Abstract
Elevated water tanks are subjected to dynamic loads with varying capacity and located in different seismic zones. The history of the earthquake demonstrates that it has inflicted numerous losses to the life of people and has imposed damages caused to the public utility services such as water tanks. These buildings are particularly sensitive to horizontal wind pressures because of the considerable mass concentrated at the top of the narrow supporting structure. The structural parts of the elevated water tank have been subjected to rigorous computational testing in order to establish how well they function when subjected to wind loads. Four raised water tanks are modelled using finite element analysis and examined in the cloud. An axial load variation investigation of the columns with various staging heights is conducted after the completion of analysis. Results from this research will help better understand raised water tanks and how to construct them so that they can withstand wind loads.
Access provided by Autonomous University of Puebla. Download conference paper PDF
Similar content being viewed by others
1 Introduction
For liquid storage, there are a variety of tanks that can be found in practice, such as those that are either elevated or submerged in water. Among the various types of tanks, elevated tanks are the most important because of their high tank capacity and their ability to meet the demand of the public or industry. Patel [1] studied that water tanks play an important part in public utility and industrial structures, as they are essential for providing a steady flow of water over an extended distance with appropriate static head. Shakib and Omidinasab [2] said that reservoirs that hold water and other liquids are located on the ground and in the air. Reservoirs and tanks have a similar force analysis regardless of the chemical composition of the product. To prevent leaks, all tanks are constructed with no cracks or crevices. If the reinforcement is well maintained, reinforced concrete can be used to build walls and slabs for the storage of water or petroleum products. Vyankatesh and Varsha [3] proposed that a additional treatment is needed on the concrete surface since water and petroleum react with it. Upadhyay and Chirag [4, 5] suggested that overhead distribution systems are often lower in size because they rely on gravity to distribute products.
1.1 Types of Bracing Systems Used
Different models are used for calculating base shear and nodal displacements for staging with cross bracing, staging with chevron bracing, staging with diagonal bracing, staging with k-type bracing, and staging with v-type bracing.
1.2 Response Spectrum Analysıs
In order to perform the seismic analysis and design of a structure to be built at a particular location, the actual time history record is required. Nemade [6] suggested that, however, it is not possible to have such records at each and every location. Further, the seismic analysis of structures cannot be carried out simply based on the maximum values of the ground acceleration as the response of the structure depends upon the frequency content of ground motion and its own dynamic properties. Mhetre [7] proposed that to resolve these difficulties, earthquake response spectrum is the most popular tool in the seismic analysis of structures. Yogeshwarana [8] mentioned that there are many advantages in using the response spectrum method of seismic analysis for prediction of displacements and member forces in structural systems. The method of analysis involves calculation of only the maximum values of the displacements and member forces in each mode of vibration using smooth design spectra that are the average of several earthquake motions. Gandhi [9] illustrated that the response spectral values depend upon energy release mechanism, epicentral distance, focal depth, soil condition, Richter magnitude, damping in the system, and time period of the system.
2 Lıterature Revıew
Upadhyay and Chirag [5] proposed that when an elevated water tank is subjected to away earthquakes, the response of the elevated water tank is examined and an evaluation of seismological response to the same. For earthquake-prone areas, tanks should be designed so that their tops are large enough to develop the seismic-weakness constructions. Haroun MA and Ellaithy [10] studied the soil and foundation structure interactions during earthquakes which were examined by Reheat and Sunna for an elevated rectangular tank. Sloshing effects on the raised tanks’ seismic behaviour and the soil’s radiation dampening impact were ignored. The dynamic interaction between the tower and the supporting soil-foundation system was studied by Haroun and Temraz using two-dimensional X-braced elevated tank models supported on isolated footings. However, the sloshing effects were completely neglected [11]. Marashi and Shakib carried out an ambient vibration test to evaluate the dynamic characteristics of elevated tanks. Dutta et al. [12] examined the structural stability of elevated tanks as a part of their research. A set of estimated empirical equations for the stiffness of different frame supporting systems was proposed by the researchers. It was also studied how the tank system with unintentional eccentricity alters in torsional behaviour as the number of panels grows. Soil-structure interaction (SSI) has been shown to enhance base shear, particularly for tanks with high structures and short structural periods (Dutta et al. 2012). Additionally, the study found that disregarding the effect of SSI could result in high tensile strains in some of the staging columns due to seismic loads. For fluid-elevated tank-foundation-soil systems, they proposed a straightforward analytical approach and employed this approximation in selected tanks. Marashi and Shakib [13].
In this review work, Bansode [14] titled seismic investigation of raised water tank with variable staging design. Using staad-pro v8i 2007, he investigated the behaviour of several staging systems under various tank conditions. Response Spectrum Analysis was performed on three different types of bracing systems of elevated water tanks for various types of zones. He compared the base shear and nodal displacement of an elevated water tank while it was empty and full. Rajesh [15] published a review study on the behaviour of elevated water tanks at various staging heights. They concentrated on the behaviour of raised tanks under varied loads and the safer design of structures in their research. In his review paper titled “Seismic Analysis of RC Elevated Water Tank Using Different Staging Pattern”, Quandri [16] considered different parameters such as water storage capacity, water tower height as consistent and variation in number of segment h/d ratio, and staging arrangement such as normal staging, hexagonal staging, cross staging, and radial staging with central column. Dhage [17] labelled her research “dynamic analysis of RCC elevated water tank”. In her study, she considered two situations with the same tank capacity and found that changes in geometric features of the container can cause changes in the response of the elevated water tank. Gujar [18] laboured to secure a direct source of water from the rain for the water tank. Using water from a tank for irrigation is cost effective in areas where building a well is prohibitively expensive. The water obtained from the high water tank was suitable for home usage, for example, drinking, cooking, and washing. Using water from a tank for irrigation is cost effective in areas where building a well is prohibitively expensive. The water obtained from the high water tank was suitable for home usage, for example, drinking, cooking, and washing.
3 Methodology
The process comprises the simulation of a 100 mm3-litre water tank. These overhead water tanks are analysed at staging heights of 15 m, 18 m, 21 m, and 25 m, accordingly. It is observed at a wind speed of 44 m/s. Wind load dynamic analysis is done using the Staad.Pro software. The design of the water tank must be able to endure earthquake loads, which increases as the seismic zones increase.
Methods of seismic analysis
Main two different types of design analysis are as follows.
Equivalent static analysis
Water tanks with an elevated water level can be effectively appealed statistically. When the seismic load is represented in the form of identical static loads, it is necessary, to get an accurate estimate, and it only needs one degree of freedom in the estimation in relation to the tank.
where
-
K = Lateral stiffness of staging
-
P = Applied lateral force
-
∆ = Deflection in mm
Dynamic analysis
Water tanks with an elevated water level can be effectively applied numerically. When the seismic load is represented in the form of identical static loads, it is necessary to get an accurate estimate. It only needs one degree of freedom in the estimation in relation to the tank.
Seısmıc Analysıs of Elevated Water Tank
Equivalent static analysis of raised water tanks is used to convert seismic loads into equivalent static loads, which is the most common method of analysing tanks. The method for analysing an elevated water tank for seismic loading has been provided by IS: 1893–2002. Seismic loads have historically been measured in terms of equivalent static accelerations, which were affected by a variety of factors, including the location’s seismicity, soil qualities, the natural frequency of the building, and its proposed usage. When a water tank is elevated, it can be analysed in both the full and empty states. A single-mass tank can be ideal for both conditions. Although both water and structure are assumed to be adhered to the container, the water-structure interaction indicates that both water and structure acquire picks at the same time for an identical static analysis.
General specifications
The dimensions of the circular and rectangular water tanks are regarded the same for all the different stage heights. The foundation, columns, and bracing all have a role in supporting the weight of the tanks above. Structural elements used to construct the water tank’s staging must be strong enough to withstand axial loads, moments, and shear forces.
Foundation
Bottom of foundation 2 m
Centre of plinth beam 0 006D
Width of plinth beam 0.25 m
Depth of plinth beam 0.5 m
Columns
Diameter of the column 0.55 m
Bracing
Width of bracing beam 0.25 m
Depth of bracing beam 0.5 m
-
Floor beam
Width of floor beam 0.3 m
Depth of floor beam 0.7 m
-
Floor slab
Thickness of floor slab 0.2 m
-
Walking gallery
Thickness of gallery 0.2 m
-
Cylindrical wall or rectangular wall
Top width of wall 0.2 m
Bottom width of wall 0.2 m
Height of wall 4.2 m
-
Roof Slab
Thickness of roof slab 0.2 m
Weight of components
The weight of the components is determined by calculating the volume of the elements by the density weight of the concrete. Imperviousness is a condition for any water tank design. Wider fractures in the water tanks should be avoided, if possible, to make them impenetrable. M30 grade concrete which has a density of 25kN/m3 is considered. Empty tank weight plus one-third of staging weight is included in the structural calculation procedure. A water load is considered a dead load. Furthermore, the freeboard is not considered in the depth of water while conducting dynamic analysis (Tables 1, 2, 3 and 4).
Centre of gravity
The stability of objects is affected by their centre of gravity. Centre of gravity greatly simplifies calculations involving gravity and dynamics, allowing us to regard an object's mass as though it is concentrated at one location. Product of distance from top of floor beam to components of empty tank and component weights divided by total empty tank weight yields centre of gravity of empty tank.
Wind Force
According to a building’s or structure’s effective frontal area Ae and design wind pressure Pd, total wind load on that particular building or structure can be calculated using force coefficients (Figs. 1, 2 and Table 5).
4 Results and Discussions
The 100 mm3 tank models are created and analysed in the software for the staging heights of 15 and 25 m, respectively. The x- and z-direction moments for the circular and rectangular tanks are compared to see how they are different. Circular and rectangular raised service reservoirs on different staging heights are studied in the maximum axial stress acting on the column RC 100 mm3 capacity circular and rectangular water container. For all seismic zones, the tank is situated on a medium-soil base. Staging concrete is graded M30, and steel is graded Fe415, correspondingly. Concreting is 25 kN/m3 in density, and the tanks are analysed for vibrations (Fig. 3 and Tables 6, 7).
Inferences
-
1.
Displacement of Circular tank-1 > Circular tank-2 > Rectangular tank-1 > Rectangular tank-2.
-
2.
In all the cases, displacement in full condition is more and in empty condition is less.
-
3.
For staging height 15 m < staging height 25 m, i.e. 13 mm and 17 mm (Fig. 4 and Table 8).
Inferences
-
1.
Base shear is more for Circular tank-2 and Rectangular tank-2 due to more wall thickness of 1890 mm.
-
2.
Circular tank-1 and Rectangular tank-1 show less base shear value due to less wall thickness of 1665 mm.
-
3.
Base shear of staging height 15 m is almost equal to staging height 25 m (Fig. 5 and Table 9).
Inferences: Regarding Base Shear
-
1.
Circular tank-2 and Rectangular tank-2 show more shear force values.
-
2.
Empty condition for Circular tank-2 has the largest shear force value.
-
3.
Full condition for the Rectangular tank-2 has the next largest shear force value.
-
4.
Half condition for Circular tank-1 has the lowest shear force value (Fig. 6 and Table 10).
Inferences
-
1.
In all the cases, full condition shows more displacement and empty condition shows less displacement.
-
2.
Circular tank > rectangular tank.
-
3.
Circular tank-1 > Circular tank-2 > Rectangular tank-1 > Rectangular tank-2 (Fig. 7 and Table 11).
Inferences
-
1.
In all the cases, empty condition shows more base shear but in Rectangular tank-2, full condition shows more value, and in Circular tank-2, half fill tank condition shows more value.
-
2.
Circular tank > rectangular tank.
-
3.
Circular tank-2 and Rectangular tank-2 show more values since the wall thickness is more (Fig. 8 and Table 12).
Inferences
-
1.
In general, empty condition is more, but in Circular tank-2 half fill condition and in Rectangular tank-2 full fill condition effect is more.
-
2.
Circular tank is more effective than rectangular tank.
-
3.
Rectangular tank-2 has more effect than Rectangular tank-1 since the wall thickness is more. Therefore, capacity > demand.
Zone III Different Storey level with 15 m staging
Inferences: Regarding Displacement
-
1.
Circular tank-1 > Circular tank-2 > Rectangular tank-1 > Rectangular tank-2.
-
2.
Full condition > half fill condition > empty condition for all the shapes.
-
3.
15 m Staging > 25 m staging.
Inferences: Regarding Base Shear
-
1.
In general, empty is more than other cases, except in Rectangular tank-2 full condition since for Rectangular tank-2, wall thickness is 1890 mm which is greater than Rectangular tank-1 of 1665 mm.
-
2.
Rectangular tank-2 and Circular tank-2 show more base shear since wall thickness is more.
-
3.
15 m staging > 25 m staging.
Inferences: Regarding Shear Force
-
1.
All most all the cases are equal; however, a slight more in Rectangular tank-2 and a slight less in Circular tank-1 are observed.
-
2.
In general, empty conditions show more value except Rectangular tank-2 full fill condition.
-
3.
25 m staging < 25 m staging.
Zone III with 25 m staging
Inferences: Regarding Displacement
-
1.
Circular tank-1 > Circular tank-2 > Rectangular tank-1 > Rectangular tank-2.
-
2.
Circular tank > rectangular tank.
-
3.
15 m staging > 25 m staging.
Inferences: Regarding Base Shear
-
Base shear is larger in Circular tank-2 half fill condition, and Rectangular tank-2 full fill condition is maximum since the wall thickness is more, i.e. 1890 mm.
-
Circular tank-1, half fill condition and Rectangular tank-1, full fill condition have same values since they have same wall thickness 1665 mm which are less than Circular tank-2 and Rectangular tank-2.
-
25 m staging > 15 m staging.
Inferences: Regarding Shear Force
-
1.
Circular tank-2 with half fill condition and Rectangular tank-2 with full condition show more values.
-
2.
Circular tank-1 shows less value than all other cases.
-
3.
25 m staging > 15 m staging since distribution of base shear is more.
Zone IV Different Storey levels in m for 15 m staging
Inferences: Regarding Displacement
-
1.
Circular tank-1 > Circular tank-2 > Rectangular tank-1 > Rectangular tank-2.
-
2.
Full condition > half fill condition > empty condition.
-
3.
Maximum 30 mm, minimum 3 mm.
-
4.
15 m staging < 2 m staging, i.e. 30 mm < 40 mm.
Inferences: Regarding Base Shear
-
1.
Circular tank-2 and Rectangular tank-2 show more values, i.e. 320 KN and 350 KN, respectively.
-
2.
Circular tank-2 with empty condition and Rectangular tank-2 with full condition shape influence more since thickness of wall is more, i.e. 1890 mm.
-
3.
15 m staging is almost equal to 25 m staging.
-
4.
Maximum is 370 KN and minimum is 220 KN.
Inferences: Regarding Shear Force
-
1.
Shear force is more in case of Rectangular tank-1 and Rectangular tank-2, which is about 325 KN to 330 KN even though maximum value exists in Circular tank-2 empty condition, i.e. 370 KN.
-
2.
Circular tank-1 and Circular tank-2 show less values except empty condition of Circular tank-2, i.e. about 350 KN.
-
3.
25 m staging > 15 m staging since distribution of base shear is along the height.
Zone IV For 25 m staging
Inferences: Regarding Displacement
-
1.
Circular tank-1 > Circular tank-2 > Rectangular tank-1 > Rectangular tank-2.
-
2.
Full condition > half condition > empty condition 40 mm > 26 mm > 15 mm for circular tank.
-
3.
25 m staging displacement > 15 m staging displacement, i.e. 40 mm > 30 mm due to less stiffness.
Inferences: Regarding Base Shear
-
1.
Circular tank-2 with half fill condition and Rectangular tank-2 with full condition show more base shear 350 KN and 400 KN, respectively.
-
2.
Circular tank-1 and Rectangular tank-1 have almost same value, i.e. 275 KN in empty condition.
-
3.
25 m staging base shear is almost equal to 15 m staging base shear, i.e. 370 KN and 380 KN, respectively.
Inferences: Regarding Shear Force
-
1.
Rectangular tank-2 and Rectangular tank-1 have about 340 KN to 350 KN, which are more than Circular tank-1 and Circular tank-2 except half fill condition in Circular tank-1 with 375 KN and empty condition in Circular tank-2 with 380 KN.
-
2.
25 m staging > 15 m staging, i.e. 380 KN > 370 KN.
Zone V Different Storey level for 15 m staging
Inferences: Regarding Displacement
-
1.
Circular tank-1 > Circular tank-2 > Rectangular tank-1 > Rectangular tank-2.
-
2.
Full condition > half fill condition > empty condition in each case.
-
3.
Displacement of 25 m staging > 15 m staging, i.e. 60 mm > 45 mm.
Inferences: Regarding Base Shear
-
1.
Circular tank-2 and Rectangular tank-2 show more values, i.e. 332 KN and 370 KN.
-
2.
Circular tank-2 with empty condition and Rectangular tank-2 with full condition show more values because wall thickness is more, i.e. 1890 mm > 1665 mm.
-
3.
Base shear for 25 m staging > 15 m staging, i.e. about 380 KN and 370 KN.
Inferences: Regarding Shear Force
-
1.
Almost all are the same except Circular tank-1 with half fill condition having 375 KN and Circular tank-2 having 380 KN.
-
2.
Rectangular tank has slightly more than that of the circular tank.
-
3.
25 m staging > 15 m staging, i.e. about 390 KN > 380 KN.
Zone V Different Storey level for 25 m staging
Inferences: Regarding Displacement
-
1.
Circular tank-1 > Circular tank-2 > Rectangular tank-1 > Rectangular tank-2, i.e. 15 mm > 50 mm 32 mm > 18 mm.
-
2.
Full Condition > half fill condition > empty condition.
-
3.
25 m staging > 15 m staging because of less stiffness.
Inferences: Regarding Base Shear
-
1.
Circular tank-2 and Rectangular tank-2 are having maximum values. 375 KN and 360 KN values for Circular tank-2 in half fill condition and Rectangular tank-2 in full condition, respectively. Circular tank-1 and Rectangular tank-1 are less than Circular tank-2 and Rectangular tank-2.
-
2.
Circular tank-2 dominates in empty condition.
-
3.
Circular tank-1 and Rectangular tank-1 < Circular tank-2 and Rectangular tank-2.
-
4.
25 m staging > 15 m staging, i.e. 400 KN > 370 KN since the distribution of base shear is along the height.
Inferences: Regarding Shear Force
-
1.
All are almost the same, except Circular tank-1 in half fill condition and Circular tank-2 in empty condition.
-
2.
Rectangular tank-1 and Rectangular tank-2 are uniform. Circular tank-1 and Circular tank-2 are slightly more than rectangular tanks.
-
3.
All the water fill conditions are almost the same.
-
4.
25 m staging is almost equal to 15 m staging, i.e. 375 K.
The maximum moments for circular tanks are lower than those for rectangular tanks. Increasing the height of the tanks’ staging area for the same tank capacity increases the value of the moments. Due to the smaller effective area of a circular tank, it is less subjected to wind effects than a rectangular tank is. Due to the circular tank’s lack of columns, this is more readily apparent than the rectangular tank.
5 Conclusion
Many good innovations and developments have been produced in various designs and forms for water tanks, which are highly significant for open utility and modern structure. The following are the results of the seismic analysis of the elevated water tank:
-
1.
Because of the zone factor, response reduction factor, etc., the base shear of a full water tank and an empty water tank is both increased in seismic zones II–V.
-
2.
Base shear in perfect working orders for the full tank is slightly higher than an empty tank because of the pressure difference or the absence of water.
-
3.
Because of the zone factor, response reduction factor, etc., the displacement of a full water tank and an empty water tank is enhanced in seismic zones II–V.
-
4.
When the tank is full, the wall of the tank has the maximum and smallest nodal deformations.
-
5.
Comprehensive and empty water tanks are subjected to higher shear and bending moments due to the zone factor, response reduction factor, etc., in seismic analysis.
-
6.
In a full tank, the shear force and bending moment are slightly larger than in an empty tank because of the lack of water or hydrostatic pressure.
References
Patel CN, Patel HS (2012) Supporting systems for reinforced concrete elevated water. Int J Adv Eng Tanks 2(1):68–71
Shakib H, Omidinasab F, Ahmadi MT (2010) Seismic demand evaluation of elevated reinforced concrete water tanks. Int J Civil Eng 8(3):204–220
Vyankatesh K, Varsha T (2017) Comparative study on dynamic analysis of elevated water tank frame staging and concrete shaft supported. IOSR J Mech Civil Eng (IOSR-JMCE) 14(1):38–46
Upadhyay S, Chirag N (2016) Seismic behavior of elevated storage reservoir by finite element method. Int Conf Recent Innov Eng Manage 4(3):1188–1197
Upadhyay S, Chirag N (2015) Seismic behavior of elevated storage reservoir by finite element method. Int Conf Recent Innov Eng Manage 4(3):1990–998
Nemade PS (2016) Parametric studies in design of staging configuration for elevated service reservoir for seismic consideration: a review. IJSTE Int J Sci Technol Eng 2(09). ISSN (online): 2349-784X
Mhetre MS, Patil GR. Analysis of elevated water storage structure using different staging system. IOSR J Mech Civil Eng (IOSR-JMCE) e-ISSN: 2278–1684, p-ISSN: 2320–334X, pp 21–32
Yogeshwarana J, Pavithra C (2015) Behaviour of an elevated RC tank subjected to various earthquake responses. Int J Eng Trends Technol (IJETT) 21(9)
Gandhi MN, Rajan A (2014) Necessity of dynamic analysis of elevated water storage structure using different bracing in staging. Int J Res Adv Technol 2(2). E-ISSN: 2321–9637
Haroun MA, Ellaithy MH (1985) Seismically induced fluid forces on elevated tanks. J Tech Top Civil Eng 111(1):1–15
Haroun MA, Termaz MK (1992) Effects of soil-structure interaction effects on seismic response of elevated tanks. Soil Dynam Earthq Eng 11(2):37–86
Dutta S, Mandal A, Dutta SC (2004) Soil-structure interaction in dynamic behavior of elevated tanks with alternate frame staging configurations. J Sound Vib 227(4–5):825–853
Marashi ES, Shakib H (1997) Evaluations of dynamic characteristics of elevated water tanks by ambient vibration tests. In: Proceedings of the 4th international conference on civil engineering, Tehran, Iran, I, pp 367–73
Bansode PA, Datye VP. Seismic analysis of elevated water tank with different staging configuration. MAT J Geotechn Stud 3(1)
Rajesh C, Jha S, Shrilakshmi P. Seismic behavior of an elevated water tank for different staging height. Int J Magaz Eng Technol Manage Res
Quadri SS, Sawant RM. Seismic analysis of RC elevated water tank using different staging pattern. Int J Struct Eng Analy
Dhage PN, Joshi MM. Review study an dynamic analysis of RCC elevated water tank. Int J Emerg Technol Innov Res
Gujar V, Sayyed S (2011) Review on seismic analysis of elevated water tank with different staging configuration. Int J Eng Res Technol (IJERT) 8(12). ISSN: 2278–0181
Lakhankiya J, Shah HJ (2015) A parametric study of an Intze tank supported on different staging. Int J Sci Res Eng Dev 3(9):1108–1112
Livaoglu R, Dogangün A (2007) Effect of foundation embedment on seismic behavior of elevated tanks considering fluid- structure-soil interaction. First Int Conf Seismol Earthq Eng (SEE) 27(1):855–863
Author information
Authors and Affiliations
Corresponding author
Editor information
Editors and Affiliations
Rights and permissions
Copyright information
© 2022 The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd.
About this paper
Cite this paper
Tirupathi, D., Srinivasu, K. (2022). Analysis of Elevated Water Tank by Considering Slab, Wall, and Capacity in Seismic Zones. In: Geetha, K., Gonzalez-Longatt, F.M., Wee, HM. (eds) Recent Trends in Materials. Springer Proceedings in Materials, vol 18. Springer, Singapore. https://doi.org/10.1007/978-981-19-5395-8_25