Keywords

6.1 Introduction

Soil reinforcement, in various forms, has been rigorously applied in several civil engineering applications, such as foundations, pavements, slopes, retaining walls, and embankments. In past few decades, soil-reinforcements are evolved through several modifications, in terms of material (metallic to geosynthetics) and type (two-dimensional planar strip, and sheet to three-dimensional geocell). Geocell is a three-dimensional honeycombing confining system of interconnected cells, made of thermally welded or mechanically bonded polypropylene and polyethylene materials. Readymade geocells are available commercially, which are easy to handle and transport in collapsed form and can be expanded as mattress at site (Fig. 6.1). They can also be made in field using planar geotextiles or geogrids as per required dimensions.

Fig. 6.1
figure 1

Typical geometry of geocell (Yang et al. 2010)

The benefits of planar reinforcements are demonstrated by Binquet and Lee (1975), Akinmusuru and Akinbolade (1981), Fragaszy and Lawton (1984), Khing et al. (1994), Mandal and Sah (1992), Sitharam and Sireesh (2004), and Biswas et al. (2015). As compared to planar form, geocell is a comparatively new invention in soil reinforcement, devised by Webster and Watkins (1977). Different studies have revealed its superiority over the planar reinforcements and/or various traditional ground improvement techniques, such as heavy compaction, soil replacement, and chemical stabilization. The advantage of using geocells is established through several applications, such as foundations, embankments, bridge abutments, gravity walls and steepened slopes, roadways, and railways. (Rajagopal et al. 1999).

Schematic configuration of a typical geocell-reinforced foundation system is shown in Fig. 6.2. To improve the bearing capacity of foundation soil, geocells are placed directly over the native soft ground, and then, the pockets of geocell are filled, preferably, with granular materials like sand which have better drainage properties and reinforcement interaction behavior. Two types of soils can be noticed in the figure: The Soil Type-2 is the native soil underneath the reinforced-soil, and the Soil Type-1 is geocell-reinforced/unreinforced fill soil. D is the diameter of the footing. H is the thickness of geocell-reinforced sand layer overlying the clay subgrade, d is the geocell opening size, u is the depth of placement of geocell-mattress below the base of footing, b is the width of geocell-mattress, and h is the height of geocell-mattress. In practice, natural ground (subgrade) may exist at different strength levels, and situations may arise where reasonably strong soils also fail to meet the design requirements which need to be improved. In such situations, performance of reinforced foundations with different subgrade strengths should be considered. As can be seen in Fig. 6.1, the entire geocell-mattress is supported by the underlying subgrade. Hence, the behavior of geocell-reinforced foundation system is largely dependent on the underlying subgrade.

Fig. 6.2
figure 2

Schematic configuration of geocell-reinforced foundation systems (after Biswas et al. 2016)

In view of this, the main objective of this chapter is to provide insight into the performance of geocell-reinforced sand beds resting on clay subgrades of various strengths. Biswas et al. (2013, 2015, 2016), Biswas (2016), performed various physical model tests with soil subgrades of varied strengths, from very soft to stiff clay, varying the undrained shear strengths (cu) from 7 to 60 kPa overlain by geocell-reinforced sand mattresses of different heights. This chapter briefly describes the physical model tests conducted and presents the outcomes of model studies in terms of foundation reaction modulus, improvement factor, and percentage reduction in settlement.

6.2 Physical Model Tests

Model tests were carried out on a circular footing of 150 mm diameter (D) resting on 1 m × 1 m × 1 m foundation bed (test bed-cum loading frame assembly in the laboratory) having clay subgrades of different undrained shear strengths (cu), ranging from 7 to 60 kPa. Different series of laboratory model tests were performed on homogeneous and layered foundation systems. The layered systems were comprised of unreinforced and reinforced sand of varying layer thicknesses (H = 0.63D to 2.19D) overlying the clay subgrades. Two types of soils were used: a locally available clay soil for the subgrades and a river sand for the overlying layer. The geocell-reinforcements were formed using a biaxial geogrid through bodkin joints (with plastic dowel strips). A brief summary of the materials used and their properties are presented in Table 6.1.

Table 6.1 Material properties (Biswas 2016)

6.2.1 Preparation of Clay Bed/Subgrade

A calibration curve (Fig. 6.3a) depicting the variation of shear strength with water content of clay, for a uniform compaction effort, was developed through a series of trial tests (details were presented in Biswas et al. 2015). The clay soil was pulverized, air dried, and mixed with the required water (as per the calibration curve) to achieve the desired shear strength. The wet soil was kept in sealed containers for about a week to get moisture equilibrium. The prepared clay was placed in the test tank and compacted in layers of 50 mm thickness, until the desired height was reached. In order to verify the uniformity, clay samples from different locations and layers were collected by pressing mold into the clay beds. The shear strength values of the samples were determined through vane shear apparatus and found to be with ± 2% variation from the targeted shear strength values.

Fig. 6.3
figure 3

Calibration curves: a for clay and b for sand (after Biswas 2016)

6.2.2 Preparation of Sand Bed

Sand beds were prepared through raining technique. The raining device consisted of a large container and a long hollow pipe having a 60° inverted cone connected at its bottom. By trial, the height of fall was adjusted to attain the required density in both reinforced and unreinforced cases, as shown in Fig. 6.3b. It may be noticed that to attain a desired density, the raining heights for geocell-beds were more compared to unreinforced case as higher energy was required to compensate the geocell-wall-interruption. Relative density (Dr) of sand was maintained as 80% (γd = 15.83 kN/m3) throughout the experimental program.

6.2.3 Geocell

The geocell-mattresses were prepared with geogrid strips, cut from a full roll into required dimensions, and assembled in chevron pattern using ‘bodkin’ joints (Simac 1990; Caroll and Curtis 1990; Biswas et al. 2015). The HDPE geogrid, with 38 × 38 mm aperture size, was having tensile strength of 20 kN/m at 11% of axial strain. The bodkin-dowels were 3 mm thick and 6 mm wide plastic strips, made of low-density polypropylene. Maximum tensile strength of the bodkin joints used was found to be 3.3 kN/m at axial strain of 9%. To prepare the geocell-mattress, the transverse and longitudinal geogrid members were cut from a long roll and assembled in ‘chevron’ pattern using ‘bodkin’ joints (Fig. 6.4).

Fig. 6.4
figure 4

Photograph of typical geocell-mattress in chevron pattern

6.2.4 Test Setup

The test setup for the experimental program is shown in Fig. 6.5. Foundation beds were prepared in a steel tank of 1 m × 1 m × 1 m in dimension. The tank walls were well braced with heavy steel-sections (horizontally and vertically) to avoid lateral deformation, if any during testing. The test tank was provided with a loading frame for load application. The load was applied, by pushing the footing into the soil (at approximately 3 mm/min), through a hydraulic jack. The load applied was measured through a pre-calibrated proving ring, placed between hydraulic jack and footing. In order to ensure verticality of loading, a ball-bearing was positioned between proving ring and the footing. Responses of the model foundations were monitored at different loading stages by recording the deformations (heave or settlement) at different locations on the foundation surface through eight dial gauges (Dg1 to Dg8 shown in Fig. 6.5) of 0.01 mm accuracy. Two dial gauges (Dg4 and Dg5) were placed diagonally opposite on the footing, while the other six were placed on the soil surface, at distances of D, 2D, and 3D. The spindles of these dial gauges were rested over small plates of perspex sheet placed on the foundation surfaces. Observations were recorded at regular intervals of footing settlement (s) and continued till the failure of foundation or up to s/D = 24%.

Fig. 6.5
figure 5

Experimental setup (after Biswas et al. 2013)

6.2.5 Experimental Program

Tests were conducted on different homogeneous and layered configurations (unreinforced and reinforced) of foundations having varying clay subgrades under circular footing, as listed in Table 6.2. Pressure-settlement behavior of homogeneous sand and clay of varying strength was studied in series A. Unreinforced layered foundations with different thickness of sand layer (H/D = 0.63, 1.15, 1.67 and 2.19) over the clay subgrades of varying strength (cu = 7, 15, 30 and 60 kPa) were studied in series B. The response of geocell-reinforced foundations with different subgrades was examined in series C. In total, 37 model tests were performed under three different test series (Table 6.2). In the layered configurations, the subgrade strength (cu) and layer thicknesses (H) were varied keeping other parameters constant at their optimum (Biswas and Krishna 2017a).

Table 6.2 Details of model tests

6.3 Test Results

The results obtained are presented as bearing pressure-settlement responses and footing settlement vs surface deformation graphs. Parameters such as sand layer thickness (H), height (h), and width (b) of geocell-mattress, depth of sand cushion on top of geocell-mattress (u), and footing settlement (s) are normalized with respect to the footing diameter (D) and expressed as H/D, h/D, b/D, u/D, and s/D, respectively.

6.3.1 Bearing Pressure—Settlement Behavior

A typical comparison of pressure-settlement responses of unreinforced and geocell-reinforced foundation systems, for cu = 7 kPa, is presented in Fig. 6.6. Higher bearing pressures at larger footing settlements can be noticed. The geocell-reinforced bearing pressure is increased from 77 to 119 kPa, for the footing settlement (s/D) variation from 12 to 24% (at H = 0.63D). In similar foundation configurations, the variation of bearing pressures for unreinforced foundations was from 45 to 56 kPa. This indicates considerably high improvement in pressure values, for geocell-reinforced foundation systems as compared to unreinforced cases. Besides, it is seen that this improvement was increased with increasing settlement levels.

Fig. 6.6
figure 6

Typical pressure-settlement responses for unreinforced and geocell-reinforced foundations (different H/D) with cu = 7 kPa

The pressure-settlement responses showing the influence of subgrade strength on the performance of geocell-reinforced foundations (at H = 0.63D) are presented in Fig. 6.7. Substantial improvements, with higher bearing pressures for stiffer subgrades, can be noticed in the figure. The bearing pressures at s/D = 24% are 56, 140, 161, and 203 kPa for unreinforced layered systems having cu = 7, 15, 30, and 60 kPa, while bearing pressures were increased to about 119, 189, 238, and 413 kPa, respectively, with geocell-reinforcement.

Fig. 6.7
figure 7

Typical pressure-settlement responses for different clay subgrades with unreinforced and reinforced sand layer foundations with H = 0.63D (after Biswas 2016)

6.3.2 Surface Deformation—Settlement Behavior

A typical surface deformation profiles of homogeneous bed (cu = 15 kPa) at different levels of footing settlements (s/D) are presented in Fig. 6.8. The distance from the footing center ‘x’ is expressed in non-dimensional form as x/D. The surface settlement and heave are differentiated with ‘−’ and ‘+’ signs, respectively. It can be noticed that the surface deformations were mostly pronounced around the footing center (at x = D); while it was reduced as the distances increased (at x = 2D and 3D).

Fig. 6.8
figure 8

Surface deformation profile at different s/D for cu = 15 kPa

A typical variation of surface deformation (δ/D) with footing settlement (s/D) is shown in Fig. 6.9, for different foundation systems overlying clay subgrade of 7 kPa (cu) at H = 0.63D. It can be noticed that as compared to the unreinforced foundations, the geocell-reinforced system has shown higher settlement at x = D and more heaving at x = 2D and 3D. Such deformation profile is attributed to the deep beam action of geocell-mattress (Dash et al. 2003) which undergone sagging (causing settlement) around the footing center and hogging (causing heaving) away from the loading. However, the magnitude of deformations is dependent on thickness of geocell-mattress (h) and the strengths of the underlying subgrades (cu).

Fig. 6.9
figure 9

Variation of δ/D with s/D at x = D, 2D, and 3D for cu = 7 kPa (H = 0.63D)

Biswas et al. (2016) concluded that the sand layer thickness, H = 1.15D has better performance among the performed four different sand layer thickness of H/D = 0.63, 1.15, 1.67, and 2.19. The geocell-reinforced layered foundation has higher bearing capacity with reduced settlement compared to the unreinforced layered foundation. The beneficial effect was attributed to reinforcing action namely pocket all round confinement provided by geocell due to its cellular structure (Dash et al. 2003) and the interface frictional resistance from adjacent cells (Pokharel et al. 2010; Biswas et al. 2016). Besides, stiffness of geocell plays vital role in providing the degree of improvement of reinforced layer (Bathurst and Rajagopal 1993).

6.4 Interpretations of the Test Results

The test results obtained are analyzed and discussed in terms of the interpreted values, as foundation reaction modulus, improvement factor, and percentage reduction in settlement values for different foundation configurations.

6.4.1 Foundation Reaction Modulus, kf

The foundation reaction modulus (kf) is the secant modulus of the foundation system corresponding to a given settlement (slope of the line joining the origin to any point on pressure-settlement curve at the given settlement level). kf values for model foundations with different configurations at different settlement levels were evaluated and presented herein.

Figure 6.10 presents the variation of kf values with footing settlement (s/D) for different subgrades (cu) and different foundation configurations (for H = 1.15D). In general, the figure indicates that kf values decrease nonlinearly with increase in settlement levels for unreinforced foundations. A steep decrease of kf in between 2 and 6% of s/D is followed by gradual reduction till the maximum level of settlements (s/D = 24%). This behavior can be related to the surface deformation behavior of the foundation system. Biswas and Krishna (2017b) reported negligible surface deformation at initial settlement levels (s/D < 6%) and from thereon the surface deformations increased with footing load till the end of test. However, in the case of reinforced foundations, the introduction of geocell-reinforcement enhanced the reaction modulus values significantly in comparison with the corresponding values for unreinforced (homogeneous and layered) foundations as shown in Fig. 6.10. For geocell-reinforced systems, the reduction in kf with s/D is fairly linear. In this case, geocell-pockets completely arrest the shearing of sand from footing bottom and cut the potential failure planes to force it deeper into the foundation beds making the geocell-sand bed as an elastic coherent layer. Besides, as reported by Biswas et al. (2013), the deformations at foundation surfaces also satisfy the confinement effect indicating significant reduction in surface heaving. Figure 6.11 shows the variation of kf values with subgrade strengths (cu) for different foundation configurations at different settlement levels (s/D = 2, 6 and 12%). It is to be noticed that the foundation reaction modulus increases for subgrade strength for any settlement level (s/D). In general, higher kf values are found for superior foundation configurations, i.e., geocell-reinforced > unreinforced layered > homogeneous clay.

Fig. 6.10
figure 10

Variation of kf values with footing settlement (s/D) for different subgrades (cu) and foundation configurations (with H = 1.15D)

Fig. 6.11
figure 11

Variation of kf values with subgrade strength at s/D = 2, 6 and 12% for different foundation configurations (with H = 1.15D)

6.4.2 Improvement Factor, If

The ratio of bearing pressure of layered foundation to that of homogeneous clay bed foundation, at similar level of footing settlement, is defined as improvement factor (If). Three improvement factors, Ifs (Eq. 6.1), Ifsgc (Eq. 6.2), and Ifgs (Eq. 6.3), to represent the improvement of the geocell-reinforced foundation with respect to homogeneous clay and unreinforced layered foundation, are evaluated (refer Fig. 6.12) for different foundations at different settlement levels. The improvement factors evaluated for different foundation configurations are summarized in Table 6.3.

Fig. 6.12
figure 12

Definition sketch of calculation of improvement factors

Table 6.3 Summary of bearing pressure improvement factors
$$I_{\text{fs}} = \frac{{{\text{Bearing pressure of unreinforced layered foundations at}}\frac{{s_{\text{o}} }}{D}\left( { = q_{\text{s}} } \right)}}{{{\text{Bearing pressure of homogeneous clay beds at }}\frac{{s_{\text{o}} }}{D}\left( { = q_{\text{c}} } \right)}} .$$
(6.1)
$$I_{\text{fsgc}} = \frac{{{\text{Bearing pressure of geocell}} - {\text{reinforced foundations at }}\frac{{s_{\text{o}} }}{D}\left( { = q_{\text{r}} } \right)}}{{{\text{Bearing pressure of homogeneous clay beds at }}\frac{{s_{\text{o}} }}{D} \left( { = q_{\text{c}} } \right)}}$$
(6.2)
$$I_{\text{fgc}} = \frac{{{\text{Bearing pressure of geocell}} - {\text{reinforced foundations at}}\frac{{s_{\text{o}} }}{D} \left( { = q_{\text{r}} } \right)}}{{{\text{Bearing pressure of unreinforced layered foundations at }}\frac{{s_{\text{o}} }}{D} \left( { = q_{\text{s}} } \right)}}$$
(6.3)

Variations of improvement factors, Ifsgc, with footing settlement, for different layered configurations on very soft clay subgrade (cu = 7 kPa), are presented in Fig. 6.13. The figure also shows the improvement factors, Ifs, obtained for the unreinforced layered configurations. It can be observed that the improvement factors, Ifsgc and Ifs, are increased with increasing footing settlement. Variation of Ifsgc as 3.38–5.56 can be noted with footing settlement (s/D) in the range of 6–24%, for cu = 7 kPa at H = 1.15D, while the corresponding variation in Ifs is 1.35–1.72. A very high improvement factor of 11.6 is observed for cu = 7 kPa, for the thickest geocell-mattress of h = 2.09D (H = 2.19D), at the largest settlement level tested (s/D = 24%). This higher improvement in bearing pressure responses is contributed by the geocell-reinforcement.

Fig. 6.13
figure 13

Variation of Ifs and Ifsgc with s/D for cu = 7 kPa

Variations of Ifgc with footing settlement for different subgrades (cu = 7, 15, 30, and 60 kPa) are presented in Fig. 6.14, for two different layer thicknesses, such as H = 0.63D and 1.15D. It can be noticed that the variation of Ifgc, in Fig. 6.14, is not very consistent for all subgrades and for the layer thickness variations. However, in most of the cases, it was found increasing with settlement, showing more geocell contribution at higher strain.

Fig. 6.14
figure 14

Variation of Ifgc with s/D for different cu at H = 0.63 and 1.15D

Variations in improvement factors (Ifs and Ifsgc) for different subgrades (cu) with varying layer thicknesses (H/D) are presented in Fig. 6.15 (at 12% of s/D). It is observed that the improvement factors are decreased with the increase in subgrade strength. At H = 2.19D, the improvement factor Ifs (dotted lines) is varied from 4.45 to 0.82 as the subgrade strength (cu) increased from 7 to 60 kPa, while with geocell-reinforcement in similar condition, the Ifsgc variation is 6.45–1.78. However, at H = 0.63D, for both the foundation systems, the improvement factors (Ifs and Ifsgc) were greater for the subgrade having cu = 15 kPa. The improvement factor, Ifs, was found as 2.29 compared to 1.45 (for cu = 7 kPa), 1.5 (for cu = 30 kPa), and 0.82 (for cu = 60 kPa). Similarly, for 15 kPa, the Ifsgc was 2.86 compared to 2.45, 1.71, and 1.60, for cu = 7, 30, and 60 kPa, respectively. Due to the inclusion of geocell-reinforcements, the shearing of sand layer was arrested, and geocell-sand layer behaved like semi-rigid slab to increase the overall bearing capacity higher than the unreinforced layer configuration (even higher that the corresponding homogenous clay responses).

Fig. 6.15
figure 15

Variation of Ifs and Ifsgc with cu for different H/D at s/D = 12%

6.4.3 Percentage Reduction in Settlement, PRS

The performance of geocell-reinforced foundations over clay beds of varying subgrade strength is also quantified with respect to reduction in footing settlements using a non-dimensional parameter described as “percentage reduction in settlement” (Sitharam et al. 2007). Referring Fig. 6.16, if so be the settlement of homogeneous beds and sr be the settlement of geocell-reinforced foundation at a given pressure value qo (corresponding to so = 2, 6, 12, 18, and 24% of D), the percentage reduction in settlements (PRS) can be expressed as Eq. 6.4.

Fig. 6.16
figure 16

Definition sketch for calculation of PRS

$${\text{PRS}} = \frac{{s_{\text{o}} - s_{\text{r}} }}{{s_{\text{o}} }} \times 100\%$$
(6.4)

Figure 6.17 shows the variation in PRS with respect to subgrade clay strength (cu) for different settlement levels (s/D%). In general, the figure shows a trend of increase in PRS value with increase in s/D (%). The behavior indicates that the beneficial effect of geocell-reinforcements (confinement, interfacial resistance, and acting as semi-rigid slab) increases with increase in footing settlement. However, the trend for variation in PRS with respect to subgrade strength (cu) is opposite as seen in case of s/D (%). The variation in PRS is decreased nonlinearly with increase in cu. Though the settlements are significantly reduced even for higher subgrade strength soils, for lower subgrade strength soils, the reduction is more. For example, PRS values for cu of 7 kPa ranged in between 60 and 95% for different settlement levels. The corresponding PRS values for cu of 60 kPa are in the range of 15–80%.

Fig. 6.17
figure 17

Variation of PRS for different cu at H = 1.15D

6.5 Conclusion

This article reported observations from physical model tests carried out on model circular footing resting on foundation beds of different configurations having clay subgrades of varying strengths underneath. The responses obtained clearly indicated that the subgrade strength, irrespective of presence of reinforcement, largely influences the foundation behavior. The unreinforced sand layer favors softer clay subgrades (cu ≤ 30 kPa), while it affected negatively on stiff clay of 60 kPa. In the case of reinforced foundations, the introduction of geocell-reinforcement enhanced the reaction modulus (kf) values significantly in comparison with corresponding values for unreinforced (homogeneous and layered) foundations. kf values decrease with increase in settlement levels. For a given settlement level, kf increased with increase in subgrade strength, indicating higher performance for clay subgrade with higher strength.

The reinforcements have positive impact on all clay subgrades; however, the degree of improvement, with reference to native subgrade soil capacity, reduced with increase in undrained strength of clay. The degree of improvement, both in terms of strength (Ifsgc or Ifgc) and settlement (PRS), with respect to homogeneous clay is considerably high in case of foundation with soft clay (cu = 7 kPa), while it was reduced with increase in subgrade strength. Though the settlements are significantly reduced even for higher subgrade strength soils, for lower subgrade strength soils, the reduction is more. Thus, depending on the observations, it is concluded that the use of geocell and/or layers of compacted unreinforced soil (sand) must be in accordance to native subgrade strength. The degree of improvement expected to be achieved (both in terms of increase in bearing pressure and reduction in settlement) from reinforcement shall be evaluated according to the subgrade shear strength.