Introduction

There has been a growing increase in the amount of waste disposed in landfills and waste disposal systems as a result of increased global population and higher level of industrial activities (Guy et al 2000; Olagunju et al. 2017). Waste products are typically disposed in landfills and waste-disposal systems where they pose significant negative influences on public health and cause degradation of the environment (Martinho and Almeida 2006). In consequence of these negative effects, landfills and dumpsites must be located far from residential areas (Dolk et al. 1998). Certain landfills have their waste enclosed within them so as to prevent infiltration of rainfall or snow, which leads to the production of leachate (Lohva et al. 2008; Genelle et al. 2012). Leachate is the liquid formed from the decomposed waste, and it typically has high electrical conductivity as result of the dissolved salts within it (Yoon et al. 2002; Martinho and Almeida 2006). Leachate plumes have higher electrical conductivity than the surrounding pore waters; hence, such plumes can be detected using geophysical surveying methods such as vertical electrical sounding (VES) and electrical resistivity tomography (ERT) (Kamura 2002; Moreira et al 2014; Udosen and George 2018). Vertical electrical sounding and electrical resistivity tomography are geophysical techniques that reconstruct subsurface resistivity from current injected into the ground (Gautam and Biswas 2016; George et al. 2017; Udosen and Potthast 2018).

Vertical electrical soundings (VES) and electrical resistivity tomography (ERT) are non-invasive and quick methods of delineating leachate plumes within the subsurface (Naudet et al. 2004; Gallas et al. 2011, Akinola et al. 2018). Resistivity methods can also be used to determine the depth between the waste material and the underlying ground cover (Chambers et al. 2006; Leroux et al. 2007) and to monitor the rate at which leachate has re-circulated (Grellier et al. 2008; Clement et al. 2011). These resistivity methods measure apparent electrical resistivity, and they enable a fast mapping of the resistivity distribution within an area (Devaraj et al. 2018). The electrical resistivity distribution within an area is influenced by soil porosity, salinity, temperature, cementation and mineral content of subsurface materials (White et al. 2015).

The South-eastern part of Nigeria has numerous non-enclosed waste-disposal systems and these pose numerous aesthetic and public health problems. The solid waste within these waste-disposal systems decompose slowly over several years, sending a large volume of leachate and other environmental pollutants into underground aquifers. These non-enclosed waste-disposal systems lead to contamination of the aquifer; hence this work uses electrical resistivity methods which have been found very useful in investigating leachate contamination at waste-disposal sites (Cardarelli and Bernabini 1997; Aristodemou and Thomas-Betts 2000; Bernstone et al. 2000; Ahmed and Sulaiman, 2001; Gawande et al. 2003; Abu-Zeid et al. 2004; Guerin et al. 2004; Batayneh and Barjous 2005; Depountis et al. 2005; Martinho and Almeida 2006; Zume et al. 2006; Olagunju et al. 2017; Fatoba et al. 2020).

The waste-disposal site under investigation is located in Uyo metropolis in Akwa Ibom State and was created in 2016 as the central waste-disposal site for Uyo, the capital of Akwa Ibom State. Uyo metropolis has a population of approximately 2 million. A previous waste-disposal site located a few miles away from this new site had generated lots of complaints from nearby residents. Complaints ranged from pollution of groundwater resources, environmental degradation, destruction of farm land, and air pollution. Consequently, in 2016, the government proposed a move to relocate the waste disposal site to a new location, where it felt the direct impact on public health and the environment would be minimal. This research investigates this new site, a few years after its creation, to evaluate its influence on public health and environmental degradation. This work uses vertical electrical sounding and electrical resistivity tomography to evaluate leachate contamination on the site. It aims at determining the extent and depth of leachate intrusion within the subsurface and alerting policy makers on the public health impacts and environmental degradation as a result of leachate percolation within the study area. As earlier mentioned, resistivity surveying methods are extremely useful tools for monitoring the extent of leachate percolation through the landmass.

Setting of study area

The study area, located in South-eastern Nigeria, lies between Latitudes 5.03° N and 5.05° N and Longitudes 7.93° E and 7.95° E. The geologic map of the study area is shown in Fig. 1 and the location map is shown in Fig. 2. The area is drained by Imo River, Kwa Iboe River and Cross River together with their tributaries. The elevation of the area ranges between 42 and 57 m above sea level. The study area comprises sandstone, gravels with intercalations of clay, and sandy clay in certain locations. The waste materials are dumped in the valley beside the site. The area experiences two seasons: wet season (April–October) and dry season (November–March), while the average annual rainfall is about 3000 mm characterized by humid tropical climate. Geologically, the study area is underlain by Recent to Tertiary sediments belonging to the Benin Formation (Tertiary to Quaternary coastal plain sands) of Niger Delta. The Benin Formation, underlain by the paralic Agbada Formation, has sediments which comprise fluvial loose sands, clays and lignite streaks. The Benin Formation is the major aquiferous unit in the area and it comprises of fine, medium and coarse sands alternating with lignite and thin clay at some areas.

Fig. 1
figure 1

Geologic map of the study area

Fig. 2
figure 2

Map of the study area showing location of VES and ERT points. The VES points are denoted by red circles, while the ERT points are denoted by red circles

Methods

Leachate percolation was modeled with vertical electrical soundings (VES) and electrical resistivity tomography (ERT) to determine the penetration depth of resistivity signals in the conductive waste and to investigate the extent of leachate accumulations within the waste-disposal site.

The VES and ERT data were collected using an ABEM resistivity meter, the aim being to obtain the depth to target, the thickness of each subsurface layer and the respective subsurface resistivity. Since dumpsites are usually heterogeneous, both VES and ERT profiles had electrodes lined up adjacent and across the site to enable the full mapping of leachate percolation within the site.

The VES data were acquired with the Schlumberger array configuration due to Schlumberger array’s high sensitivity to vertical structures and greater depth of subsurface penetration. The ERT data were acquired with the Wenner array configuration due to Wenner array’s high sensitivity to horizontal structures, low sensitivity to geological noise, and strong signal strength, which is useful in areas with high background noise.

Five VES profiles were acquired in the study area. All VES profiles had lengths of 400 m each. Four electrodes were used to generate data for each profile: two current electrodes were used to inject current into the subsurface and two potential electrodes were used to measure the corresponding potentials. The minimum electrode spacing was 1 m and the maximum electrode spacing was 200 m. At an initial potential electrode spacing of 0.5 m, the current electrode spacing used was 2 m, then 3 m, then 4 m, and finally 6 m. At a potential electrode spacing of 1 m, the current electrode spacing used was 8 m, then 10 m, then 12 m, then 14 m, then 16 m, then 18 m and finally 20 m. At a potential electrode spacing of 2 m, the current electrode spacing used was 10 m, then 30 m, then 40 m, and finally 60 m. At a potential electrode spacing of 5 m, the current electrode spacing used was 80 m, then 100 m, then 120 m, and finally 160 m. At a potential electrode spacing of 20 m, the current electrode spacing used was 200 m, then 300 m, and finally 400 m. The reason for the progressive increment in the potential and current electrode spacing was to increase the depth of current penetration. The VES field data were then input into WINRESIST software to generate logarithmic models of apparent resistivity against half the spacing between the current electrodes (AB/2). These models are shown in Figs. 3, 4, 5, 6, 7.

Fig. 3
figure 3

Model of VES 1 profile line

Fig. 4
figure 4

Model of VES 2 profile line

Fig. 5
figure 5

Model of VES 3 profile line

Fig. 6
figure 6

Model of VES 4 profile line

Fig. 7
figure 7

Model of VES 5 profile line

Two ERT profiles were acquired in the study area. All profiles had lengths of 100 m each. Four electrodes were used: two current electrodes to inject current into the subsurface and two potential electrodes to measure the corresponding potential. The minimum electrode spacing was 5 m and the maximum electrode spacing was 35 m. Data acquired from the field survey were modeled with RES2DINV software from Geotomo to generate 2D models of the resistivity distribution within the subsurface. These models are shown in Figs. 8 and 9.

Fig. 8
figure 8

Model of ERT 1 profile line

Fig. 9
figure 9

Model of ERT 2 profile line

Results and discussion

Five VES profiles were acquired in the study area and with the use of WINRESIST software. One-dimensional models of resistivity were obtained for the VES profiles. The VES models generated from the WINRESIST software are indicated in Figs. 3, 4, 5, 6 and 7. Each VES model indicates the resistivity and thickness of each subsurface layer (see Table 1 for the summary of this data). The VES models indicate the presence of three geo-electric layers (overlying motley topsoil, coarse sand and fine sand) with the aquifer lying between the second and third layer.

Table 1 Table showing resistivity, thickness and depth information for each geo-electric layer

Two ERT profiles were acquired in the study area and with the use of RES2DINV software, two-dimensional models of resistivity were obtained for the ERT profiles. The ERT models generated from the RES2DINV software are indicated in Figs. 8 and 9. Each ERT model indicates the 2D image of the resistivity and thickness of the subsurface layers. Assessments of the ERT models show that the first subsurface layer (motley topsoil) has resistivity values ranging between 2.4 and 480 Ωm. The second layer (coarse sand) has resistivity values ranging between 120 and 3375 Ωm, and the third layer (fine sand) has resistivity values ranging between 19 and 4393 Ωm. The regions with anomalous low resistivity values are the leachate plumes (Yoon et al. 2002; Martinho and Almeida 2006). As earlier mentioned, leachate plumes have a higher electrical conductivity than the surrounding pore water due to the presence of dissolved salts within it. Hence, areas with anomalous values of high conductivity indicate the presence of leachate, and on the ERT models in Figs. 8 and 9, leachate is identified by high conductivity values (i.e., low resistivity values ranging from 0.5 to 6 Ωm) at about a depth range of 9 m. The ERT models show that the leachate is moving rapidly towards the aquifer. This is a worrisome situation as the sole potable water source in the area is ground water. The extent of leachate contamination is aggravated by the difference in topography between the waste disposal site and the groundwater body as the disposal site is located on a hill and hence, leachate will more easily drain into the groundwater system downstream. The leachate on this site results from the disposal of organic and inorganic matter on the site, which is characteristic of domestic and industrial waste deposited at this waste disposal site. The leachate plumes are indicated by anomalous zones of high conductivity. This has been confirmed by past work (e.g., Grellier 2004, 2007). In these past studies, temporal changes in resistivity were observed after injection of leachate into the subsurface. Zones with increased conductivity appeared at locations at which leachate was injected.

Given the known thicknesses and resistivity values of the study area’s lithology as obtained from the VES models generated in Figs. 3, 4, 5, 6, 7, it became possible to calculate the Dar-Zarrouk parameters, which are the longitudinal conductance S and the transverse resistance R. The longitudinal conductance \(S = \sum\limits_{n}^{i = 1} {\frac{{h_{i} }}{{\rho_{i} }}}\), where h is the thickness of the layers overlying the aquifer and ρa is the apparent resistivity of the layers overlying the aquifer layer. The longitudinal conductance defines areas with ground water potential. The transverse resistance \(T = \sum\limits_{n}^{i = 1} {h_{i} } \cdot \rho_{i}\) is also another parameter for defining areas with ground water potential.

Table 2 shows the results obtained from computation of the Dar-Zarrouk parameters and how these results have been used to indicate the protective capacity of the aquifer. Longitudinal conductance values ranging from 0.1 to 0.19 indicate weak protective capacity, values ranging from 0.2 to 0.69 indicate moderate protective capacity, and values ranging between 0.7 and 4.9 indicate good protective capacity while values less than 0.1 correspond to poor protective capacity (Oladapo and Akintorinwa 2007). Based on the longitudinal conductance values obtained from this site, the protective capacity of the aquifer ranges from good to poor.

Table 2 Computation of longitudinal conductance, transverse resistance, and reflection coefficient

The electrical resistivity reflection coefficient \(k = \frac{{\rho_{2} - \rho_{1} }}{{\rho_{2} + \rho_{1} }}\), which indicates how soil resistivity varies between the geoelectric layers was also computed (Table 2). This computation showed how resistivity varied between the first and second layers. The positive values of electrical resistivity reflection coefficient k obtained indicate that the resistivity values of the first layer are less than the resistivity values of the second layer. Negative values would have indicated that the resistivity of the first layer was greater than that of the second layer.

This work investigated leachate contamination resulting from deposition of organic and inorganic waste at waste-disposal site in South-eastern Nigeria. Waste disposal sites cause serious health hazards and environmental degradation, especially when such sites are unconfined. The interest in this work has been the aquifer, which is the sole water resource for people living around the area. The essence of the VES surveys (1D resistivity imaging) was to delineate and model the location of the aquifer and map out the litho-stratigraphic units within the area while the essence of the ERT surveys was to model the location and direction of the leachate plumes. Both methods, as combined as in this study, have successfully shown the extent and direction of leachate contamination on the site. Computations of the Dar-Zarrouk parameters have shown that the protective capacity of the aquifer is generally low, indicating that the study area has a very high rate of aquifer contamination.

Conclusions

This work set out to investigate migration of leachate within a contaminated waste-disposal site in South-east Nigeria with the use of vertical electrical sounding (VES) and electrical resistivity tomography (ERT). VES data were used to generate 1D models of the subsurface, and it indicated the presence of three subsurface layers, (motley sand, coarse sand and fine sand). The VES models show that the aquifer lies between the second and third layers. The ERT data was used to generate 2D models of the subsurface, and it indicated that leachate is very rapidly moving into the surrounding aquifer which lies between the second and third subsurface layer. This is alarming, being that the sole potable water source for residents in the region is groundwater. The ERT models indicate the presence of leachate plumes and its flow direction. It also shows that the leachate is migrating downward and will soon reach the water table to mix with the groundwater system. Given the generally poor protective capacity of the aquifer as computed from the Dar-Zarrouk parameters, this situation warrants urgent attention.

This work also shows that that integrated use of 1D and 2D surveys provided useful information about the electrical characteristics of the subsurface. Both VES and ERT surveys were able to describe both the depth and lateral boundary of the contaminant plumes, thereby providing useful information for the management and monitoring of the extent of contamination on the site. This confirms previous work (e.g., Yoon et al. 2002; Frid et al. 2008; Rosqvist et al. 2011; Olagunju et al. 2017; Fatoba et al. 2020). The resistivity surveys at our waste disposal site were conducted on a grid to determine the locations and boundaries of leachate contaminant plumes that arise from the presence of accumulated waste and to assess the characteristics and thickness of the underlying subsurface formation. Resistivity modeling is therefore, useful for mapping the subsurface resistivity structure as well as lateral changes in stratigraphy. ID and 2D surveys when used together, as it is done in this work, provide complementary information on how the subsurface resistivity is distributed. They also reveal the distribution of contaminant plumes and delineate the geo-stratigraphy of the study area.