Abstract
Advanced Static Var Compensators (ASVCs) are high power electronics based devices used to provide fast variable reactive power compensation to power networks. They should be properly controlled to ensure fast and continuous reactive power to meet a certain fluctuating load demand and enhance the transient stability of the power system. The effectiveness of these compensators depends on the choice of the control strategy.
In this paper, we deal with the application of the Internal Model Control technique (IMC) and the State Feedback Control (SFC) concept to adjust the ASVC Var flow with the ac transmission network. These controllers are evaluated under a variety of operating conditions where performances and robustness have been analyzed and compared to a conventional PI controller.
Simulation results in the case of a non linear model show that SFC and IMC controllers, suitable for real time implementation, lead to improved transient response and hence provide fast reactive power compensation to ac transmission networks.
Access provided by Autonomous University of Puebla. Download chapter PDF
Similar content being viewed by others
Keywords
32.1 Introduction
The configurations of static compensators of reactive power based on switched inverters are today the most used in electric current transmission systems. The apparition of high-powered electronic devises in the design of power electronic converters has resulted in a solid-state Var source with a more simple structure namely the Advanced Static Var Compensator (ASVC) [4, 6]. The ASVC uses a PWM controlled dc/ac Voltage-Source Inverter (VSI) with a capacitor as a dc power storage device.
The ASVC is connected in derivation that can operate in networks of transport as well as of distribution to generate or absorb reactive power, without using bank of condensers or inductors, in order to provide fast variable and continuous reactive power compensation following large, fluctuating load demands.
Power transmission performances with higher long line transmission capacity and transient stability are achieved by controlling the reactive current injected or absorbed from the transmission line. The effectiveness of these compensators depends mainly on the choice of the control strategy which allows greater control of the power flow in real time taking into account network condition changes and responding almost instantaneously to stability problems. Various control approaches have been proposed in the literature [1, 2, 5, 8] where conventional voltage regulation loops used are based principally on a proportional-integral (PI) controller. These produce satisfactory performance only for limited operating range conditions. In this paper, we consider the application of the Internal Model Control technique (IMC) and the State Feedback Control (SFC) concept to adjust the ASVC Var flow with the ac system. The performances of the closed loop control systems are analysed and the effectiveness of the ASVC proposed controllers under a variety of operating conditions are demonstrated and compared to a conventional PI controller.
32.2 Overview and Modeling of the ASVC
The basic ASVC scheme is illustrated in Fig. 32.1. The ASVC circuit consists of six-pulse VSI with a dc capacitor and a PWM modulator. Connection of the ASVC to the transmission line is via a coupling transformer where Rs and Ls are the coupling transformer active losses and leakage respectively as shown in the three-phase equivalent circuit of the ASVC connected to a transmission line of Fig. 32.2.
Basically, the ASVC supplies reactive power to the ac transmission system if the magnitude of the inverter voltage is greater than the ac terminal voltage. It draws reactive power from the ac transmission system if the magnitude of the ac terminal voltage is greater to the inverter voltage. Var exchange is zero when the two voltages are equal [7].
It is assumed that the source is a balanced sinusoidal three-phase voltage supply with frequency ω.
Applying d-q transform to the ac circuit and combining the dc circuit equation, the ASVC model is obtained as:
The modulation index (MI) relates the maximum phase voltage to the dc link voltage.
The state equation is non-linear with respect to the control variable α which is related to the phase difference between the source voltage and inverter output voltage. In the range of small values of α (|α| < 5°), the small signal equivalent state equations are expressed as:
The system input is the control variable deviation Δα and the output is the generated reactive power given by:
Hence the system transfer function is given by:
32.3 Control Scheme of the ASVC
32.3.1 Internal Model Controller
The overall closed loop control system is pictured in Fig. 32.3 and the basic architecture of a classical IMC is illustrated by Fig. 32.4 [3]. A system model is placed in parallel with the actual system. The difference is used to adjust the command signal. An attractive feature of IMC is that it produces an offset-free response even when the system is subjected to a constant disturbance.
With reference to Fig. 32.4, the control and output signal are expressed as:
If a perfect model is assumed (G(z) = Gm(z)) then the closed loop system is stable if the controller C(z) and the system are stable. However under mismatch conditions (G(z) ≠ Gm(z)), a low pass filter is introduced in the feedback loop to improve the controller robustness with respect to modeling errors.
The design filter has the following transfer function
In what follows β has been fixed to 0.002.
Since the controller is the inverse of the system model (i.e. C0(z) = Gm(z)−1) then Qc(z) = Q*(z) and consequently the inverse system model should be stable. Furthermore if C0(1) = Gm(1)−1 the controller produces an offset-free response.
With Ts = 0.005 s, the discrete-time transfer function of the system is obtained as:
By taking Gm(z) = G(z) then the poles and zeroes of Gm(z) are p1,2 = −0.407 ± j0.2943, p3 = 0.5404, and z1,2 = −0.5549 ± j0.5775.
Then, the controller transfer function is given by:
32.3.2 State Feedback Controller
The overall closed loop control system with SFC control technique is shown in Fig. 32.5 and the cascade control system of the state-feedback configuration is given in Fig. 32.6 [3]. The controlled variable y is compared with the set-point value r and the control error is fed back to an integrator. The former feedforward gain k1 is now the gain of the integrator. This configuration shows that the gain K in the internal closed-loop is a feedback parameter.
The basic principle of the designed system is to insert an integrator in the feed forward path between the error comparator and the process as shown in Fig. 32.7.
From this diagram we obtain:
We assume that the plant given by Eq. 32.9 is completely state controllable. The transfer function of the plant can be given by:
The system dynamics can be described by an equation that is combination of Eqs. 32.9 and 32.12.
Where
We shall design an asymptotically stable system such that x(∞), ξ(∞), and u(∞) approach constant values, respectively. Then, at steady state \( \dot{\xi} \)(∞) = 0, and we get y(∞) = r.
Where
32.4 State Space Method Control Applied to the ASVC System
The state space representation of the system becomes:
Where
Hence
The poles selected for a good dynamic response of the closed loop system are determined by the Ackermann algorithm where:
p1 = −500; p2 = −600; p3 = −700; p4 = −750.
Hence
We shall determine the necessary state feedback gain matrix K using the pole placement technique, where:
32.5 Results and Discussion
Simulations were performed under Matlab/Simulink environment with the following ASVC parameters:
The PI parameters are obtained using root locus design for a damping factor of 0.7 where the following controller gains are obtained: Kp = 7.5 × 10− 6 Ki = 2.5 × 10− 3.
The IMC and SFC controllers were evaluated under more realistic simulation condition when the ASVC devices were controlled by PWM control circuit.
Figure 32.8 shows the transient response in the case of IMC and SFC controllers based on the non-linear model of the ASVC. The Var command was varied from 10 Kvar (inductive) to −10 Kvar (capacitive) to swing the system from leading to lagging mode at time 0.2 s.
The results obtained show that by the IMC and the SFC controller lead to a faster transient response with a shorter settling time and with no overshoot. It can be observed also that the SFC control produces a better performance than IMC and PI control which demonstrates its robustness under model mismatch situations.
Figures 32.9 and 32.10 show the reactive power responses under IMC and SFC controllers compared to a PI controller and Figs. 32.11 and 32.12 show the current waveforms behavior. It is observed from Fig. 32.11 how the current injected into the transmission line swings instantaneously in response to a capacitive Var demand.
Figures 32.13 and 32.14 show the transient response of the dc-side voltage Vdc, and Id, Iq ac current components respectively with IMC and SFC controllers. We notice that the response is faster and smooth in tw case of SFC control.
32.6 Conclusion
Internal Model Control and State Feedback Control techniques applied to an advanced static var compensator were presented in this work. Performance and robustness of IMC and SFC have been evaluated and compared to a conventional PI controller.
Simulation results demonstrate that the proposed strategy is feasible, it can be concluded that SFC and IMC control lead to improved transient response and hence provide fast reactive power compensation to the ac transmission network. Also the SFC controller is better than the IMC controller and can be easily tuned and very suitable for real time experimental implementation.
References
Abbasian M (2009) Robust control of STATCOM based on sliding mode technique. International Conference on renewable energies and power
Benyamina M, Mazari B, Tahri A (2007) A comparative study of robust control for an ASVC-based Var flow compensation. Int Rev Electric Eng 2(5):681–686
Bouhamida M (2005) Power system stabilizer design based on robust control techniques. ACSE Journal of Automatic Control and System Engineering. 5(3)
Grunbaum R (1999) FACTS: les systèmes performants pour le transport flexible de l’énergie électrique. Revue ABB review 4:4–17
Morari M, Zafiriou E (1989) Robust process control. Prentice Hall, Englewood Cliffs, NJ
Qader MR (2006) Optimal location of advanced static VAR compensator (ASVC) applied to non-linear load model. Energy 31:1761–1768
Trabelsi M (2008) Modélisation et commande directe d’un convertisseur multi-niveau monophasé. Congrés jeunes chercheurs en génie électrique, France 08
Sato Y, Kataoka T (1993) State feedback control of current-type PWM AC-to-DC converters. IEEE Trans. on Industry Application 29(6):1090–1097
Author information
Authors and Affiliations
Corresponding author
Editor information
Editors and Affiliations
Nomenclature
Nomenclature
- ASVC:
-
Advanced static Var compensator
- IMC:
-
Internal model controller
- MI:
-
Modulation index
- SFC:
-
State feedback controller
- ω:
-
Supply frequency
- A:
-
n × n constant matrix
- B:
-
n × l constant matrix
- C:
-
l × n constant matrix
- Co(z):
-
Controller transfer function
- Cs:
-
Source capacitor
- F(z):
-
Filter transfer function
- G(z):
-
Discrete-time transfer function
- Ica Icb, Icc :
-
ASVC currents
- Is IL :
-
Source and load currents
- K:
-
Gain matrix K
- Kp Ki:
-
PI parameters
- Ls:
-
Source inductance
- r:
-
Reference input signal (step function scalar)
- Rs:
-
Source resistor
- s:
-
Laplace operator
- u:
-
Control signal (scalar)
- Vdc Idc :
-
dc-side voltage and current
- Vsa Vsb, Vsc :
-
Source voltages
- x:
-
State vector of the plant (n-vector)
- y:
-
Output signal (scalar)
- α:
-
Control variable
- Δα:
-
Control variable deviation
- ξ:
-
State variable
Rights and permissions
Copyright information
© 2014 Springer International Publishing Switzerland
About this chapter
Cite this chapter
Benyamina, M., Mazari, B. (2014). Robust Control Techniques of ASVC-Based Var Flow Compensation. In: Dincer, I., Midilli, A., Kucuk, H. (eds) Progress in Sustainable Energy Technologies Vol II. Springer, Cham. https://doi.org/10.1007/978-3-319-07977-6_32
Download citation
DOI: https://doi.org/10.1007/978-3-319-07977-6_32
Published:
Publisher Name: Springer, Cham
Print ISBN: 978-3-319-07976-9
Online ISBN: 978-3-319-07977-6
eBook Packages: EnergyEnergy (R0)