Abstract
The isolated AC/DC converter has many advantages such as the ability to convert electricity according to needs, high efficiency, small size, high power density, and the ability to act as a load or power source on demand. The corresponding modulation strategy and control strategy of the topology are analyzed in this paper. Due to the impact of the peak inductance current in its topology on system performance, this paper proposes a control strategy for minimizing the peak value of inductance current to improve system reliability and reduce on-state losses. The optimal algorithm is used to simultaneously change the modulation coefficient and external phase angle to achieve the minimum peak value of inductance current, and the experimental results verify proposed method.
Access provided by Autonomous University of Puebla. Download conference paper PDF
Similar content being viewed by others
Keywords
1 Introduction
In the recent years, the three-phase isolated AC-DC converter has been proposed as a converter between AC grid and DC power source or load [1,2,3,4]. Because of high efficiency, high power density, and bi-directional power transfer ability, the topology has enormous application prospects.
After studying traditional control methods such as direct current control with fixed external phase angle, direct current control with fixed modulation coefficient, and model prediction with fixed modulation coefficient, it was found that the above traditional methods are either constant modulation coefficient or constant phase angle control, which cannot achieve control of the peak value of inductance current.
This paper proposed a coordinated optimal control algorithm based on the minimum modulation coefficient and external phase angle of the peak value of inductance current. By changing the modulation coefficient and external phase angle simultaneously through the optimal algorithm, the peak value of inductance current of the isolated AC/DC converter is minimized, the on-state loss of the device is reduced, and the system efficiency and steady-state performance are improved. Based on the above optimal algorithm, this paper proposes two control strategies: the minimum PI control strategy for the peak value of inductance current and the minimum model predictive control strategy for the peak value of inductance current. Finally, the proposed method was validated using MATLAB/Simulink and an experimental platform.
2 System Topological Structure and Working Principle
2.1 System Topology
The circuit topology of the isolated AC/DC matrix converter (IAMC) is shown in Fig. 1, from left to right, consisting of a three-phase AC power supply, grid-side filter, 3–1 matrix converter, high-frequency transformer, rear stage H-bridge circuit, DC side filter, and load [5, 6].
In Fig. 1, usa, usb, and usc are three-phase AC voltages, isa, isb, and isc are grid-side currents, ua, ub, and uc are the three-phase input voltages of the 3–1 matrix converter, and the currents are ia, ib, and ic. The output voltages of the 3–1 matrix converter are up, and the current is iL. The output voltages of the high-frequency transformer are us. idc is the load side current and u0 is the load side voltage [7].
2.2 Modulation Strategy of IAMC Circuit
The front stage 3–1 matrix converter adopts a bipolar current space vector modulation strategy. The input of the front stage 3–1 matrix converter is an AC voltage source. During circuit operation, the AC power supply cannot be short circuited, and a free moving path needs to be provided for the inductor Lk. In order to ensure its normal operation, the upper and lower bridge arms of the front stage 3–1 matrix converter can only conduct one bi-directional switch at any time [8,9,10,11].
This paper divides a loop into 12 sectors, and the current reference current can be composed of two adjacent fundamental vectors and a zero vector.
To transmit power, a coordinated control method is used, which inserts a phase shift angle between the front stage 3–1 matrix converter and the rear stage H-bridge circuit. The voltage and current waveforms of the output voltage up of the front stage 3–1 matrix converter and the output voltage us of the rear stage H-bridge in one control cycle Ts are shown in Fig. 2.
Starting from t0, the output voltage up of the previous stage 3–1 matrix converter divides a control cycle Ts into five time periods. The forward maximum line voltage umax of the previous stage 3–1 matrix converter corresponds to the vector action time t0–t2, the forward minor line voltage umed corresponds to the vector action time t4–t6, the negative maximum line voltage umax corresponds to the vector action time t2–t4, and the negative minor line voltage umed corresponds to the vector action time t6–t8, zero vector action time t8 − Ts.
Divide a control cycle Ts into 9 time periods to obtain the timing of each control period: \(t_{1} = \Delta T_{1}\), \(t_{2} = \frac{{d_{1} }}{2}T_{s}\), \(t_{3} = \frac{{d_{1} }}{2}T_{s} + \Delta T_{1}\), \(t_{4} = d_{1} T_{s}\), \(t_{5} = d_{1} T_{s} + \Delta T_{2}\), \(t_{6} = d_{1} T_{s} + \frac{{d_{2} }}{2}T_{s}\), \(t_{7} = d_{1} T_{s} + \frac{{d_{2} }}{2}T_{s} + \Delta T_{2}\) Among them, \( T_{s} = \frac{2\pi }{{\omega_{s} }}\), the phase shift time between the front and rear stages is \({\Delta }T_{1} = \frac{{\phi d_{1} T_{s} }}{2\pi }\), and \({\Delta }T_{2} = \frac{{\phi d_{2} T_{s} }}{2\pi }\), where \(\phi\) is the external phase shift angle and its value range \(0 \le \phi \le \pi /2\).
The expressions for d1, d2, and d0 when obtaining 12 sectors are given in Table 1.
The range of modulation coefficient m is \(0 \le m \le 1/\sqrt 2\) and the range of sector angle \(\theta_{i}\) is \(0 \le \theta_{i} \le \frac{\pi }{6}\).
3 Minimum Control of Peak Inductance Current in Isolated AC/DC Converter
The range of voltage regulation in this topology is large. From the grid-side line voltage of the front stage 3–1 matrix converter in Fig. 3, for different load side voltages u0, the peak inductance current will occur in the following two situations.
When the maximum line voltage umax is greater than the load side voltage nu0, the peak of inductance current is obtained at point A and B in the first case. When the maximum line voltage umax is less than the load side voltage nu0, the peak of inductance current is obtained at point C and D in the second case.
Take the first sector as an example, in the first case, the peak inductance current expression is:
Formula for modulation factor m, phase shift angle \(\phi\), and current Ii as (2):
When the reactive power is 0 and the current Ii = Icd, \(\phi = {{\delta \pi } \mathord{\left/ {\vphantom {{\delta \pi } 2}} \right. \kern-0pt} 2}\) will be substituted into Eq. (2), and then combined with Eq. (1) and Table 1 to obtain the expression (3) for the peak of the inductance current and shift ratio in the first sector:
Take the derivative of expression (3), make its derivative function zero, and obtain its minimum in Eq. (4):
Similarly, the optimal shift corresponding to the minimum peak of the inductance current in the other 11 sectors can be obtained in two cases, as given in Table 2.
4 Simulink Results and Analysis
This paper uses MATLAB/Simulink to build a simulation model of an isolated AC/DC converter. The simulation results of constant modulation coefficient current direct control and model predictive control, inductance current peak minimum PI control, and model predictive control prove the correctness of the proposed control strategy. The main circuit parameters are given in Table 3.
The inductance current waveforms of the four control strategies are shown in Fig. 4.
The simulation results of the relationship between peak inductance current, reference voltage, and load resistance of the four control strategies are shown in Figs. 5 and 6.
From the simulation results of Figs. 4, 5, and 6, the peak value of the inductance current of the proposed control strategy is smaller than that of the fixed modulation coefficient control strategy, which is consistent with theory.
5 Experimental Results and Analysis
To further validate the effectiveness of this method through experiments, an experimental platform for the IAMC converter was established, and the experimental parameters were the same as the simulation parameters. The inductance current waveforms of the four control strategies are shown in Fig. 7.
The relationship between the peak of inductance current, reference voltage, and load resistance of the four control strategies is shown in Figs. 8 and 9.
From the experimental results in Figs. 7, 8, and 9, it can be observed that the peak value of the inductance current of the proposed control strategy is smaller than that of the fixed modulation coefficient control strategy, which is consistent with theory and simulation.
6 Conclusions
To achieve the minimum peak value of inductance current, this paper proposed a coordinated control method for modulation coefficient and external phase angle. The proposed method was compared with the conventional constant modulation coefficient control method in simulations and experiments. The results show that the proposed control strategy has the smallest peak inductance current with good dynamic performance.
References
Williamson SS, Rathore AK, Musavi F (2015) Industrial electronics for electric transportation: current state-of-the-art and future challenges. IEEE Trans Industr Electron 62(5):3021–3032
Song J, Zhao R, Kwasinski A (2011) Design considerations for energy storage power electronics interfaces for high penetration of renewable energy sources. ICPE (ISPE)
Vazquez S, Lukic SM, Galvan E et al (2010) Energy storage systems for transport and grid applications. IEEE Trans Industr Electron 57(12):3881–3895
Yilmaz M, Krein PT (2012) Review of battery charger topologies, charging power levels, and infrastructure for plug-in electric and hybrid vehicles. IEEE Trans Power Electron 28(5):2151–2169
Garcia-Gil R, Espi JM (2004) An all-digital controlled AC-DC matrix converter with high-frequency isolation and power factor correction. In: 2004 IEEE international symposium on industrial electronics. Istanbul, Turkey, IEEE, pp 1075–1080
García-Gil R, Espí JM, Dede EJ, et al (2005) A bidirectional and isolated three-phase rectifier with soft-switching operation. IEEE Trans Indus Electr 52(3):765–773
Singh AK, Das P, Panda SK (2014) Novel switching scheme for matrix based isolated three phase AC to DC conversion. In: IECON 2014-40th annual conference of the IEEE industrial electronics society. IEEE, pp 3324–3329
Varajao D, Araujo RE, Miranda LM et al (2018) Modulation strategy for a single-stage bidirectional and isolated AC-DC matrix converter for energy storage systems. IEEE Trans Industr Electron 65(4):3458–3468
Fang F, Li YW (2017) ModuLation and control method for bidirectional isolated AC/DC matrixbased converter in hybrid AC/DC microgrid. In: 2017 IEEE energy conversion congress and exposition (ECCE). IEEE
Shigeuchi K, Xu J, Shimosato N, Sato Y A new modulation method applying optimal duty cycle and phase shift for bidirectional isolated three-phase AC/DC converter based on matrix converter 3514–3521. https://doi.org/10.23919/IPEC.2018.8507521
Abdallah M, Suzuki K, Takeshita T, et al (2017) Soft-switching PWM technique for grid-tie isolated bidirectional DC-AC converter with Si C device. IEEE Trans Indus Appl 1–1
Author information
Authors and Affiliations
Corresponding author
Editor information
Editors and Affiliations
Rights and permissions
Copyright information
© 2024 The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd.
About this paper
Cite this paper
Ao, X., Jia, Z. (2024). Research on Control System of Three-Phase Isolated AC/DC Converter. In: Yadav, S., Arya, Y., Muhamad, N.A., Sebaa, K. (eds) Energy Power and Automation Engineering. ICEPAE 2023. Lecture Notes in Electrical Engineering, vol 1118. Springer, Singapore. https://doi.org/10.1007/978-981-99-8878-5_43
Download citation
DOI: https://doi.org/10.1007/978-981-99-8878-5_43
Published:
Publisher Name: Springer, Singapore
Print ISBN: 978-981-99-8877-8
Online ISBN: 978-981-99-8878-5
eBook Packages: EnergyEnergy (R0)