, semi-rigid beam-to-column connections) seismic components. The resistant component is considered as “secondary”, when its total contribution to the lateral stiffness is less than 15% of all primary seismic components. In this case, Eurocodes allow designers to neglect the strength and stiffness of these parts in the seismic resistant system (EN1993-1-1-2005 2005a).
Despite even simple gusset plate connections may contribute to this secondary strength and stiffness capacity, at present they are not taken into account in design, and treated as simple pinned joints (as shown in Fig. 2). This assumption is attractive for design engineers as it provides simplifications during the analysis and design phases. However, when efficiency and economy are concerned, especially in low-to-moderate seismic regions, this normally neglected frame resource may be economically interesting to consider due to the limited shear deformation demand of CBFs.
Current seismic code assumptions originate from the traditional focus of seismic engineering community on maximizing the building performance in the high-seismicity context. Application of the same assumptions to the low-to-moderate seismicity may not be economically feasible. This issue has been recently highlighted by several researchers worldwide (Gioncu and Mazzolani 2010; Stoakes 2012; Nelson et al. 2006; Kanyilmaz et al. 2013, 2015; Murty and Malik 2008; Reaveley and Nordenson 1990; Callister and Pekelnicky 2011; Han and Choi 2008; Kelly and Zona 2006; Pinto 2000). Specific assumptions for frame action tuned for low-to-moderate seismicity, can increase the global performance of CBF structures, and their design can be optimized (Gioncu and Mazzolani 2010). Several researchers studied the secondary frame contribution to CBF building performance designed for high seismicity (Hsiao et al. 2013; Málaga-Chuquitaype et al. 2014; Vargas and Bruneau 2008). For moderate seismicity, recent research exists, but limited to component based experimental activities (Stoakes and Fahnestock 2010). There are few recent studies that investigate the performance of beam-to-column shear and gusset plate connections (Stoakes 2012a; Yoo et al. 2008, 2009; Carter 2009) developed for US design practice. European design practice does not provide any specific procedure to design beam-to-column connections involving bracing gusset plates. Elghazouli et al. (2008) underlines the need to develop European guidelines on the design and detailing of recommended bracing connections for seismic resistance, by means of experimental research.
Uriz and Mahin (2008) investigated the contribution of beam-to-column connections involving gusset plates by means of full scale tests (Fig. 3). The specimen was designed according to high seismicity (ductile) approach (SCBF) of AISC Seismic Design Provisions (2010). Authors pointed out a considerable frame action developed by the beam-to-column gusset plate connections. This frame action contributed to the lateral load resistance of the specimen after braces buckled, carrying 30% of the peak lateral load developed by whole braced specimen, an aspect which was not considered during design. This was a very interesting outcome for braced frames designed for high seismic actions.
Hines et al. (2009) underline the necessity to consider the steel frame design in moderate seismicity regions in a new manner. They propose an independent seismic design philosophy for low-ductility structures in moderate seismicity regions, specifically focusing on the reserve capacity concept, and its ability to improve collapse performance for chevron braced steel frames not specifically detailed for seismic resistance. Keeping the behavior factor small as possible (R = 3, according to American Standards), they try to exploit the energy dissipation characteristics of the gravity system which serves as reserve capacity, although this is not permitted by the current standards.
Aboosaber et al. investigated reserve capacity possessed by braced steel frames in the form of gravity framing and gusset plate connections, focusing on the welded bracings with tubular cross sections (Aboosaber et al. 2012). The semi-rigid joints forming a reserve moment frame prevented sidesway collapse even when the bracings get damaged and fractured which means that primary lateral force resisting system is eliminated (Fig. 4). Authors proposed designing braced frames in low and moderate seismicity regions as moderate-ductility dual systems, which can improve the seismic behaviour of steel structures in these zones while keeping the design as simple as possible. Using this approach, moderate-ductility systems can achieve global ductility through coupling of a stiff braced and a flexible semi-rigid moment-resisting frame, on contrary to the high-ductility systems where the ductility is achieved mainly by means of plastic buckling and tensile yielding of bracings. In this way, even though the brittle CBF system fails, the flexible reserve system would possess sufficient strength, stiffness and ductility to prevent global collapse.
Stoakes and Fahnestock (2010) has studied beam-to-column connection flexural behaviour and seismic collapse performance of concentrically braced frames (Fig. 5). They performed tests at component level, and indicated as future research directions, the need of a validation by means of large-scale testing providing observations regarding the complex interaction between bracings, beams, columns, and connections.
In Japanese design practice, bracing systems are always combined with moment-resisting frames, and the global ductility parameters of braced frames depend also on the frame ductility (Marino et al. 2005). Japanese building code (BCJ 1997) classifies four moment-resisting frame (FA, FB, FC, FD), and three bracing classes (BA, BB, BC), letter “F” standing for frame, and “B” standing for bracing, whereas the letters A, B, C, D describes the ductility class (Table 1). The smallest behavior factor Ds value (0.25) stands for the most ductile frame type “FA” (Japanese behaviour factor “Ds” has smaller values for higher ductility, in contrast to the European behavior factor q). Ductility of BA, BB, BC types are determined according to the bracing slenderness. For braced frames, “Ds” is modified by means of “β” parameter, which is the ratio between the shear sustained by bracings and the total braced frame. Ductility of braced frame types BB and BC increases with a higher frame participation, when the β values are smaller than 0.7 (i.e. 70% of the shear sustained by bracings), and 0.5 respectively. Arising from an essentially strong-seismicity approach, these threshold values can be considered as high, but it reflects very well the philosophy of exploiting the frame action in braced structures.
The literature study showed that most of the earthquake engineering research focused on applications for the regions exhibiting a high seismicity level, with the aim of maximizing the capacities of buildings in terms of energy dissipation and preventing brittle collapses. Very few research projects investigated the contribution of gravity systems to the lateral system in moderate seismic zones, mostly compatible to US standards. On the other hand, researchers worldwide acknowledge the necessity to find specific design strategies for the CBF structures designed for moderate seismicity. However, very few experimental evidence is available for the characterization of various resistance, stiffness, and ductility resources of braced frames designed for moderate seismicity, mostly limited to the experiments at a component level (e.g. testing only joints), or full scale tests investigating CBFs designed for high seismic actions. There is not enough evidence to quantify the real performance of CBFs designed for moderate seismicity, and draw general conclusions.
European research project RFSR-CT-2013-00022 MEAKADO (Degée et al. 2015; Kanyilmaz 2015) investigates the possibilities to develop specific design methodologies for steel and steel–concrete composite structures in regions characterized by a low to moderate seismic activity, with an appropriate reliability level. It comprises a combination of experimental and numerical studies and aims to formulate proposals according to a pre-standard format in the perspective of further revisions of the design codes. This paper presents the results of full scale tests performed within this research project, which characterize resistance, stiffness, and ductility resources of CBF systems designed for moderate seismicity. The paper focuses on the frame action provided by gusset plate connections of CBF systems, and quantifies its contribution to the global performance of CBF frames designed for moderate seismicity.
2 Experimental program
Although the existing earthquake engineering literature focuses on the high-seismicity context, potential benefits of the secondary frame action of CBF structures have been recently emphasized for low-to-moderate seismicity. Yet, there is still not enough experimental evidence to quantify different aspects of this phenomena related to seismic performance of buildings designed for moderate earthquake actions. For this reason, full scale tests have been designed and performed as a task of the ongoing EU-RFCS MEAKADO project (Degée et al. 2015). From these experimental studies, recommendations for the design of concentrically braced frames in areas with moderate seismicity have been derived, and will be presented hereafter.
Test specimens represent a single storey frame extracted from a multi-storey structure, with dimensions corresponding to realistic full sizes of a building frame, yet limited by the testing facilities. 24 full scale cyclic tests have been performed with specimens of 1 level and 1 bay (2.6 m height and 4.3 m length), having three types of bracing profiles. Two types of test frames have been used:
-
A moment resisting frame with semi-rigid beam-to-column connections (MRF) (Fig. 6a).
-
A frame with ideally pinned connections (PC) (Fig. 6b).
In the first case (MRF), semi-rigid beam-to-column joints have been obtained by means of a gusset plate bolted both to the beams and columns. In the second case (PC), beam-to-column connections have been realized by steel pins that introduce rotational degree of freedom in the loading plane.
Figure 7 shows the construction drawings of the MRF and PC specimens. Beams and columns of these frames have been designed in such a way that they remain elastic at collapse limit state. In the tests, inelastic deformation is permitted and limited only to the bracings and their connections. Between MRF and PC specimens, the overall frame dimensions are kept equal about element inter-axes, so that comparison can be easily made between several tests. Gusset plates are designed in such a way that they can be bolted to the beam and column members of the test frame to allow an easy installation and replacement. After each test, gusset plates and bracing elements have been replaced.
Different bracing configurations have been tested. MRF specimen has also been tested without bracings, with and without gusset plates. The six configurations are described as follows (Fig. 8):
-
1.
X-braced MRF specimens.
-
2.
Single braced MRF specimens.
-
3.
X-braced PC specimens.
-
4.
Single braced PC specimens.
-
5.
MRF specimens without bracings, with gusset plate connections.
-
6.
MRF specimens without bracings and gusset plate connections.
The specimens have been designed according to 30-1-1 recommendations (EN1993-1-1-2005 2005a). Beam-to-column connections of MRF specimen have been designed using double angle plates bolted both to the column flange and to the beam web, by means of Φ24 mm high strength bolts (Fig. 9). This connection type is not expected to have a significant flexural strength and stiffness, with a behaviour close to ideal pin. Therefore, it has been verified against the limit states of shear failure, block shear and bearing strength at the bolt holes.
Gusset plates connecting the bracing joints to the beam-to-column connections have been designed according to uniform force method (American Institute of Steel Construction 2010). They have been designed to avoid buckling under bracing compression loads so that the inelastic deformation is limited only to in-plane buckling of the bracing. Although plastic rotations of gusset plates can be desirable from structural point of view, in the case with double angle bracings, it causes out-of-plane buckling which would eventually damage non-structural components of the building. For moderate seismicity, preventing out-of-plane buckling can be more reasonable due to the low ductility demand.
The gusset plates are welded to the steel plates which are bolted to the beam and column members. The column and beam flange plates are not welded between each other to avoid an extra rotational restraint in the joint (Fig. 10b). This detail was needed in the full-scale tests, to represent the behavior of typical gusset plate connections used in practice, where gusset plates are directly welded to the column and beam flanges.
Also in case of PC specimens, modular gusset plates have been realized, but in this case, the connection element has been hinged at the beam-to-column connection by means of high strength pins, releasing any flexural resistance for the frame. Gusset plates have been bolted to the “fork-type” pinned connection elements (Fig. 11).
Bracings are made of double angles arranged back-to-back by means of steel interconnectors, which is a typical bracing configuration widely used in Europe. Two angles were closely connected with steel plate interconnectors every 30–35 cm (compatible with the requirement of 15.imin of EN1993-1-1 (EN 1993)), which permitted considering the angles as a single integral member under buckling. They are inclined by an angle θ = 30° with the respect of the horizontal axis and have a theoretical length of 5.00 m. The following profiles have been tested:
-
2L-profile 60 × 60 × 8 mm with 4M16 10.9 pre-tensioned bolts.
-
2L-profile 70 × 70 × 7 mm with 4M20 10.9 pre-tensioned bolts.
-
2L-profile 80 × 80 × 8 mm with 4M20 10.9 pre-tensioned bolts.
Table 2 shows the geometrical properties of the bracing profiles with reference to Fig. 12.
Mechanical properties of the steel used for the columns, beams, bracings and the connection elements have been evaluated by means of uni-axial tensile tests (Fig. 13). Table 3 reports the mechanical properties obtained from these tests.
All bracing connection bolts were pre-loaded according to the indications of EN1090-2 (UNI 1090). Combined method has been used, which consists a first tightening phase of the bolts by imposing a torque moment equal to 75% of the pre-load, and a second phase in which the nut is rotated with an additional angle as a function of the total thickness to be tightened (including the thickness of the washers). Table 4 summarizes the values calculated for the two types of bolts.
The bracings in X-type-configuration have been bolted to a steel mid-plate of 15 mm thickness, made of S275JR (Fig. 14).
Design parameters and results are shown in Table 5. In the table, S60, S70, S80 refer to the single bracing diagonals, and X60, X70, X80 refer to the X-bracing specimens. Bracing joints are designed according to EN1993-1-8 rules (EN1993-1-1-2005 2005b), without taking into account any dissipative design concept of EN1998 (EN1998-1-2004 2004). This “non-compliance to the capacity design criteria” is shown by means of CR parameter, which is the ratio between joint resistance (Rd) and the section resistance with over-strength (Npl,ov of Eq. 1 with reference to EN1998-1-1 (EN1998-1-2004 2004)). Shear over-strength (Fv,Rd/Fb,Rd) has been estimated as a ratio between design shear and bearing resistance calculated according to EN1998-1-1 (EN1998-1-2004 2004) clause 6.5.5. The seismic requirement of 1.2 in this case has not always been considered.
where
Rd: min (Fv,Rd; Fb,Rd; Nu,Rd; Veff,Rd) with reference to Table 5.
Npl, Rd: plastic resistance of the connected dissipative member based on the design yield stress of the material.
\( \gamma_{ov} \): Over-strength factor (1.25).
CR: Rd/Npl,ov.
The specimens are designed so that first yielding mechanism is the plastic compression buckling, which is followed by the joint block tearing. Net section yielding is the next phenomena in the sequence for S60, S70, X60 and X70 specimens, while it is the bolt hole yielding due to bearing for the S80 and X80 specimens. All specimens except for S60 and X60 satisfy the 1.20 shear strength rule. None of the specimens satisfies capacity design rule, S60 and X60 are being the closest to achieve the requirement with 0.65 (Table 6).
Tests have been performed in “Laboratorio Prove Materiali” of Politecnico di Milano, from 11th February to 29th April of 2016. Test frame components are shown and listed in Fig. 15. In all tests, cyclic loading has been applied in correspondence to the top joint of right-side column by means of a short beam, transferring the force from the electromechanical actuator, which has a tension/compression capacity of 1000 KN, and a total stroke of 600 mm. Test specimens have been restrained out-of-plane. A displacement controlled loading protocol has been used. The tests have been performed in a quasi-static regime with an application of the displacement at a speed of 0.4 mm/s. ECCS loading protocol has been modified to obtain information at small displacement amplitude increment. Effect of gravity loads has been considered non-influent on the parameters under examination, therefore they have not been applied. Applied global horizontal load has been measured by means of a load cell attached to the loading jack. All the displacements have been measured at various locations of the specimens by means of displacement transducers (LVDT).
Axial deformations have been measured by means of strain gauges. 3-wire strain gauges with FLA-6-350-11-3LT model, manufactured by Tokyo Sokki Kenkyujo Co., with a resistance of 350 Ω, 6 mm grid length and a gauge factor equal to 2.12 have been used. Four strain gauges have been placed at bracing cross sections to calculate axial forces (Fig. 16). Positions of the strain gauges have been kept distant from the possible plastic hinge locations throughout the bracing elements.
The specimen photos are shown in Fig. 17.
Final test program is summarized in Table 7, with the codes used in this paper.
3 Analysis of the test results
In CBF structures, “frame action” naturally exists in the form of beam-to-column shear connections and gusset plate connections of braces. Gusset plate connections provide an extra stiffness and strength engaging the beam and column by means of a welded plate to which the concentric bracing is connected (Fig. 18). This may be a valuable resource as a secondary system to increase global resistance and ductility, and eventually prevent collapse, providing a certain degree of stiffness and strength following the bracing yielding and failure.
Despite even simple gusset plate connections may contribute to this “extra” strength and stiffness capacity in CBF systems, in European design practice these connections are normally designed as simple pinned joints. Several researchers have highlighted the fact that these connections may provide significant strength and stiffness, though only a few experimental studies have been carried out at global level to quantify them (Stoakes and Fahnestock 2010; Uriz and Mahin 2008; Kishiki et al. 2008). In this section, by means of the cyclic tests performed on the specimens schematized in Fig. 19, the secondary frame action has been quantified for the moderate-seismicity context.
Testing these specimens allowed the following investigations:
-
Global behaviour of braced frames has been investigated by means of tests “a” (double bracing MRF specimens) and “b” (single bracing MRF specimens).
-
Global elastic–plastic capacity assessments have been made by single bracing specimens and the double bracing specimen with slender bracings.
-
Global stiffness assessments have been made by two double bracing specimens with less slender bracings.
-
Test types “e” and “f” allowed the assessment of the frame action provided by gusset plates and beam-to-column shear connections.
-
Test types “c” and “d” allowed the assessment of bracing behaviour thanks to idealized pin connections for bracing ends and beam-to-column joints.
Sign convention of load application is shown in Fig. 20a. Base shear is obtained from the load cell attached to the actuator, while global interstorey-drift has been calculated from the LVDT measurements obtained at the top node displacement with the following formula (Fig. 20b):
Figure 21 compares the full global behavior of four test specimens with different bracing elements. S60, S70, S80, X60 represent respectively the three specimens with single diagonals (respectively with 2L60 × 60 × 8, 2L70 × 70 × 7, 2L80 × 80 × 8 bracing profiles), and a double diagonal specimen with relatively high slenderness (2L60 × 60 × 8). Continuous (black) hysteresis curve shows the global force–displacement behavior of the braced frame with single diagonal, drawn until bracing failure, while the dashed-line (blue) hysteresis curve shows the global force–displacement behavior of the MRF frame without bracings. The MRF specimen without bracings has been pushed until large drifts to simulate the performance of the braced frame after a total collapse of bracings. In all tests, secondary frame action could sustain a significant portion of the peak base shear.
Capacity of each specimen following the bracing failure is reported in Table 8, where:
- Vb :
-
Peak base shear (positive)
- Vt :
-
Peak base shear (negative)
- Vfb :
-
Peak base shear of MRF specimen in the same direction with Vb at 2% drift
- Vft :
-
Peak base shear of MRF specimen in the same direction with Vt at 2% drift
During post-buckling stage, specimens continued to have significant strength and stiffness. Figure 22 describes three points on the global behaviour of specimens:
- “A”:
-
Global lateral resistance when the buckling resistance of bracing reached
- “B”:
-
Minimum global lateral resistance during the post buckling stage
- “C”:
-
Global lateral resistance of the frame at 2.0% inter-storey drift
Numerical values corresponding to these points are summarized in Table 9 with the following parameters:
- V(A,B,C) :
-
Global base shear
- IDR(A,B,C) :
-
Global inter-storey drift ratio (%)
- POST-RES:
-
Ratio between the specimen’s minimum post buckling and buckling resistance: VB/VA
- FRAME-RES:
-
Ratio between the specimen’s frame-only (at 2% IDR) and the buckling resistance: VC/VA
- \( \bar{\lambda } \) :
-
Non-dimensional slenderness defined in Sect. 2
Ultimate resistance of the specimens was comparable to their buckling resistance. This means that even when the bracings were in the post-buckling stage, significant resistance was provided by the secondary frame alone. Ratio between the resistance provided by the braced frame with buckled diagonals and the buckling resistance changed between 58 and 80% (Table 9). When the bracings were largely damaged (at incipient collapse stage corresponding to 2% inter-storey drift), only secondary frame action could provide 46 to 127% of lateral resistance of the braced specimens. In case of S60-MRF specimen, the base shear has been increased and even reached values larger than the bracing buckling resistance, within the following cycles.
In all cases, when the bracings were completely damaged due to connection fractures, the moment resisting frame with semi-rigid joints provided an extra capacity. Thanks to this frame back-up, specimens continued to deform reaching large drifts (around 2.5%) with not too large but remarkable resistance and stiffness. Figure 23 shows the specimen X60 before and after section fracture.
Table 10 reports the global ductility provided by bracings-only, and the whole specimen, by means of the following parameters:
- dA-B :
-
Ductility provided by bracing under compression (IDRB/IDRA)
- dA-C :
-
Overall ductility (IDRC/IDRA)
Such a comparison [made with reference to the work of Aboosaber et al. (2012)], confirms that although the CBF systems are known to have limited ductility, when the frame action is able to provide sufficient strength and deformability, the overall ductility reaches important values. With the most slender diagonal (2L60 × 60 × 8) the overall ductility is more than three times the ductility provided by bracings. This significant frame action was mainly due to beam-to-column gusset-plate connections. This is seen in Fig. 24c, where the global base shear- inter storey drift behavior of the MRF specimen with and without gusset plates have been compared. In this case, 75% percent of the elastic stiffness, and the 79% of the ultimate resistance (at 2% drift) are provided by the gusset plate connections.
The source of the beam-to-column ductility is based on a combination of the inelastic deformations of T-stub connection between the gusset plate and the column (Fig. 25) and the web angles connecting the beam web to the column flange (Fig. 26).
Figure 27 shows comparisons between the global behavior of PC and MRF specimens with single diagonal profiles. The contribution of secondary frame action to global resistance is much more significant when the bracings are compressed. This global resistance increase is caused by the combination of two effects: semi-rigid beam end joints with gusset plates and reduced effective slenderness of bracings. The latter effect is due to the fact that in PC specimens the bracings and beam-ends are perfectly pinned, while in MRF specimens their boundary conditions can be considered as semi-rigid, with a rotational stiffness. Unquestionably, ideally pinned conditions result in higher effective slenderness, which is far from the reality. When the bracings are under tension, the effect of bracing boundary condition disappears on the global resistance capacity, and such capacity is affected only by the partial strength of the gusset plate beam-to-column connections. In this case, the influence of the frame effect decreases with decreasing the bracing slenderness. Figures 28 and 29 compare the global stiffness of MRF and PC specimens.
Table 11 reports the global stiffness values obtained in all tests, with following parameters:
- \( \bar{\lambda } \) :
-
Non-dimensional slenderness defined in Sect. 2
- KX :
-
Global stiffness of the X-braced specimen obtained as a ratio of global base shear divided by global interstorey drift at elastic phase, kN/(mm/mm)
- KS :
-
Global stiffness of the single-diagonal specimen obtained as a ratio of global base shear divided by global interstorey drift at elastic phase, kN/(mm/mm)
- MRF:
-
Global stiffness values calculated for MRF specimens
- PCB :
-
Global stiffness values calculated for PC specimens
- MRFB :
-
Global stiffness values calculated subtracting the frame stiffness (281 kN/[mm/mm] for X-braced, 176 kN/[mm/mm] for single-bracing specimens) from MRF values
- CMRF :
-
Per-cent contribution of frame action on braced frame specimens
Lateral stiffness contribution of the frame action (CMRF) is between 7.6 and 13.5% depending on boundary conditions, and bracing slenderness. PC specimens have lower global initial stiffness values with respect to MRF specimens, with the same bracing profiles, because of their ideally pinned connections.
4 Conclusions
Bracing gusset plate connections, although normally designed as simple pinned connections, indeed develop considerable strength and stiffness. This paper investigated the contribution of this “secondary frame action” to the global behaviour of CBF structures, in the context of moderate seismicity. Extra stiffness and strength provided by gusset plate connections have been evidenced by means of full scale tests. Following observations have been made from the tests:
-
Secondary frame resistance combined with the post-buckling resistance of bracings counted between 58 and 80% of the overall braced specimen resistance.
-
Following the total failure of bracings at very large inter-storey drifts, secondary frame action provided between 46 and 127% of the resistance previously developed by the overall braced specimen.
-
Although the CBF systems are known to have limited ductility, when the frame action is taken into account, the overall ductility reached important values (between 1.73 and 4.99 times the ductility provided by bracings-only). This ductility levels have been reached at the resistance levels between 58 and 80% of the maximum resistance of the braced specimen.
-
Lateral stiffness contribution of the secondary frame was between 7.6 and 13.5%, which depended on the boundary conditions, and bracing Sections
-
75% of the elastic stiffness and 79% of the ultimate resistance of the secondary frame, were provided by gusset plate connections. The rest was due to the beam-to-column shear connections.
-
PC specimens had lower global initial stiffness values with respect to MRF specimens, with the same bracing profiles. This difference is caused by the ideally pinned connections of PC specimens.
These results suggest that, in moderate seismic regions, performance of CBF systems can be optimized if the frame action provided by gusset plates is explicitly taken into account. Such contribution can be maximized engaging the beam and column by means of a gusset plate connection (instead of other bracing connection types where gusset plates are connected only on the beam), or a similar solution with the aim of increasing the global stiffness, strength, and ductility. This flexural capacity can be further enriched with additional plates, or involving the composite slab action. Such an intermediate effort may let designer to consider an increased ductility, which can enhance the economy of the building project. It should also be underlined that, in this study, gusset plates are designed to remain elastic and buckling-resistant. It is known that, allowing some inelasticity to the gusset plates, the ductility of the CBF systems increase even more (Hsiao et al. 2012).
Furthermore, current design procedure with simple pinned beam-end assumption does not reflect the realistic behavior of concentrically braced frames. This may lead to wrong estimations both at analysis and design stages in terms of global stiffness and strength characteristics of these type of structures. The author is working on a companion paper that will present a numerical case study based on these experimental conclusions, and provide increased global ductility parameters that can be used in design.
References
Aboosaber M, Bradley C, Nelson J, Hines EM (2012) Modeling reserve system performancefor lowductility braced frames. In T. U. S. o. Engineering (Ed). Tufts University Structural Systems Communication (TUSSC), Medford, MA, pp 122
American Institute of Steel Construction (2010) Seismic provisions for structural steel buildings. Seismic provisions for structural steel buildings
BCJ (1997) Structural provisions for building structures. Tokyo (in Japanese)
Callister JT, Pekelnicky RG (2011) Seismic evaluation of an existing low ductility braced frame building in california. In: Proceedings of ASCE structures congress. ASCE, New York
Carter CJ (2009) Connections and collapse resistance in R = 3 braced frames. PhD thesis
Degee H et al (2013) Design of steel and composite structures with limited ductility requirements for optimized performances in moderate earthquake areas (MEAKADO Research Proposal for EU-RFCS)
Degée H, Hoffmeister B, Castiglioni CA, Martin PO, Calderon I (2015) The “MEAKADO” Project: designing steel and composite structures for optimized performances in moderate earthquake areas. In: Eighth international conference on advances in steel structures
Elghazouli A, Castro JM, Izzuddin BA (2008) Seismic performance of composite moment-resisting frames. Eng Struct 30:1802–1819. doi:10.1016/j.engstruct.2007.12.004
EN 1993-1-1, European Standard (2005) Eurocode 3: Design of steel structures—Part 1-1: General rules and rules for buildings. Eurocode 3, vol 1, p 91
EN1993-1-1-2005 (2005a) Design of steel structures—Part 1.1: General rules and rules for buildings. European Committee for Standardization, CEN, Brussels
EN1993-1-1-2005 (2005b) Design of steel structures—Part 1.8: Design of joints. European Committee for Standardization, CEN, Brussels
EN1998-1-2004 (2004) Design of structures for earthquake resistance—Part 1: General rules, seismic actions and rules for buildings. European Committee for Standardization, CEN, Brussels
Gioncu V, Mazzolani F (2013) Seismic design of steel structures. CRC Press
Han S-W, Choi Y-S (2008) Seismic hazard analysis in low and moderate seismic region-Korean peninsula. Struct Saf 30:543–558. doi:10.1016/j.strusafe.2007.10.004
Hines E, Appel M, Cheever P (2009) Collapse performance of low-ductility chevron braced steel frames in moderate seismic regions. AISC Eng J 3rd Quarter, 149–180
Hsiao PC, Lehman DE, Roeder CW (2012) Improved analytical model for special concentrically braced frames. J Constr Steel Res 73:80–94. doi:10.1016/j.jcsr.2012.01.010
Hsiao PC, Lehman DE, Roeder CW (2013) Evaluation of the response modification coefficient and collapse potential of special concentrically braced frames. Earthq Eng Struct Dyn 42:1547–1564. doi:10.1002/eqe.2286
Kanyilmaz A (2015) Inelastic cyclic numerical analysis of steel struts using distributed plasticity approach. COMPDYN 2015. In: 5th ECCOMAS thematic conference on computational methods in structural dynamics and earthquake engineering, National Technical University of athens, pp 3663–74
Kanyilmaz A, Castiglioni CA, Degèe H, Martin P (2015) A preliminary assessment of slenderness and overstrength homogeneity criteria used in the design of concentrically braced steel frames in moderate seismicity 25–7
Kelly DJ, Zona JJ (2006) Design tips for steel in low or moderate seismicity regions. Mod Steel Constr 46(2):50
Kishiki S, Yamada S, Wada A (2008) Experimental evaluation of structural behaviour of gusset plate connection in BRB frame system. 14th World conference on earthquake engineering, Beijing, China
Málaga-Chuquitaype C, Elghazouli AY, Enache R (2014) Contribution of secondary frames to the mitigation of collapse in steel buildings subjected to extreme loads. Struct Infrastruct Eng 2479:1–16. doi:10.1080/15732479.2014.994534
Marino EM, Nakashima M, Mosalam KM (2005) Comparison of European and Japanese seismic design of steel building structures. Eng Struct 27:827–840. doi:10.1016/j.engstruct.2005.01.004
Murty CVR, Malik JN (2008) Challenges of low-to-moderate seismicity in India. In special issue: Earthquake engineering in the low and moderate seismic regions of Southeast Asia and Australia (2008). EJSE, 64–78
Nelson TA, Gryniuk MC, Hines EM (2006) Comparison of low-ductility moment resisting frames and chevron braced frames under moderate seismic demands. Moment 2:4
Pinto PE (2000) Design for low/moderate seismic risk. Bull NZ Soc Earthq Eng 33:303–324
Reaveley LD, Nordenson GJ (1990) Acceptable damage in low and moderate seismic zones. In: Fourth US-Japan workshop on the improvement of building structural design practices, Hawaii
Stoakes CD (2012) Beam-column connection flexural behavior and seismic collapse performance of concentrically braced frames
Stoakes C, Fahnestock L (2010) Flexural behavior of concentrically-braced frame beam-column connections. Structures congress 2010, pp 1350–1360
UNI EN 1090-2 (2011) UNI EN 1090-2 Execution of steel structures and aluminium structures Part 2: Technical requirements for steel structures
Uriz P, Mahin SA (2008) Toward earthquake-resistant design of concentrically braced steel-frame structures. PEER report 2008/08. Earthquake Engineering Research Center, University of California, Berkeley
Vargas RE, Bruneau M (2008) Experimental validation of the structural fuse concept. In: Proceedings of the 14th world conference on earthquake engineering: innovation practice safety
Yoo JH, Lehman DE, Roeder CW (2008) Influence of connection design parameters on the seismic performance of braced frames. J Constr Steel Res 64:607–623. doi:10.1016/j.jcsr.2007.11.005
Yoo JH, Roeder CW, Lehman DE (2009) Simulated behavior of multi-story X-braced frames. Eng Struct 31:182–197. doi:10.1016/j.engstruct.2008.07.019
Acknowledgements
This article presents the results of full scale tests performed within MEAKADO project coordinated by Prof. Herve Degee, which is carried out with the financial grant of the Research Program of the Research Fund for Coal and Steel of the European Commission (RFSR-CT-2013-00022). Special thanks to Prof. Carlo Andrea Castiglioni, for his precious comments. Thanks to the manager and technicians of the LPM laboratories of Politecnico di Milano. Assistance of the Master thesis students Alberto Volonterio and Umberto Rico during the test implementations is also deeply appreciated.