1 Introduction

Ground-source heat pump (GSHP) systems utilize buried ground loops (i.e., geothermal heat exchangers) to transfer heat between the ground and a heat pump for heating and cooling of a building. The subsurface is generally an effective thermal source and sink because ground temperatures become relatively stable with increasing depth below ground surface (bgs) and nearly constant at 5 m bgs year round (Kusuda and Achenbach 1965; Williams and Gold 1976; Florides and Kalogirou 2007). In comparison to traditional heating, ventilation, and air conditioning (HVAC) systems, GSHP systems offer benefits of reduced greenhouse gas emissions, high reliability, low maintenance, and lower energy, operating, and life-cycle costs (Inalli and Esen 2005; Tarnawski et al. 2009; Congedo et al. 2012). Despite these advantages, however, the design of the ground loop may be highly conservative, which then may lead to high initial capital costs that continue to hinder consumer appeal and implementation.

For smaller heat load applications, such as residential and commercial heating and cooling, shallow vertical or horizontal ground loops are used. When a sufficient footprint is available, shallow horizontal ground loops are cost effective because trench installation equipment is widely available and inexpensive compared to borehole drilling. In horizontal configurations, the ground loop is typically buried 1–2 m bgs and a fluid (e.g., water) is circulated within the loop, transferring heat from the ground to the ground loop or vice versa. The second law of thermodynamics places constraints upon the direction of heat transfer to and from the ground loop. For example, in the winter, the ground loop extracts heat (i.e., heating mode) from the ground since the ground temperature is warmer than the air temperature. Conversely, in the summer, the ground loop rejects heat (i.e., cooling mode) to the ground since the ground temperature is cooler than the air temperature.

The design of a horizontal ground loop is complex and depends on numerous parameters that include the arrangement of the horizontal trenches, specifications of the heat pump (i.e., capacity, flow rate, electrical demand, and efficiency), thermal properties of the soil and heat exchanger pipe, fluid flow rate in the ground loop, ground temperature, and geographic climate. Within the past decade, a number of parametric studies using numerical modeling analyses have been conducted to predict the performance of horizontal ground loops. Demir et al. (2009) developed a numerical model to investigate surface climate effects on heat transfer through parallel horizontal pipes. Wu et al. (2010) used computational fluid dynamics (CFD) software to predict the thermal performance of horizontal slinky ground loops and discussed the effects of coil diameter and interval distance. Benazza et al. (2011) performed quasi three-dimensional numerical simulations of horizontal ground loops to investigate the effects of operation conditions, loop spacing, loop diameter, and soil thermal conductivity (λsoil). Congedo et al. (2012) also used CFD software to evaluate the effect of geometrical (e.g., loop diameter, pitch, and depth) and functional (e.g., fluid flow rate in loop and λsoil) parameters on straight, helical, and slinky horizontal ground loops. Additionally, Chong et al. (2012) used CFD software to evaluate the effects of loop diameter, loop pitch, and thermal properties of soil on the thermal performance of horizontal slinky heat exchangers. A common finding among these studies was that the λsoil surrounding the ground loop had a significant effect on the thermal performance of horizontal ground loops. Congedo et al. (2012) concluded that λsoil was the most important parameter for heat transfer performance of the GSHP system. However, a shared limitation in these studies was that constant and uniform values of λsoil were assumed for their simulations.

Soil thermal conductivity governs the rate of conductive heat flow through soil and is defined as the quantity of heat transfer through a unit area of soil in a unit of time under a unit temperature gradient. Using a constant value of λsoil in transient conditions is imprudent because λsoil can vary with soil composition, soil density, soil moisture content, and temperature (Farouki 1981; Salomone and Kovacs 1984; Woodward et al. 2013). For horizontal ground loops, variability of λsoil is primarily expected as a result of changing moisture conditions. Generally, horizontal ground loops are installed in a single type of backfill and a certain soil density can be achieved through compaction. During operation of the ground loop, the density of the backfill does not change significantly. Varying temperatures of the backfill are expected from operation of the ground loop as well as seasonal fluctuations. However, the range of temperatures around an operating ground loop is only a few degrees (Demir et al. 2009; Wu et al. 2010). Changes in λsoil as a function of temperature generally occur over wider temperature ranges (Smits et al. 2012). Spatial and temporal variations of soil moisture content are not as easily predicted due to the complex cycle of moisture migration mechanisms, including thermally induced moisture migration, groundwater table (GWT) fluctuations, and climatic variations. Therefore, a variable value of λsoil as a function of soil moisture would better characterize unsaturated soil conditions in horizontal ground loop modeling.

The thermal conductivity dryout curve (TCDC) for a soil defines the relationship between moisture content (gravimetric water content, volumetric water content, or degree of saturation) and thermal conductivity (λ), and thus quantifies the moisture-dependent thermal behavior of soil. The retention of water in unsaturated soil can be predicted from the soil–water characteristic curve (SWCC), which defines the relationship between moisture content and suction (ψ). Furthermore, to predict the rate of water movement, the SWCC can be used to estimate the hydraulic conductivity curve, which defines the relationship between moisture content and hydraulic conductivity (k). The TCDC and SWCC are characteristic functions for a given soil, and when coupled, govern the transport of heat and moisture. With various model estimation and experimental techniques available (e.g., Côté and Konrad 2005; Likos et al. 2012; Woodward et al. 2013; Fredlund and Xing 1994; Agus and Schanz 2005) as well as a growing base of literature with published values (e.g., Campbell et al. 1994; Leij et al. 1996; Smits et al. 2010; Krishnapillai and Ravichandran 2012), TCDCs and SWCCs are now relatively easy to obtain and are useful for modeling coupled heat and moisture flow.

In this study, coupled TCDCs and SWCCs were integrated in the modeling of coupled heat and moisture transfer present in unsaturated soil surrounding a shallow horizontal ground loop. Specifically, the significance of moisture migration on predicting values of in situ λsoil was evaluated. Values of λsoil predicted from backfill with experimentally measured TCDCs and SWCCs are compared with the conventional method of using conservative and constant λsoil. Moreover, the importance of selecting a value of λsoil is demonstrated by using simulation results to quantify changes in thermal performance and length of horizontal ground loop for a GSHP system using a heat pump with nominal 3-ton (10.55 kW) capacity and coefficient of performance (COP) of four.

2 Soil Properties

Three quartz-rich sands—hereby referred to as soil A, B, and C—were selected as backfill for the current simulations of horizontal ground loops. Quartz sands are favored for use as backfill due to their favorable thermal properties (λquartz = 8 W/mK > λfines = 2.9 W/mK > λwater = 0.6 W/mK ≫ λair = 0.024 W/mK). Grain-size distribution (ASTM D422-63), standard Proctor compaction (ASTM D698-12), and X-ray diffraction techniques were performed to determine physical characteristics of the soils, as shown in Table 1.

Table 1 Physical characteristics of selected backfill soils A, B, and C

The three soils were compacted to approximately 90 % maximum dry unit weight to determine TCDCs and SWCCs using the automated hanging column method outlined in Smits et al. (2010). The automated hanging column method can be used to simultaneously determine the TCDC and SWCC of coarse-grained soils through the continuous collection of data from a dielectric moisture content sensor, temperature probe, tensiometer, and dual-needle thermal probe embedded in the specimen. The TCDCs and SWCCs were obtained at room temperature (i.e., 21 °C) during a drying process as pore water was allowed to drain through specimens along an initial drainage path. The experimentally determined TCDCs and SWCCs of each soil in terms of degree of saturation (S) are shown in Fig. 1a, b, respectively. While TCDCs at elevated temperatures (e.g., >50 °C) can display nonmonotonic behavior with a maximum at low saturation (e.g., Smits et al. 2012), the monotonically decreasing TCDCs presented in Fig. 1a were implemented in the current simulations since relatively low temperatures (e.g., less <30 °C) were used.

Fig. 1
figure 1

a TCDCs and b SWCCs of backfill soils A, B, and C

A key feature on both the TCDC and SWCC is the residual saturation (arrows at the knee of the curves) in Fig. 1a, b. Knowledge of the residual saturation provides an indicator for thermal instability. In the TCDC, the residual saturation, which is also referred to as the critical saturation, defines the point at which incremental decreases in saturation result in a significant decreases in thermal conductivity. Likewise, in the SWCC, the residual saturation defines the point at which incremental decreases in saturation require much greater suctions. Moisture migration due to thermal and hydraulic gradients can create dry soil conditions around the ground loop and continued drying below the residual saturation results in significant reductions of λsoil. If the developed dry zone persistently inhibits dissipation of heat from the ground loop, a thermal runaway condition may ensue. As a preventative measure, a conservative estimate of λsoil usually corresponds to a value below the residual saturation. However, there is still a wide range of saturations (~0.3 < S < 1.0) where higher λsoil exists.

3 Simplified Heat Transfer Model

Heat transfer in the ground is challenging because the ground temperature gradients vary spatially and temporally. In this study, a simplified heat transfer model was used as a more manageable approach to estimate model input parameters and to approximate the length of ground loops based on predicted values of λsoil influenced by moisture migration mechanisms relevant to horizontal ground loops. By assuming isothermal boundary conditions at the ground loop and ground surface, a thermal resistance network involving a conduction shape factor for a horizontally buried cylinder is applicable. The thermal resistance approach is analogous to the Neher and McGrath (1957) method used to model heat transfer mechanisms in underground cable installations for calculating cable ampacity. An approximate length of ground loop for a given heat pump capacity and COP can be derived from an energy balance on the GSHP system and differential element shown in Fig. 2. The capacity of the heat pump was assumed to represent the required building load (i.e., energy demand).

Fig. 2
figure 2

a Simple GSHP system schematic and b ground loop differential element

Based on known values of the heat pump capacity (Qhp), heat pump efficiency (COP or energy efficiency ratio (EER)), fluid flow rate (mw), and entering water temperature (EWT = Tw,out), the heat exchanger load (Qhx) and leaving water temperature (LWT = Tw,in) can be determined by:

$$COP = \frac{power \, output}{power \, input} = \frac{{Q_{hp} }}{{Q_{hp} - Q_{hx} }}$$
(1)
$$EER = \frac{cooling \, energy \, output}{electrical \, energy \, input} = \frac{{Q_{hp} }}{{Q_{hx} - Q_{hp} }}$$
(2)
$$Q_{hx} = m_{w} c_{wp} \Delta T_{w}$$
(3)

where cwp is the specific heat capacity of the fluid at constant pressure and ΔTw is the temperature difference of the fluid (ΔTw = Tw,out − Tw,in = EWT − LWT). The rate of heat transferred per unit length between the heat exchanger fluid (Tw) and ground (Tg) can be determined by:

$$Q = \frac{{\left( {T_{g } - T_{w} } \right)}}{{R_{total} }}$$
(4)

Depending on whether the ground loop is used to extract or reject heat, Q may be positive (i.e., heating mode) or negative (i.e., cooling mode). If Tg is assumed to be the temperature at the ground surface, then the total thermal resistance (Rtotal) for a horizontal pipe with inner diameter (Di) and outer diameter (Do) buried at a certain depth (d) is the sum of resistances (i.e., inverse of conductivity) from fluid convection (Rconv), pipe conduction (Rpipe), and soil conduction (Rsoil):

$$R_{total} = R_{conv} + R_{pipe} + R_{soil}$$
(5)
$$R_{conv} = \frac{1}{{h_{w} \pi D_{i} }}$$
(6)
$$R_{pipe} = \frac{{\ln \left( {\frac{{D_{o} }}{{D_{i} }}} \right)}}{{2\pi \lambda_{pipe} }}$$
(7)
$$R_{soil} = \frac{1}{{SF \lambda_{soil} }}$$
(8)

In Eq. (6), the fluid properties necessary to determine the heat transfer coefficient (hw) are evaluated at the average fluid temperature (Tavg) since variations with temperature are not significant (Incropera et al. 2006). The Nusselt number (Nu) and Gnielinski correlation (Eq. 10) can be used to determine hw:

$$T_{avg} = \frac{{T_{w,in} + T_{w,out} }}{2}$$
(9)
$$N_{u} = \frac{{h_{w} D_{i} }}{{\lambda_{w} }} = \frac{{\left( {f/8} \right)\left( {\text{Re} - 1000} \right)P_{r} }}{{1 + 12.7\left( {f/8} \right)^{1/2} \left( {\Pr^{2/3} - 1} \right)}}$$
(10)
$$f = \left( {0.79\ln \left( {R_{e} } \right) - 1.64} \right)^{ - 2}$$
(11)

where λw is the thermal conductivity of the fluid, f is the Darcy friction factor, Re is the Reynolds number (i.e., ratio of inertial to viscous forces), and Pr is the Prandtl number (i.e., ratio of momentum to thermal diffusivity). The Gnielinski correlation is valid for 0.5 ≤ Pr ≤ 2,000 and 3,000 ≤ Re ≤ 5 × 106 (Incropera et al. 2006). For the design of a horizontal ground loop, the circulating fluid flow rate and pipe diameter are chosen to maintain turbulent flow (i.e., Re > 4,000) to enhance heat transfer. In Eq. (7), λpipe is the thermal conductivity of the heat exchanger pipe which is typically made of high-density polyethylene (HDPE). In Eq. (8), SF is the conduction shape factor for a horizontally buried cylinder between two defined temperatures (Incropera et al. 2006):

$$SF = \frac{2\pi }{{\ln \left[ {\left( {\frac{2d}{{D_{o} }}} \right) + \sqrt {\left( {\frac{2d}{{D_{o} }}} \right)^{2} - 1} } \right]}}$$
(12)

An energy balance on the differential element, where Qhx = Q, produces the differential heat transfer:

$$dQ = m_{w} c_{wp} dT_{w} = \frac{{\left( {T_{g } - T_{w} } \right)}}{{R_{total} }}dx$$
(13)

By separation of variables, integration, and application of boundary conditions shown in Fig. 2 (T = Tw,in at x = 0 and T = Tw,out at x = L), the length of ground loop (L) can be estimated by:

$$L = m_{w} c_{wp} R_{total} \ln \left[ {\frac{{\left( {T_{g} - T_{w,in} } \right)}}{{\left( {T_{g} - T_{w,out} } \right)}}} \right]$$
(14)

At constant mw and defined temperatures, Tg and ΔTw, Eq. (14) suggests λsoil (incorporated in Rtotal) is a key variable that influences the length of ground loop since λsoil can vary from coupled heat and moisture flow. However, in current state-of-practice, a conservative value of λsoil representative of the greatest soil resistance expected during long-term operation of the ground loop is often estimated or assumed for the ground formation into which the ground loop will be installed (ASHRAE 2007; Remund and Carda 2009). While designing conservatively for the worst-case scenario may appear as prudent, oversized ground loops may be inefficient and more costly to install and operate. Since λsoil is one of the most influential design parameters, an improved approach to simulate actual operating conditions is to predict variable values of λsoil that characterize unsaturated soil behavior.

4 Numerical Modeling of Coupled Heat and Moisture Flow

Coupled heat and moisture flow in unsaturated soil is a combination of conductive heat transfer and moisture transfer under hydraulic and temperature gradients. Thermal energy transferred by the movement of fluids (i.e., groundwater flow) can also contribute convective heat transfer. In the current study, the SVHeat and SVFlux programs of SoilVision® Systems’ SVOffice (a finite-element software package) were used to simulate coupled heat and moisture transfer in unsaturated soils around a shallow horizontal ground loop. The SVHeat program allowed for the input of soil TCDCs (i.e., Fig. 1a). Additionally, the SVFlux program allowed for the input of soil SWCCs (i.e., Fig. 1b) and was used to fit the SWCCs with the van Genuchten (1980) equation to estimate the hydraulic conductivity curve. Finite-element modeling was utilized to solve the complex and nonlinear governing equations for coupled heat and moisture flow. In SVHeat and SVFlux, moisture flow (i.e., liquid flow, vapor flow, and freezing) is governed by Eq. (15) and heat flow is governed by Eq. (17) (Thode and Zhang 2009):

$$\frac{\partial }{\partial y}\left[ {\left( {\frac{{\left( {k_{y}^{w} + k^{vd} } \right)}}{{\gamma_{w} }}} \right)\frac{{\partial u_{w} }}{\partial y} + k_{y}^{w} + \left( {\frac{{k^{vd} ( - u_{w} )}}{{\gamma_{w} (274.15 + T)}}} \right)\frac{\partial T}{\partial y}} \right] = \frac{{\partial \theta_{w} }}{\partial t} + \frac{{\rho_{i} }}{{\rho_{w} }}\frac{{\partial \theta_{wi} }}{\partial t}$$
(15)
$$k^{vd} = \gamma_{w} \frac{{\omega_{v} u_{v}^{soil} }}{{\rho_{w} R(T + 273.15)}}\frac{{D^{v*} }}{{\rho_{w} }}$$
(16)
$$\frac{\partial }{\partial y}\left[ {\left( {\frac{{\left( {L_{f} k_{y}^{w} + L_{v} k^{vd} } \right)}}{{\gamma_{w} }}} \right)\frac{{\partial u_{w} }}{\partial y} + \left( {\lambda + (L_{v} + L_{f} )\left( {\frac{{k^{vd} ( - u_{w} )}}{{\gamma_{w} (274.15 + T)}}} \right)} \right)\frac{\partial T}{\partial y} + L_{f} k_{y}^{w} } \right] - C_{w} q_{y}^{w} \frac{\partial T}{\partial y} = (C + L_{f} m_{2}^{i} )\frac{\partial T}{\partial t}$$
(17)

where k w y is hydraulic conductivity; k vd (Eq. 16) is water vapor conductivity by diffusion within the air phase; ω v is the molecular weight of water vapor; u soil v is soil–water vapor pressure; R is the universal gas constant; D v* is vapor diffusivity through soil; T is temperature; u w is pore water pressure; γ w is the unit weight of water; \(\theta_{w}\) is volumetric water content; \(\theta_{wi}\) is volumetric ice content; ρ w is water density; ρ i is ice density; y is elevation; t is time; L f is the mass latent heat of fusion of water; L v is the volumetric latent heat of water vaporization; C w is the volumetric heat capacity of water; q w y is water flow flux; C is the volumetric heat capacity of soil; and m i2 is the slope of the soil-freezing characteristic curve. In 2D modeling, partial derivative terms with respect to the x-axis (∂/∂x) are incorporated. Equations (15) and (17) are coupled through the ice content (\(\theta_{wi}\)) and vapor (k vd) terms.

5 Simulation Methodology

A two-dimensional (2D) cross-sectional modeling domain was evaluated to compare the thermal performance of a single horizontal ground loop in a two-pipe, trench configuration (Fig. 3). The 2D cross-section approach is reasonable if the cross-section is taken through the mid-section of the trench along the direction of fluid flow (Chiasson 2010). Furthermore, the 2D approach provides the benefit of reduced computational time.

Fig. 3
figure 3

Geometry, boundary conditions (BC), and finite-element mesh

The model domain was 8-m wide by 12-m deep with an initial groundwater table (GWT) located 2.5-m bgs. The size of the domain was assumed to be sufficiently large to encompass the expected thermally-disturbed area from operation of the single ground loop. Native soil was simulated as a sandy loam with thermal (λsoil = 0.8 W/mK) and hydraulic (Table 2) properties derived from Abu-Hamdeh and Reeder (2000) and Leij et al. (1996), respectively. Due to symmetry about the y-axis, symmetrical heat transfer in the ground was assumed and zero-flux boundary conditions (BC) were applied to the left and right side of the domain. The top surface boundary was defined by daily air temperature and precipitation. Approximated air temperature and precipitation data (Fig. 4a) were used to reduce computational time. The domain was assumed to be deep enough for the bottom boundary temperature to remain constant at 10 °C, which is the approximate groundwater temperature of northern continental United States. Furthermore, the bottom boundary was defined by varying total head values to simulate a fluctuating GWT (Fig. 4b). Since several databases were used to obtain climatic data, the precipitation and GWT data were not perfectly coupled. However, both precipitation and fluctuating GWT conditions were used to more accurately represent possible mechanisms for moisture migration.

Table 2 Hydraulic parameters of sandy loam and backfill soils
Fig. 4
figure 4

a Daily air temperature and precipitation used for top BC and b depth to GWT below ground surface for bottom BC

For a typical horizontal two-pipe configuration, a single 1-m-wide by 2-m-deep trench was centered within the model domain at the ground surface. Within the trench, two parallel SDR-11 (32-mm nominal diameter) HDPE pipes were buried 1.97-m deep and separated along the x-axis by 0.8 m. As part of the simplified heat transfer model, the HDPE pipes were modeled as constant temperature elements equivalent to the average of a design EWT suggested in ASHRAE (2007) and LWT calculated by Eq. (3). The average fluid temperature (e.g., Tavg = −2.84 °C in heating and Tavg = 29.37 °C in cooling for a heat pump with 3-ton capacity and COP of 4) was also used to specify thermophysical properties of the fluid and determine the convective heat transfer coefficient from forced convection in turbulent pipe flow (Eq. 10). The fluid was assumed to be a mixture of water and 20 % by volume propylene glycol antifreeze since design temperatures were expected to fall below the freezing point of water.

The backfill in the trench was simulated using soils A, B, and C. Two simulations were performed for each of the three backfill soils. One simulation used the soil’s experimentally measured TCDC and the other simulation used a conservative value of λsoil selected from between the dry and residual saturation of the soil’s TCDC. For the conservative analyses, a constant value of 0.7 W/mK was selected for soils A and B since both soils had similar values of λsoil below their residual saturation. A constant value of 0.8 W/mK was selected for soil C. Each simulation was performed for 365 days beginning on the 1st of January to encompass a heating mode followed by cooling mode and returning to heating mode. The ground loop was simulated to operate in the heating mode during measured heating degree days (e.g., 253 days when the average air temperature is greater than the reference temperature, Tref = 18.33 °C) or cooling mode during cooling degree days (e.g., 112 days when the average air temperature is less than Tref). For each simulation, the initial ground temperature at any depth (i.e., y) was approximated by a pure harmonic function (Hillel 1982):

$$T_{g} \left( {y,t} \right) = T_{a} + A_{o} e^{{\left( {y/\sqrt {2\alpha /\omega } } \right)}} \sin \left[ {\frac{{2\pi \left( {t - t_{o} } \right)}}{365} - \frac{y}{{\sqrt {2\alpha /\omega } }} - \frac{\pi }{2}} \right]$$
(18)

where Ta is the average ground temperature, Ao is the annual amplitude of the ground temperature, α is soil thermal diffusivity, ω is the annual angular frequency, t is time, and to is the time lag from an arbitrary starting date (usually January 1) to the occurrence of the minimum temperature in year. The initial hydraulic conditions were prescribed from the initial groundwater table location and corresponding partially saturated soil resulting from equilibrium capillary rise. The soil skeleton was assumed to be rigid and deformations were not considered. The SVFlux and SVHeat programs were fully coupled and performed simultaneously during simulation to determine transient moisture and temperature profiles of the ground.

6 Results

6.1 Moisture Variation

In the case of precipitation infiltration from the top of the trench and a fluctuating GWT near the bottom of the trench, soil moisture varied spatially and temporally. Figure 5a shows the volumetric water content (θw) time series for soil C at five observation points (0.67, 1.30, 1.98, 2.30, and 2.67 m bgs) along the y-axis (Fig. 3) through the center of the model domain. Similar results were also obtained for soils A and B. Figure 5b shows the θw-time series for all simulations at an observation point equivalent to the depth of the ground loop (1.98 m bgs) within the trench. For all soils, the trend of the θw-time series closely followed the increase and decrease of precipitation as well as rise and fall of the GWT (Fig. 4), suggesting that the amount of precipitation and location of GWT have a significant influence on in situ moisture conditions. The initial θw as well as ensuing θw from capillary effects were dictated by the soil SWCCs (Fig. 1b). For all simulations, the lowest observed θw (i.e., driest condition) was the residual water content of the soil.

Fig. 5
figure 5

Daily θw (a) at five observation points along the y-axis for simulation of soil C and (b) at 1.98 m bgs for all simulations. Curves labeled with λ represent simulations modeled with constant λsoil

6.2 Thermal Conductivity Variation

Figure 6a shows the λ-time series at the same five observation points for soil C as in Fig. 5a. Likewise, Fig. 6b shows the λ-time series at the same observation point for all simulations as in Fig. 5b. Since soils A and B had the same constant λsoil value for the conservative analysis, only one curve for both soils is shown in Fig. 6b. As dictated by the soil TCDCs (Fig. 1a), the spatial and temporal variation of λsoil followed the same trends as θw. Even though the 2.30 m and 2.67 m bgs observation points were closer to the GWT, the λsoil of the sandy loam was inherently lower than the λsoil from the TCDCs of the backfill at high saturation. The backfill closest to the ground loops was able to maintain relatively high λsoil due to precipitation infiltration and capillary rise effects from the GWT. As a consequence, the conservative and constant λsoil values were about half to a third of the λsoil values predicted in the simulations using the soil’s measured TCDC.

Fig. 6
figure 6

Daily λsoil (a) at five observation points spaced along the y-axis for simulation of soil C and (b) at 1.98 m bgs for all simulations. Curves labeled with λ represent simulations modeled with constant λsoil

6.3 Water Flux Variation

Figure 7 shows θw contour plots overlain with average water flux vectors for soil C at 120 days, towards the end of the first heating mode. Similar results were also obtained for soils A and B. The size of the vectors indicates the magnitude of water flux (i.e., larger arrow indicates greater water flux). The magnitude of water flux was less in models simulated with TCDCs (Fig. 7a) and greater in models simulated with a constant λsoil (Fig. 7b). The circular zones delineated by the water flux vectors around the ground loops suggest that water was not moving towards the ground loops but rather around the ground loops. Moreover, these circular zones suggest development of dry zone conditions since the θw contours show lower θw near the ground loops compared to adjacent soil outside the trench. Under continuous operation of the ground loop without resupply from moisture migration, excessive thermally induced moisture migration moving water away from the ground loops can continue to develop the dry zone. Drying conditions developed faster in models simulated with a constant λsoil since the constant values of λsoil were less than half of the λsoil predicted by using the TCDCs (Fig. 5b). As illustrated in comparing Fig. 7a, b, the θw contours show greater water retention in the trench for the simulation modeled with the TCDC compared to the simulation modeled with constant λsoil.

Fig. 7
figure 7

Water content contour profiles with moisture flux vectors after 120 days of simulation for soil C: a simulation modeled with TCDC and b simulation modeled with constant λsoil. Contour labels are in θw

6.4 Ground Temperature Variation

Figure 8 shows ground temperature contour plots for soil C at the end of 365 days when the simulation finished in the heating mode. Similar results were also obtained for soils A and B. In models simulated with TCDCs, the temperature contours were farther apart and the overall temperature profile was more widespread (e.g., 8 °C temperature contour extends lower in Fig. 8a than b), which was expected since heat transfer between the ground and ground loop is more effective at higher λsoil. In general, temperature contours in the trench also showed that the ground temperature closest to the ground loop was colder (and were also hotter in the cooling mode) in simulations modeled using a TCDC compared to simulations modeled using constant λsoil. At the end of 1 year of operation, the greatest difference between ground temperature contours obtained from models simulated with a TCDC versus a constant λsoil was about 0.2 m. Stable temperature contours near the bottom of the domain indicate the lower boundary temperature did have not a significant effect during the simulations.

Fig. 8
figure 8

Ground temperature contour profiles after 365 days of simulation for soil C: a simulation modeled with TCDC and b simulation modeled with constant λsoil. Contour labels are in °C

6.5 Length of Ground Loop

Approximate lengths of ground loop for the specified GSHP system were calculated using the input data in Table 3 and Eq. (14) for each simulation. To approximate the longest required length of ground loop, the lowest observed value of λsoil during each simulation was used (Table 4). Figure 9 presents the total length of ground loop required for each soil and indicates that the difference in λsoil had a significant effect. The length of the ground loop was 25–50 % longer for every soil simulated with constant λsoil rather than its TCDC. These simulation results demonstrate the importance of accurately modeling temporal and spatial moisture profiles to predict the thermal behavior of backfill surrounding horizontal ground loops.

Table 3 Fixed input parameters used to approximate length of ground loop in the heating mode
Table 4 Values of λsoil from simulation results used to approximate length of ground loop
Fig. 9
figure 9

Approximate length of ground loop for each simulated soil

7 Conclusion

Coupled TCDCs and SWCCs were used in horizontal ground loop modeling to predict the moisture-dependent behavior of λsoil. By using the soil’s SWCC and TCDC, λsoil was more accurately predicted by incorporating the effects of moisture migration. The SWCC provided determination of soil moisture variability in response to transient hydraulic and thermal gradients from climatic variations and ground loop operation. Furthermore, by coupling the TCDC, the thermal response of the surrounding soil and λsoil were determined. In the performed simulation scenarios, values of λsoil predicted from the soil’s TCDC were nearly twice the conservative and constant λsoil. As a consequence, using the soil’s TCDC rather than a conservative and constant value of λsoil also resulted in 25–50 % shorter loops.

In extremely arid or wet climates, where soil moisture is not expected to vary over a wide range, the current state of practice of selecting a constant λsoil representative of the dry or saturated condition may serve as a suitable design parameter for designing shallow horizontal GSHP systems. However, in regions where the soil is susceptible to moisture migration, the SWCC and TCDC of the backfill and native soil are useful to model actual conditions. These finite-element simulations showed that coupled SWCC and TCDC models are capable of capturing coupled heat and moisture flow in shallow horizontal ground loop applications and have potential value in improving the design of the ground loop. Performing these simulations for the design life of the GSHP system and using nonisothermal boundary conditions should be considered in the future for a more complete approach. Furthermore, the implementation of experimental testing (i.e., installing and monitoring temperature and moisture sensors at a shallow horizontal ground loop site) would provide validation and verification of the simulated models.