Keywords

1 Introduction

Designing an energy-efficient structure is one of the best methods to reduce energy costs in buildings. To design energy-efficient buildings, structural components and building envelope parameters must be optimized. It is critical to recognize the basic factors that are directly related to heat transfer processes. The theoretical design phase of a structure is the best ideal opportunity to incorporate feasible systems. Energy-efficient design methods provide additional value that benefits the end-user. An organized plan dependent on energy-saving standards diminishes economic expenses all through the lifecycle of the structure because of its lower energy consumption [1, 2]. Since there are additionally less CO2 discharges into the environment all through the structure’s yearly energy utilization, this is advantageous to society also. Energy saving is a high need in developed nations. Consequently, energy efficient measures are as a rule progressively executed in all possible areas.

2 Literature Review

The energy saving is a high need in the entire world. The residential sector is a major contributor to the total energy consumption. A large amount of energy is utilized in the cooling and heating systems. Energy efficient structures can be constructed by studying and applying the measures required for achieving it. The measures include shape of the building, building orientation, building envelope system, cooling, and heating, etc., of residential structures [3]. It is possible to improve the energy efficiency of buildings without any additional cost. Buildings should be oriented properly to get the maximum passive solar energy. Morrissey et al. [4] concluded that the concept of passive solar energy should be incorporated in design stage to improve the energy efficiency of buildings. The effect of passive parameters, for example, building shape and building orientation on heating demand has been theoretically examined by Aksoy and Inallib [5] by selecting a cold region (Elazig region) of Turkey. Building orientation was varied from 0° to 90°. It is concluded that structures with a square shape are more advantageous with respect to energy efficiency. Ourghi et al. [6] examined the effect of the shape for office building on its yearly cooling and total energy use. A streamlined examination technique is developed dependent on point-by-point investigations using a few blends of building geometry, glazing type, glazing area, and climate. An immediate connection has been made between relative minimization and complete structure energy use just as the cooling energy prerequisite.

Eskin and Turkmen [7] studied the electricity use in commercial buildings in Turkey. The interactions between various conditions, control systems, and heating/cooling loads in office buildings in the four significant climatic zones in Turkey were studied. This study is used to examine energy conservation opportunities on annual cooling, heating and total building load at four major climatic zones of Turkey. Jazayeri and Aliabadi [8] investigated energy efficiency in the cold and semi-arid climate of Shiraz, Iran. They evaluated energy efficiency in two stages. In the first stage, larger windows with NS facade were considered and in second stage all facades of equal window-to-wall ratio and different building aspect ratios were considered. When different facades are varied, the optimal aspect ratio of a building can be different for different Window to wall ratio (WWR). Friess et al. [9] studied the energy demand of residential villas in Dubai. Minimum insulation levels for external wall and roof wall (U-value = 0.57 w/m2-k) and reinforcement concrete frame was considered non-insulated. This work studied the effect of thermal impact on the structure’s energy consumption by using a software model. Simulation results showed that with suitable outside wall protection methodologies alone, energy savings of up to 30% are obtained. Studies were also carried out on energy simulation tools and the strengths and weaknesses of each tool were studied [10]. Most of the studies have focused on a particular envelope component in a generic building. There is a lack of comparative study of the relative efficiency and impact of passive design strategies.

3 Methodology

3.1 Model and Parameters

In this study, a residential single-family residence house is considered and the effects of different building envelope parameters are studied on the energy efficiency of the building. A single-family house with one floor and basement is modeled for study. Building overview details are provided in Table 1. The house is located at Gadag, Karnataka, which falls under climate Zone 1B: warm and humid as per ECBC [11]. Table 2 provides information on the geography and climate of Gadag. The floor plan is shown in Fig. 1 and the building envelope parameters which have been used as the input parameters in this study are presented in Table 3.

Table 1 Building overview details
Table 2 Details of geography and climate of Gadag
Fig. 1
Building floor plan using Model and Parameters of a residential single-family residence house considered and the effects of different building envelope parameters studied on the energy efficiency of the building. The plan is divided into stairway, parking, living room, hall and dining room, 2 bedrooms, kitchen, bathroom and toilet.

Building floor plan

Table 3 Building envelope parameters

A residential building with three aspect ratios 1:1, 1:1.5 and 1:2 same building area 111.30 m2 is considered for analysis. Hall, bedroom, kitchen, stairway, and parking, etc., suitable dimensions of length and breadth are set out as given in Table 4.

Table 4 Building geometry

3.2 Internal Loads and Schedules

The residential building of single-family with an occupancy of five people is considered for the present study. Details of activity, maximum occupancy, equipment load and lighting loads in each of the rooms are provided in Table 5.

Table 5 Activities and schedules (general energy code or ECBC, 2017)

3.3 Building Envelope

The building envelope is the physical boundary between the outside and inside environments encasing a structure. It is comprised of a series of components and frameworks that shield the inside space from the impacts of the environment such as precipitation, wind, temperature, humidity and also ultraviolet radiation. The internal environment is comprised of the occupants, building materials, lighting, machinery and the HVAC system. Improving the structure envelope of houses is perhaps the most ideal approach to improve energy efficiency. This home is modeled using advanced framing techniques. Layer-by-layer details of the wall, roof, and floors are provided. Using these details, creating custom layers and, if necessary, materials using the Design-Builder software. Building envelope construction details are considered as per ECBC 2017 (Fig. 2).

Fig. 2
Building Envelope, a physical boundary between the outside and inside environments encasing a structure which is comprised of a series of components and frameworks that shield the inside space from the impacts of the environment such as precipitation, wind, temperature, humidity and also ultraviolet radiation.

Building envelope selected for the present study

3.4 Mechanical Systems

The building is considered to be centrally heated and cooled. The heating is provided through a gas furnace and the cooling system is a central split system. Efficiency details of the HVAC and SHW systems are provided as per ECBC 2017 (Table 6). The building is modeled in a software tool (Design builder) and various parameters are assigned to study the thermal efficiency in a warm and humid climate zone in India. Three envelope parameters namely aspect ratio (1:1, 1:1.5 and 1:2), orientation (North–South and East–West) and window-wall ratio (30, 40 and 50%) are varied by using three typical models and their energy efficiencies are evaluated.

Table 6 Mechanical system details (general energy code or ECBC 2017)

Following are the details of the three models considered in this study:

  • Model 1Single-family residential building with outer dimensions of 10.55 m × 10.55 m is considered for Model 1. Aspect ratio is kept as 1:1 and both orientations North–South and East–West are considered. Window to wall ratio is varied as 30, 40 and 50% (Fig. 3).

    Fig. 3
    A bar graph of energy consumption for model-1 for a single-family residential building with outer dimensions of 10.55 m × 10.55 m is considered and the aspect ratio is kept as 1:1.

    Energy consumption for model-1

  • Model 2Single-family residential building with outer dimensions of 12.93 m × 8.62 m is considered for Model 2. Aspect ratio of 1:1.5 and orientations in both North–South and East–West direction are considered. Window to wall ratio is varied as 30, 40 and 50%.

  • Model 3Single-family residential building with outer dimensions of 14.96 m × 7.45 m is considered for Model 3. Aspect ratio is kept as 1:2 and both orientations North–South and East–West are considered. Window to wall ratio is varied as 30, 40, and 50%.

4 Results and Discussions

In this section, the results of the thermal analysis of the three models are presented and discussed. The thermal efficiencies are discussed in terms of electricity consumption for lighting, heating, DHW, cooling, annual energy consumption and temperature.

4.1 Thermal Energy Efficiency of Model-01

The results of the thermal energy efficiency for model-1 are presented in Table 7. It is seen that the room electricity requirement of 1722.28 kWh is constant for different window to wall ratios. When lighting electricity is considered, small variations are seen for different window to wall ratios. It is observed that for window to wall ratio of 30% lighting electricity is found to be 1197.14 kWh, 1179.70 kWh for 40% and 1169.16 kWh for 50%. Heating and DHW electricity remained constant for different window to wall ratios. The cooling electricity is found to vary for different window to wall ratios. It is seen that for window to wall ratio of 30% cooling requirement is found to be 9314.08 kWh and for 40% and 50%, the cooling requirements are found to be 10007.93 kWh and 10699.93 kWh respectively. There is a large variation in the annual energy consumption for different window to wall ratios. The annual energy consumption is found to be 14405.11 kWh, 15081.55 kWh and 15762.98 kWh for window to wall ratio of 30%, 40% and 50%, respectively. In general, it can be seen that irrespective of the orientation, the energy consumption is found to increase with increasing window to wall ratios. This is true due to the fact that there will be increased thermal energy transfer between inside and outside environments with increased window to wall ratios and vice versa.

Table 7 Energy consumption results model-1

The energy consumption model is presented in Fig.4. The difference in the cooling electricity requirement is found to be lesser by 693.85 kWh and 693.85 kWh for a window to wall ratio of 30% and 40% respectively in comparison with 50%. It is observed that the annual energy electricity requirement is found to be reduced by 676.44 kWh and 681.43 kWh for window wall ratio of 30% and 40% as compared to 50%.

Fig. 4
A bar graph of temperature variations between inside and outside environments of model-01 by maintaining the window to wall ratio.

Temperature variations between inside and outside environments (model-01)

From Fig.4, it is observed that the inside temperature increases by increasing the window to wall ratio for a constant outside temperature of 36.6 ℃. The inside temperatures observed are 33.1, 33.5 and 34 ℃ for window to wall area ratios of 30%, 40% and 50%, respectively.

Annual energy consumption for model-01 is found to increase for higher window wall ratios. The annual energy consumption is found to increase by 4.7 and 4.5% for window to wall ratios of 40% to 50% respectively as shown in Table 8. Also, daylight and sunlight dispersion map of model-01 is shown in Figs. 5, 6 and 7.

Table 8 Annual energy consumption for WWR
Fig. 5
A heatmap for daylight inside the room of aspect ratio 1:1 and WWR30 percent is displayed.

Daylight inside the room (aspect ratio 1:1 and WWR30%)

Fig. 6
A heatmap for Daylight inside the room of aspect ratio 1:1 and WWR40 percent is displayed.

Daylight inside the room (aspect ratio 1:1 and WWR40%)

Fig. 7
A heatmap for Daylight inside the room of aspect ratio 1:1 and WWR50 percent is displayed.

Daylight inside the room (aspect ratio 1:1 and WWR50%)

4.2 Thermal Energy Efficiency of Model-02

The results of the thermal energy efficiency for model-2 are presented in Table 9 and Fig. 8. It is seen again that the room electricity requirement of 1530.4 kWh is constant for different window to wall ratios. Heating and DHW electricity did not vary for different window to wall ratios. When lighting electricity is considered, small variations are seen for different window to wall ratios. More variations are seen for cooling electricity for different window to wall ratios. It is seen that for window to wall ratio of 30%, cooling requirement is found to be 9314.08 kWh and for 40% and 50%, the cooling requirement are found to be 10007.93 kWh and 10699.93 kWh respectively. There is a large variation in the annual energy consumption for different window to wall ratios which can be seen in Table 9. The cooling electricity is found to increase significantly for increased window to wall ratios. Also with respect to orientation, North–South orientation is found to be better than the East–West orientation in improving the overall thermal efficiency of the building.

Table 9 Energy consumption results of model-2
Fig. 8
A bar graph of energy consumption model-2 consisting of single-family residential building with outer dimensions of 12.93 m × 8.62 m is considered with an aspect ratio of 1:1.5.

Energy consumption model-2

From Figure 9 it is observed that inside temperature increases with increasing window to wall ratio for constant outside temperature of 36.6 ℃. Also, the North–South orientation is better than East–West orientation with respect to annual energy consumption (Fig. 10). On the other hand, East–West orientation is slightly better in reducing the inside temperatures of the building. Also, daylight and sunlight dispersion map of model-02 is shown in Figs. 11, 12 and 13 (Table 10).

Fig. 9
A bar graph of temperature variations between inside and outside environments for model-2 by maintaining the window to wall ratio.

Temperature variations between inside and outside environments for model-2

Fig. 10
A heatmap for Daylight inside the room of aspect ratio 1:1.5 and WWR30 percent is displayed.

Daylight inside the room (aspect ratio 1:1.5 and WWR30%)

Fig. 11
A heatmap for Daylight inside the room of aspect ratio 1:1.5 and WWR40 percent is displayed.

Daylight inside the room (aspect ratio 1:1.5 and WWR40%)

Fig. 12
A heatmap for Daylight inside the room of aspect ratio 1:1.5 and WWR50 percent is displayed.

Daylight inside the room (aspect ratio 1:1.5 and WWR50%)

Fig. 13
Energy consumption chart model-3 consisting Single-family residential building with outer dimensions of 14.96 m × 7.45 m is considered with an aspect ratio of 1:2.

Energy consumption chart model-3

Table 10 Annual energy consumption for NS and EW model-02

4.3 Thermal Energy Efficiency of Model-03

The results of the thermal energy efficiency for model-3 are presented in Table 11. It is seen again that the room electricity requirement and heating and DHW electricity do not vary for different window to wall ratios. When lighting electricity is considered, small variations are seen for different window to wall ratios. For cooling electricity, considerable variations are seen for different window to wall ratios. It is seen that with increasing window to wall ratios, the cooling requirement increases irrespective of the orientation. There is a large variation in the annual energy consumption for different window to wall ratios, which can be seen in Table 11 and Fig 13. Also with respect to orientation, North–South orientation is found to be better than the East–West orientation in improving the overall thermal efficiency of the building.

Table 11 Energy consumption results model-3

The cooling electricity values of building with North–South orientation are found to be 12576.8 kWh, 13367.2 kWh and 14411.0 kWh for the window to wall ratio of 30, 40 and 50%, respectively. Similarly, for East–West orientation the cooling electricity values are found to be 12883.7 kWh, 13483.0 kWh and 14416.1 kWh for the window to wall ratio of 30, 40 and 50%, respectively (Fig. 14).

Fig. 14
Temperature variations between inside and outside environments for model-3 by maintaining window to wall ratio.

Temperature variations between inside and outside environments for model-3

From Fig. 15, it is observed that inside temperature increases with increasing window to wall ratio for both North–South and East–West orientations for a given outside temperature. For the outside temperature of 36.6 ℃, the inside temperatures are found to be 34.5, 34.61, and 34.65 ℃ for North–South orientation and for window to wall ratio of 30, 40, and 50% respectively. Similarly, for East–West orientation the inside temperatures are found to be 33.75, 33.9, and 34.1 ℃ for window to wall ratio of 30, 40, and 50%, respectively. Daylight and sunlight dispersion map of model-03 is shown in Figs. 15, 16 and 17.

Fig. 15
A heatmap for Daylight inside the room of aspect ratio 1:2 and WWR30 percent is displayed.

Daylight inside the room (aspect ratio 1:2 and WWR30%)

Fig. 16
A heatmap for Daylight inside the room of aspect ratio 1:2 and WWR40 percent is displayed.

Daylight inside the room (aspect ratio 1:2 and WWR40%)

Fig. 17
A heatmap for Daylight inside the room of aspect ratio 1:2 and WWR50 percent is displayed.

Daylight inside the room (aspect ratio 1:2 and WWR50%)

Also, an overall comparison of electricity usage, annual energy consumption and temperature for different Aspect Ratios are presented in Figs. 18, 19 and 20 (Table 12).

Fig. 18
A bar graph depicts the cooling load for all the models is displayed for each aspect ratio of 1:1,1:1.5, 1:2. The bar with highest value of electricity in kilowatt-hour is N S 50 and E W 50

Cooling load for all the models

Fig. 19
A bar graph depicts annual energy consumption for all the models for each aspect ratio of 1:1,1:1.5, 1:2. Triple bar graphs plots room electricity, lighting, heating plus D H W electricity, cooling electricity.

Annual energy consumptions for all the models

Fig. 20
A bar graph depicts summary of temperature variations between inside and outside environments is shown for all the structures of model 1,2 and 3. The highest temperature for outside is 36.6 and inside is 34.75.

Summary of temperature variations between inside and outside environments

Table 12 Annual energy consumption for NE and EW model-03

5 Conclusion

  1. (1)

    In warm and humid climate conditions, the aspect ratio of 1:1, for a square building, energy consumption is 8–12% lesser in comparison with aspect ratio of 1:1.5.

  2. (2)

    Annual energy consumption for North–South orientation is found to be lesser as compared to the East–West orientation for window to wall ratio 30%, 40%, and 50% respectively. The trend remains same for increased aspect ratios of 1:1.5 and 1:2.

  3. (3)

    A window to wall ratio increases overall energy consumption of the building. However, the energy required for lighting decreases.

  4. (4)

    Every 10% increase in the window to wall ratio, the inside temperature increases by 0.25–0.5 ℃.

The study is conducted based on the analytical approach using a software tool. Hence, further study involving actual experimentation can be conducted to validate the obtained results.