Keywords

1 Introduction

Modern power system is a complex network comprising of numerous generators, transmission lines, variety of loads and transformers. As a consequence of increasing power demand, some transmission lines are more loaded than was planned when they were built. With the increased loading of long transmission lines, the problem of transient stability after a major fault can become a transmission limiting factor [2].

This paper deals with the problem of static voltage stability in electrical networks. Basic notions of integrating FACTS to solve instability and voltage collapse have been presented.

The purpose of this work is to analyze the temporary stability of an electrical network containing photovoltaic generator and wind turbine in case of voltage fault in the presence of a FACTS device (SVC or STATCOM).

2 Studied System

The studied network is modeled thanks to the software PSAT, it is represented in Fig. 1. It consists of three conventional generators, slack bus, PV generator, a wind turbine, solar source, 14 transmission lines, 11 static loads and three transformers. The base power is 100 MVA and the base voltage is 13.8 kV.

Fig. 1.
figure 1

Studied network

3 Static Var Compensator (SVC)

Static VAR systems are applied by utilities in transmission applications for several purposes. The primary purpose is usually for rapid control of voltage at weak points in a network. Installations may be at the midpoint of transmission interconnections or at the line ends. Static VAR Compensators are shunting connected static generators/absorbers whose outputs are varied so as to control voltage of the electric power systems. In its simple form, SVC is connected as Fixed Capacitor Thyristor Controlled Reactor (FC-TCR) configuration as shown in Fig. 2 [3].

Fig. 2.
figure 2

Static VAR compensator of SVC [3].

The SVC is connected to a coupling transformer that is connected directly to the AC bus whose voltage is to be regulated. The effective reactance of the FC-TCR is varied by firing angle control of the anti-parallel thyristors. The firing angle can be controlled through a PI (Proportional + Integral) controller in such a way that the voltage of the bus, where the SVC is connected, is maintained at the reference value.

4 Static Synchronous Compensator (STATCOM)

The STATCOM is based on a solid state synchronous voltage source which generates a balanced set of three sinusoidal voltages at the fundamental frequency with rapidly controllable amplitude and phase angle. The configuration of a STATCOM is shown in Fig. 3.

Fig. 3.
figure 3

Static synchronous compensator (STATCOM) [3].

Basically it consists of a voltage source converter (VSC), a coupling transformer and a DC capacitor. Control of the reactive current and hence the susceptance presented to power system is possible by variation of the magnitude of output voltage (VVSC) with respect to bus voltage (VB) and thus operating the STATCOM in inductive region or capacitive region [3].

5 Network Test Settings

See Tables 1, 2, 3 and 4.

Table 1. Parameters of the wind turbine and Photovoltaic generator
Table 2. Generator parameters
Table 3. Parameters (a) SVC and (b) STATCOM
Table 4. Transformer parameters

6 Simulation Résultats

The simulation is run for four cases as follows:

6.1 Results Without Fault

In this case, we integrate a renewable source with four conventional generators. A very slight disturbance of the voltage at the bus levels (VBUS08–VBUS14) is shown in the figure below (Fig. 4).

Fig. 4.
figure 4

Tensions to the bus (Without default and FACTS)

6.2 Results with Voltage Fault

A three-phase fault has been applied on the bus 11 at time t = 3 s and deleted at time t = 3.25 s. This causes breakdowns in the lines. The simulation results are shown in Fig. 5. There is a voltage drop (short circuit) in the buses (4, 5, and 7 to 14) as shown in the figure below.

Fig. 5.
figure 5

Voltage to the bus a fault and without FACTS.

6.3 Simulation Results with Integration of the SVC

The same fault as in the previous paragraph is applied to the bus 11 in the presence of the SVC reactive energy compensator at the same bus. The simulation results are shown in Fig. 6. There is a marked improvement in the stability of voltage of the buses 7 to 14 (Fig. 7).

Fig. 6.
figure 6

Voltage to the bus a fault and SVC

Fig. 7.
figure 7

Voltage to the bus a fault and STATCOM

6.4 Simulation Results with Integration of the STATCOM

The same fault as in the previous paragraph on Bus 11 is applied in the presence of the STATCOM. The simulation results are shown in Fig. 6. There is a marked improvement and rapid return to stability of voltage of the buses 7 to 14.

7 Conclusion

In this work, we studied the stability of a network system containing a renewable energy sources in the presence of a fault. We used PSAT simulation tool running under MATLAB environment. After applying a three-phase fault on one bus, we found that the network became completely unstable. For this reason, we used compensation mechanism connected to the network. We proposed to install a flexible system (SVC and STATCOM). The results obtained show that this FACTS system gives good results for the improvement of the transient stability of the studied network with a slight superiority to STATCOM over SVC.