Keywords

1 Introduction

In today’s world, stabilization of voltage in distribution network is a major concern specifically during loading conditions. Non-stable voltage conditions may lead to frequent faults, wear, and tear of equipment and devices. To overcome this shortcoming, voltage regulation is performed by the transformer using various methods. One of the method for regulating the voltage is by using tap-change regulating transformer during on-load conditions. Using thyristor for auxiliary switch solved the problem of arcing during tap changing. Recently, based on the concept of bidirectional thyristor, solid-state relays are used because of their non-contact feature while tap changing [1]. It enables the voltage regulation even during the voltage sag or swell associated with the distribution network of the microgrid [2]. The regulating transformer consists of two units, i.e., series and parallel units. The parallel units are given input by series units so as to have an injection of voltage into distribution transmission system [3]. Strict regulation of voltage is necessary because of the attached sensitive electronics. A properly regulated voltage permits for higher voltage drop in output of distribution network and can enhance the reduction of weights of cables connecting the network. It can be achieved by using (R-TRU) regulated transformer rectifier units [4]. High efficiency and improved power density is can also be achieved by partial energy regulation but adding the auxiliary transformer in isolated topology is not preferential as it do not give any advantage while improving power density [5]. It is also observed that polarity of any associated CT is should be reversed manually because the voltage regulation is severely influenced by protection calculation logic [6].

In first model, the detailed type model 1 represents the tap changing switches and characteristics of the transformer, while the phasor type model 2 uses current source for simulation. Model 1 is can be simulated in continuous or discrete mode of simulation, but model 2 is can be simulated in phasor mode of powergui only. This makes the model 2 much faster in simulation speed as compared to model 1. Model 2 is preferable to be used for studies of transient stability. Changes in phasor voltage and current can be observed using model 1. So in order to make system much faster, model 1 of first model is deleted and replaced by the model 2. After replacement, we receive a whole new different second model which makes the simulation of the model, even much faster.

2 Literature Review

Voltage regulation is very important to maintain stability of the buses of distribution network as frequent unregulated changes may lead to severe faults. The voltage regulation is given by Eqs. (1) and (2) as shown.

$$ V = \left( {V_s .R} \right)/\left( {R^2 + X^2 } \right)^{1/2} $$
(1)

The efficiency of the voltage regulation is 71% which very low and undesired by the customers. The impedance magnitude is related to R by the coefficient α, i.e., α = X/R.

$$ V = \left( {V_s .N} \right)/\left( {1 + \alpha^2 N^4 } \right)^{1/2} $$
(2)

For real solution of N, 0 < α < 0.5 corresponding to N positive solutions by 1 < N < \(\sqrt{2}\). So, maximum regulation is possible if the regulation transformer ratio is maximum with value of 1.414. Also, to compensate the losses, capacitor bank is also used as static compensator connected in parallel with the load [7]. The regulating capacity is enhanced by using new product, i.e., capacity regulating transformer during on-load conditions as is energy saving a specifically used by industrial entities and mining enterprises or at the places where there is a variation in seasonal load [8]. Different operating conditions are studied to understand the changing nature of power network by modeling of transformers. The types of regulating transformers include phase shifting (PST) and under-load tap changing (ULTC) transformer as they regulate the voltage without interfering with the load [9]. The structure of a UHV transformer is highly complex as compared to EHV transformers because of the complex interaction between the parts of transformer leading to complex differential current affecting the working of the differential relay [10]. With the developing economies, the demand of distribution transformers are increasing heavily as they are important equipment in distribution network [11]. So it is very important to build smart, intelligent, and practical strategies to develop the new types of transformer for different new applications with proper safety and speed of operation [12]. The mechanical contacts lead to shocks while connection and arcing during disconnection. The capacitor banks generates more loss due to fluctuations and deviation in voltage [13]. Strong internal resonances are produced due to the regulating winding while choosing the tap position leading to a building up of high resonant voltage in regulating winding thus leading to initiation of ground faults in feeding cable [14]. During fixed tap position, less on-state resistance is provided by mechanical contacts leading to less power loss; however, wear-less commutation is provided by the semiconductor devices while performing the tap change [15]. The generated arc during switching of the mechanical taps increases with increase in the capacity and load current of the regulating transformer. This leads to vaporization and decomposition of insulating oil to generate gas leading to a surge in insulating oil which is not a favorable circumstance under current required conditions [16]. These limitations should be overcome while using tap-change regulating transformer in near future by using IEEE draft standards for general requirements and test code for regulating transformers [17,18,19,20,21,22].

3 Simulation Model

Two MATLAB Simulink models are developed each containing model 1 and model 2, with the help of Gilbert Sybille (Hydro-Quebec) model. Both model 1, 2, and 3-Φ regulating transformer with rating 47 MVA, 120 kV/25 kV Wye/Delta. The first case of model containing model 1 and model 2 is shown in Fig. 1.

Fig. 1
figure 1

Detailed-Phasor model of regulating transformer (First case of model)

The tap changer is connected in the HV side, i.e., 120 kV side, and transformer regulates the voltage associated with the buses B2 and B4 at 25 kV side. Tap changer has nine switches from zero to eight. Tap zero is nominal position initially with 120 kV/25 kV ratio, and there are total eight different positions for changing the tap from one to eight number. To have positive/additive or negative/subtractive position of tap, reversing switch is added with the regulation winding to allow reverse connections. The voltage correction is possible for ±0.01875 p.u. of 25 kV at secondary side voltage or ±1.875% of 120 kV of nominal voltage. Hence, range of voltage variation allowed is 102–138 kV or 0.85–1.15 p.u. by tap change of 2.25 kV or 0.01875 p.u. per step. Voltage regulators receive input from buses B2 and B4 in the form of positive sequence voltage with reference voltage at 1.04 p.u. The factor by which transformers boost the voltage with initial position of tap set at −4 is 1.081. Depending upon the need of voltage regulation, the ‘Up’ or ‘Down’ outputs are generated by pulses using the tap changer to move the tap in upward or downward direction for effective voltage regulation. The range of voltage is should be (1.021 < V < 1.059) p.u. at buses B2 and B4 until the tap position does not reach +8 or −8 position. So the permissible error range is 0.01875 p.u. The second case of model containing model 1 and model 2 is shown in Fig. 2.

Fig. 2
figure 2

Phasor-Phasor model of regulating transformer (Second case of model)

4 Results and Discussion

The changing of tap is a quite slow process as it is a mechanical process. It almost takes four seconds to change the tap position. The simulation time is set to 120 s (2 min). At starting, the nominal voltage is being generated by the source, and programmable voltage source is implemented to change the voltage of the system to see the effect on the performance of the tap changer during loading condition of 120 kV system. Later, the voltage is decreased and increased progressively to 0.95 p.u. at time t = 10 s and 1.10 at time t = 50 s. Various curves/traces were observed and plotted as can be seen in the results above. Figures 3 and 4. display the position of tap of the tap changers during entire simulation of 120 s. Figures 5 and 6 display the positive sequence voltage superposition at bus B1 (120 kV), bus B2 (2 kV), and bus B4. Figures 7 and 8 display the reactive power, while Figs. 9 and 10 display the active powers of buses B1 and B3 on 120 kV voltage side. A total of 15 MVAR capacitor banks are used for voltage compensation. The voltage regulator regulated the voltage successfully using the tap changers during loading conditions.

Fig. 3
figure 3

Tap positions (first model) versus time

Fig. 4
figure 4

Tap positions (second model) versus time

Fig. 5
figure 5

Voltage variation at B1, B2, and B4 (first model) versus time

Fig. 6
figure 6

Voltage variation at B1, B2, and B4 (second model) versus time

Fig. 7
figure 7

Reactive power at B1 and B3 (first model) versus time

Fig. 8
figure 8

Reactive power at B1 and B3 (second model) versus time

Fig. 9
figure 9

Active power at B1 and B3 (first model) versus time

Fig. 10
figure 10

Active power at B1 and B3 (second model) versus time

5 Conclusion and Future Scope

In this paper, two models of distribution network are built among each of which, two regulating transformers are integrated through parallel connection using MATLAB Simulink blocks. After achieving the desired results and analyzing them, it was observed that second model with phasor-phasor type integrated model runs two and half times faster as compared to detailed-phasor type integrated model connected parallel to the distribution system. Algebraic loops are broken by using first-order transfer function due to which some glitches are observed in voltage during step down at time t = 10 s and during step up at time t = 50 s which are can be ignored. The tap positions of the tap changer are varied to stabilize the voltage at the buses in the permissible limit of voltage range in p.u. (1.021 < V < 1.059). When the internal voltage of the source decreases or increases, tap positions are varied in lower or upward direction to attain stability of voltage at the buses. Hence, voltage is regulated by regulating transformer at the different buses using on-load tap changer, and finally, the system stabilizes at voltage at 1.043 p.u. achieved at tap position +1. In future, on-load tap change phase-shifting transformer is can be built using phasor-phasor and detailed-phasor type MATLAB Simulink model.