Keywords

1 Introduction

In the recent years, the three-phase isolated AC-DC converter has been proposed as a converter between AC grid and DC power source or load [1,2,3,4]. Because of high efficiency, high power density, and bi-directional power transfer ability, the topology has enormous application prospects.

After studying traditional control methods such as direct current control with fixed external phase angle, direct current control with fixed modulation coefficient, and model prediction with fixed modulation coefficient, it was found that the above traditional methods are either constant modulation coefficient or constant phase angle control, which cannot achieve control of the peak value of inductance current.

This paper proposed a coordinated optimal control algorithm based on the minimum modulation coefficient and external phase angle of the peak value of inductance current. By changing the modulation coefficient and external phase angle simultaneously through the optimal algorithm, the peak value of inductance current of the isolated AC/DC converter is minimized, the on-state loss of the device is reduced, and the system efficiency and steady-state performance are improved. Based on the above optimal algorithm, this paper proposes two control strategies: the minimum PI control strategy for the peak value of inductance current and the minimum model predictive control strategy for the peak value of inductance current. Finally, the proposed method was validated using MATLAB/Simulink and an experimental platform.

2 System Topological Structure and Working Principle

2.1 System Topology

The circuit topology of the isolated AC/DC matrix converter (IAMC) is shown in Fig. 1, from left to right, consisting of a three-phase AC power supply, grid-side filter, 3–1 matrix converter, high-frequency transformer, rear stage H-bridge circuit, DC side filter, and load [5, 6].

Fig. 1
An illustration of I A M C main circuit topology. It has resistors, capacitators, currents, i a, i b, and i c, three grid currents, i s a, i s b, i s c, and load side voltage u 0. Also, u s a, u s b, and u s c are three phase A C volatages.

IAMC main circuit topology

In Fig. 1, usa, usb, and usc are three-phase AC voltages, isa, isb, and isc are grid-side currents, ua, ub, and uc are the three-phase input voltages of the 3–1 matrix converter, and the currents are ia, ib, and ic. The output voltages of the 3–1 matrix converter are up, and the current is iL. The output voltages of the high-frequency transformer are us. idc is the load side current and u0 is the load side voltage [7].

2.2 Modulation Strategy of IAMC Circuit

The front stage 3–1 matrix converter adopts a bipolar current space vector modulation strategy. The input of the front stage 3–1 matrix converter is an AC voltage source. During circuit operation, the AC power supply cannot be short circuited, and a free moving path needs to be provided for the inductor Lk. In order to ensure its normal operation, the upper and lower bridge arms of the front stage 3–1 matrix converter can only conduct one bi-directional switch at any time [8,9,10,11].

This paper divides a loop into 12 sectors, and the current reference current can be composed of two adjacent fundamental vectors and a zero vector.

To transmit power, a coordinated control method is used, which inserts a phase shift angle between the front stage 3–1 matrix converter and the rear stage H-bridge circuit. The voltage and current waveforms of the output voltage up of the front stage 3–1 matrix converter and the output voltage us of the rear stage H-bridge in one control cycle Ts are shown in Fig. 2.

Fig. 2
A waveform graph of voltage and inductive current. The values on the y axis are u p t, u s t, and i l t. The values on the x axis are from t 0 to t 8. The fluctuating lines are plotted.

Waveform of voltage and inductive current at both ends of transformer

Starting from t0, the output voltage up of the previous stage 3–1 matrix converter divides a control cycle Ts into five time periods. The forward maximum line voltage umax of the previous stage 3–1 matrix converter corresponds to the vector action time t0t2, the forward minor line voltage umed corresponds to the vector action time t4t6, the negative maximum line voltage umax corresponds to the vector action time t2t4, and the negative minor line voltage umed corresponds to the vector action time t6t8, zero vector action time t8Ts.

Divide a control cycle Ts into 9 time periods to obtain the timing of each control period: \(t_{1} = \Delta T_{1}\), \(t_{2} = \frac{{d_{1} }}{2}T_{s}\), \(t_{3} = \frac{{d_{1} }}{2}T_{s} + \Delta T_{1}\), \(t_{4} = d_{1} T_{s}\), \(t_{5} = d_{1} T_{s} + \Delta T_{2}\), \(t_{6} = d_{1} T_{s} + \frac{{d_{2} }}{2}T_{s}\), \(t_{7} = d_{1} T_{s} + \frac{{d_{2} }}{2}T_{s} + \Delta T_{2}\) Among them, \( T_{s} = \frac{2\pi }{{\omega_{s} }}\), the phase shift time between the front and rear stages is \({\Delta }T_{1} = \frac{{\phi d_{1} T_{s} }}{2\pi }\), and \({\Delta }T_{2} = \frac{{\phi d_{2} T_{s} }}{2\pi }\), where \(\phi\) is the external phase shift angle and its value range \(0 \le \phi \le \pi /2\).

The expressions for d1, d2, and d0 when obtaining 12 sectors are given in Table 1.

Table 1 Expressions for d1, d2, and d0 when obtaining 12 sectors

The range of modulation coefficient m is \(0 \le m \le 1/\sqrt 2\) and the range of sector angle \(\theta_{i}\) is \(0 \le \theta_{i} \le \frac{\pi }{6}\).

3 Minimum Control of Peak Inductance Current in Isolated AC/DC Converter

The range of voltage regulation in this topology is large. From the grid-side line voltage of the front stage 3–1 matrix converter in Fig. 3, for different load side voltages u0, the peak inductance current will occur in the following two situations.

Fig. 3
2 illustrations. A. A waveform inductance current diagram for A and B in the first case. It plots u max and u med. B. An illustration of inductance current for C and D in the second case.

Inductance current diagram

When the maximum line voltage umax is greater than the load side voltage nu0, the peak of inductance current is obtained at point A and B in the first case. When the maximum line voltage umax is less than the load side voltage nu0, the peak of inductance current is obtained at point C and D in the second case.

Take the first sector as an example, in the first case, the peak inductance current expression is:

$$ {\text{i}}_{{{\text{LAB}}}} = \frac{{\delta d_{1} T_{s} nu_{o} }}{2L} - \frac{{d_{1} T_{s} nu_{o} }}{2L} + \frac{{d_{1} T_{s} u_{\max } }}{2L} $$
(1)

Formula for modulation factor m, phase shift angle \(\phi\), and current Ii as (2):

$$ I_{i} = m^{2} \frac{{nu_{0} }}{{\omega_{s} L}}\phi (1 - \frac{\left| \phi \right|}{\pi }) $$
(2)

When the reactive power is 0 and the current Ii = Icd, \(\phi = {{\delta \pi } \mathord{\left/ {\vphantom {{\delta \pi } 2}} \right. \kern-0pt} 2}\) will be substituted into Eq. (2), and then combined with Eq. (1) and Table 1 to obtain the expression (3) for the peak of the inductance current and shift ratio in the first sector:

$$ i_{LAB} = - \frac{{\sqrt { - \pi \delta nu_{0} \left( {\delta - 2} \right)\omega_{s} LI_{cd} } \left( {\sqrt 3 U_{i} \cos \left( {\theta_{i} } \right) + n\left( {\delta - 1} \right)u_{0} } \right)T_{s} \sqrt {\cos \left( {\frac{\pi }{6} + \theta_{i} } \right)} }}{{\pi \delta nu_{0} \left( {\delta - 2} \right)L}} $$
(3)

Take the derivative of expression (3), make its derivative function zero, and obtain its minimum in Eq. (4):

$$ \delta = \frac{{\left( {\sqrt 3 U_{i} \cos \left( {\theta_{i} } \right) - nu_{0} } \right)\sqrt 3 }}{{3U_{i} \cos \left( {\theta_{i} } \right)}} $$
(4)

Similarly, the optimal shift corresponding to the minimum peak of the inductance current in the other 11 sectors can be obtained in two cases, as given in Table 2.

Table 2 Optimal shift corresponding to the minimum peak of the inductance current

4 Simulink Results and Analysis

This paper uses MATLAB/Simulink to build a simulation model of an isolated AC/DC converter. The simulation results of constant modulation coefficient current direct control and model predictive control, inductance current peak minimum PI control, and model predictive control prove the correctness of the proposed control strategy. The main circuit parameters are given in Table 3.

Table 3 Parameters of IAMC

The inductance current waveforms of the four control strategies are shown in Fig. 4.

Fig. 4
4 waveform illustration for inductive current. They illustrate P I control strategy for the minimizing peak inductance current, direct current control strategy with fixed modulation coefficient, M P C strategy for minimizing the peak inductance current, and M P C strategy with fixed modulation coefficient.

Inductive current waveform diagram

The simulation results of the relationship between peak inductance current, reference voltage, and load resistance of the four control strategies are shown in Figs. 5 and 6.

Fig. 5.
A line graph of inductive current peak to peak versus load resistance highlights a declining trend.

Relationship between peak inductance current and load resistance

Fig. 6
A multi line graph of inductive current peak to peak versus reference voltage. The graph plots 4 lines. 2 line highlight increasing trend while other 2 illustrate declining trend.

Relationship between peak value of inductance current and reference voltage

From the simulation results of Figs. 4, 5, and 6, the peak value of the inductance current of the proposed control strategy is smaller than that of the fixed modulation coefficient control strategy, which is consistent with theory.

5 Experimental Results and Analysis

To further validate the effectiveness of this method through experiments, an experimental platform for the IAMC converter was established, and the experimental parameters were the same as the simulation parameters. The inductance current waveforms of the four control strategies are shown in Fig. 7.

Fig. 7
4 waveform illustration for inductive current. They illustrate P I control strategy for the minimizing peak inductance current, direct current control strategy with fixed modulation coefficient, M P C strategy for minimizing the peak inductance current, and M P C strategy with fixed modulation coefficient. The experimental parameters were same as the simulation parameters.

Inductive current waveform diagram

The relationship between the peak of inductance current, reference voltage, and load resistance of the four control strategies is shown in Figs. 8 and 9.

Fig. 8
A multi line graph of inductive current peak to peak versus load resistance. The graph plots 4 lines. All lines illustrate a declining trend.

Relationship between peak inductance current and load resistance

Fig. 9
A multi line graph of inductive current peak to peak versus reference voltage. The graph plots 4 lines. 2 line highlight fluctuating trend while other 2 illustrate increasing trend.

Relationship between peak value of inductance current and reference voltage

From the experimental results in Figs. 7, 8, and 9, it can be observed that the peak value of the inductance current of the proposed control strategy is smaller than that of the fixed modulation coefficient control strategy, which is consistent with theory and simulation.

6 Conclusions

To achieve the minimum peak value of inductance current, this paper proposed a coordinated control method for modulation coefficient and external phase angle. The proposed method was compared with the conventional constant modulation coefficient control method in simulations and experiments. The results show that the proposed control strategy has the smallest peak inductance current with good dynamic performance.