Introduction

For transporting bulk of electric power, high voltage direct current (HVDC) based transmission lines are used nowadays all around the globe. This is because of the advantages that are associated with this technology like fewer number of conductors, absence of skin effect, interconnection with alternating current (AC) grid, high efficiency, etc. Furthermore, remotely located renewable energy sources (wind, solar, hydro) can be linked to the main grid more efficiently and economically using this technology. HVDC transmission systems are matured over the years because of the tremendous improvements in power electronics converters [1, 2]. Several HVDC transmission lines are installed worldwide and are increasing with the passage of time [3]. Among these, one project is being installed between Lahore to Matiari by the National Transmission and Dispatch Company (NTDC) in Pakistan.

To implement HVDC technology for the transportation of electrical energy, a more reliable and long-lasting insulation system is required. The reason being higher degradation of insulators due to accumulation of more pollutants on their surfaces [4]. Different research studies have shown that the effect of DC voltage on the long-term performance of insulators is stronger than the AC voltage [5, 6]. The emergence of polymeric insulators for high voltage outdoor insulation has increased due to their lighter weight, high temperature withstands capability, good mechanical strength and dielectric properties as well as having high hydrophobicity [7, 8]. Among these, silicone rubber (SiR) materials are gaining popularity because their superior hydrophobicity resists the flow of leakage current and occurrence of the surface flashovers [9,10,11]. Moreover, SiR coatings are also used to enhance the hydrophobicity of ceramic insulators, facilitating thus the suppression of leakage current as well as improve the pollution performance [12,13,14,15].

Gubanski et al. studied different types of polymers like epoxy resin, RTV-SiR, HTV-SiR and EPDM under the influence of UV radiation. They also analyzed the surface partial discharge behavior of each sample and revealed that RTV- and HTV-SiR samples are more stable than the other polymers [16]. In another work, authors aged HTV-SiR under UV radiation and concluded that this polymer is suitable for many years for outdoor insulation [17]. Despite of all the advantages of SiR insulators, they are prone to degradation in the environment having multiple stresses. For their performance enhancement, different types of reinforcing fillers were incorporated in multiple research studies. As a result of the conducted analyses, it was observed that several factors including type, size, shape, orientation and concentration of fillers improve the properties/characteristics of base polymers [18, 19]. The inclusion of micro-sized fillers enhances the dielectric, mechanical, and thermal properties of insulators.

With the enlargement of micro-sized fillers, the inter-particle spacing increases which ultimately improves certain properties [20]. Moreover, the addition of a smaller concentration of nano-fillers is more effective than the larger concentration of micro-fillers [21]. To enhance the desired properties of polymeric insulators, various types of micro- and nano-sized fillers have been employed by different researchers [22,23,24,25]. The main objective is to select a filler that can improve more effectively the dielectric, thermal, mechanical and hydrophobic properties of base polymers. Silica is the most prominent filler for the enhancement of erosion performance, anti-tracking capability, thermal stability and mechanical properties [26,27,28,29]. It is shown that HTV-SiR containing nano-silica has better weather-resistant ability as compared to its micro-silica filled counterpart. Moreover, for the performance improvement of HTV-SiR, a mixture of both micro- and nano-sized fillers have also been investigated [30]. The conducted analysis revealed stronger resistant against aging of the hybrid composites than the materials filled with only one filler in the harsh environments such as that of Karachi, Pakistan.

Under AC applied voltage, the effect of multiple environmental stresses on the long-term aging behavior of various polymeric insulators has been studied by different researchers [31,32,33,34,35,36,37,38,39]. However, for DC stress, such data are insufficient for the implementation of polymeric composites in HVDC transmission lines. Although, some efforts of lab accelerated aging for 5000 h have been reported in [40,41,42]. Nevertheless, the data of long-term aging, particularly related to HTV-SiR filled with different compositions of nano/micro-silica is rather inadequate.

Having identified the research gap, this study is conducted to perform lab accelerated aging on HTV-SiR composites for a period of 5000 h in the simulated environment of Multan, Pakistan. The aging behavior was analyzed simultaneously under the application of both positive and negative DC voltages (bipolar DC) to investigate the polarity effect. For the experimentation, four types of silicone rubber samples having different proportions of micro-and nano-silica were prepared. The test samples were mounted in a specially designed weather chamber, where they were exposed to UV radiation, salt-fog, temperature, humidity and acid rain. Thereafter, the integrity of the samples was analyzed with the help of different characterization techniques. These included hydrophobicity classification, leakage current, mechanical and thermal analyses, water immersion tests and FTIR spectroscopy. Results of the conducted diagnosis are presented and discussed. Furthermore, a comparative assessment of the different studied scenarios is made.

The experiment

Preparation of test samples

The base material high-temperature vulcanized silicone rubber (HTV-SiR) was procured from the Dow Corning (USA) while, the micro/nano-silica fillers were bought from Sigma Aldrich (USA). The sizes of the nano-silica and micro-silica used were 12 nm and 5 µm, respectively. For the preparation of HTV-SiR composites, two methods used were compounding and mixing of materials. Firstly, the micro/nano-silica fillers were placed in a 100 ml solution of ethanol and then, they were stirred for 20 min mechanically. HTV-SiR was mixed with the fillers and ultrasonication was performed for 30 min to make a homogenous mixture. For the removal of ethanol, the mixture was heated at a temperature of 100 °C for one hour. Thereafter, a shear blender was used for the purpose of blending. The speed of blending was increased gradually to 150 rpm for the extraction of the lumps from the mixture and the blending time was kept as 20 min. Followed by this step, a hardener was mixed with the prepared solution. The mixture was then poured into hot steel molds to shape the samples that were 50 × 40 × 3 mm3 in size and 50 g in weight. The steel molds were placed at room temperature for 24 h to set the composites. For the experimentation, one unfilled HTV-SiR sample and three HTV-SiR composites were prepared. Specifications of the test samples are provided in Table 1.

Table 1 Specifications of the studied materials

Environmental chamber

An environmental chamber made up of acrylic sheet, schematically shown in Fig. 1, having dimensions of 2 × 1x1.5 m3 was developed for the aging analysis of fabricated composites. The multiple stresses applied on the test samples included DC voltage, UV radiation, temperature, salt-fog, humidity and acid rain. The former was obtained by rectifying secondary voltage of a center-tapped step-up transformer having a rating of 220 V/ 5 kV. The DC voltage with both positive and negative polarities was applied to the copper strips, holding the test sample. UV radiations were applied with the help of four UVA-340 fluorescent lamps. A Lutron light meter was used to check the required intensity of UV radiations in the chamber. For adjusting temperature in the chamber, four electrical heating rods of 500-watts were installed along with the sensor and controller. The latter was used to maintain the required temperature level. Moreover, a humidifier together with a sensor and controller was used to maintain the required humidity level. For salt-fog and acid rain, a nozzle was placed at an appropriate position in the chamber to spray all the samples after equal time intervals during the aging period. The acid rain was applied using an HCL solution having a pH value of 4.5. As per IEC 61,109, the samples were energized with a creepage distance of 30 mm/kV [43]. Two cycles, one for the winter and the other for summer were designed using the data taken from the Pakistan’s meteorological department to apply various stresses in the chamber. Details of the environmental factors constituting the weather cycles are given in Table 2.

Fig. 1
figure 1

Schematic illustration of the environmental chamber having arrangements for applying both polarities of DC voltage and various types of environmental stresses

Table 2 Summer and winter cycles of Multan designed using the data of Meteorological department of Pakistan

Diagnostic techniques

Hydrophobicity classification

To evaluate the performance of insulators, hydrophobicity analysis is very essential. Accumulative effects of the multiple stresses may influence surface characteristics of the samples, causing them to become hydrophilic. Therefore, hydrophobicity was analyzed after each cycle of the aging period with the help of the Swedish Transmission Research Institute (STRI) hydrophobicity classification guide [44].

According to the standard test procedure, samples were sprayed with the tap water for 20 s, followed by capturing of their high-quality images within 10 s. Thereafter, the images were compared with the standard images given in the STRI hydrophobicity guide. According to the guide, there are seven classes of hydrophobicity ranging from HC1 to HC7. HC1 being the most hydrophobic and HC7, the most hydrophilic [44].

Leakage current

To quantify the effect of multiple stresses on the performance of studied materials, leakage current analysis was performed. In the experimental arrangement, as high voltage was applied to energize each sample, therefore, an indirect method to measure leakage current we adopted. In the procedure followed, a resistor of 1 MΩ was connected in series with each sample and voltage drop was measured across it. A multimeter model UT-70B was used for this purpose and data were recorded after every cycle throughout the aging period.

Mechanical properties

To analyze the effect of applied stresses on mechanical properties of the test samples, tensile strength and elongation at break (EAB) were measured. Data were recorded both before and after exposing the materials to aging. For the measurements, Instron-4465 test machine was used. Moreover, samples were cut in a dumbbell-shaped structure following IS-3400 standard [45].

Thermal analysis

Thermal stability of the test samples both prior to and post multiple stress aging was analyzed using SDT-Q600 simultaneous TGA/DSC analyzer. Using this diagnostic technique, variation in the weight of samples with the rise in temperature was recorded. The range of temperature was kept from 25 to 900 ˚C with a constant increase of 10 ˚C per minute. Temperature-based derivative of the data was also taken to conduct differential thermogravimetric analysis (DTG) of the samples. Moreover, to avoid measurement errors, experiments were performed in a closed chamber filled with nitrogen, where its flow rate was kept as 50 ml min−1.

Water immersion tests

To check water repellency of the studied materials, two tests were performed both before and after the aging. These were 2-h boiling water test at 100 ˚C and 24-h water immersion test at 25 ˚C, conducted following ASTM-D570 [46, 47]. It is worth highlighting here that prior to each type of test, sample was cleaned with distilled water and then dried in a desiccator for a week time. Thereafter, water immersion tests were performed and weight of the sample was measured. From the obtained result, %age change in weight was calculated using the expression given as

$$M\left(t\right)=\left[\frac{{w}_{t}-{w}_{o}}{{w}_{o}}\right]\times 100$$

where M(t) represent %age absorption of water and wt and wo are masses of the sample after and before the test, respectively.

FTIR spectroscopy

FTIR spectroscopy was conducted to analyze changes in the molecular structure of the test samples due to multiple stress aging effects. For this purpose, FTIR spectrometer IRTracer-100 (Shimadzu) was used. Data showing absorption peaks vs. wavenumbers were recorded both before and after aging of the samples.

SEM analysis

SEM is a diagnostic technique used for studying surface topography to spot morphology of the materials. In the test procedure, high-energy electron beam scans the sample in a raster scanning pattern to produce SEM micrographs. Electron beam interacts with the surface atoms of the sample to produce signals, containing information of its topography and composition. In the present study, high grade SEM micrographs were captured using the FEI Quanta FEG-250 ESEM machine. Moreover, prior to the collection of data, gold was sputtered on the sample’s surface.

Results and discussion

Hydrophobicity classification

Collected data of hydrophobicity classification of all the test samples are shown in Fig. 2. The vertical axis represents the class of hydrophobicity, HC1 being the most hydrophobic and HC7, the most hydrophilic. Similarly, the horizontal axis shows the accelerated multi-stressed lab aging duration, where 672 h is equivalent to one field year. In the figure, values are shown at the multiple of 762 h as well as at 0 h (represent unaged sample) and after complete aging period (5000 h). As seen, in general, hydrophobicity for all the studied materials decreases with the increasing duration of aging. Moreover, the loss is dependent on the composition of the samples as well as on the polarity of the applied voltage. A slight recovery phenomenon can also be noticed after the aging period of 3360 h.

Fig. 2
figure 2

Hydrophobicity classification of the studied materials aged under (a) negative DC and (b) positive DC voltages

Analyzing the data for individual samples, it can be seen that for sample S1 (unfilled material), loss of hydrophobicity is the highest. On the other hand, among the additionally filled samples, S3 (doped with 15 wt.% micro-silica and 6 wt.% nano-silica) shows the lowest decrease in its hydrophobicity. While, the resistance against loss of hydrophobicity is relatively small for materials S2 and S4. Furthermore, it can be observed that degradation of the test samples under positive DC voltage is stronger as compared to the negative DC. For example, for sample S1 after 5000 h of aging, hydrophobicity class under positive DC is HC5, while under negative DC, it is HC4. Similar observations can also be noticed for the other samples as well.

Reasons for the loss of hydrophobicity can mainly be associated with the applied UV radiation and thermal stress in the environmental chamber, causing degradation of low molecular weights (LMWs) of the samples and also initiate oxidation processes on their surfaces. Moreover, the recovery phenomenon is due to the movement of LMWs from the bulk of materials toward their surfaces [48]. As far as polarity effect (stronger deterioration of the test samples under positive DC voltage than the negative DC) is concerned, it can be linked with the depolymerization and reduction of methyl group in the molecular structure of HTV-SiR [49].

Leakage current

Measured values of the leakage current for the studied materials are shown in Fig. 3. Inferring the data, it can be seen that all the values exist within the range of micro-amperes. Moreover, current increases with the increasing aging period, being dependent on the sample’s composition and polarity of the applied voltage. The only exception is after 3360 aging hours, where a slight decrease can be observed. Quantitatively, the highest change (in the total aging period) occurs for sample S1 (unfilled sample) and the lowest, for sample S3 (doped with 6 wt.% nano-silica and 15 wt.% micro-silica). Polarity effect is also noticeable. For example, after the aging period of 5000 h, leakage current for sample S1 under positive DC voltage is 8.12 μA. While, it is close to 7.5 μA under negative DC. Overall, the lowest current of 5.56 μA was obtained for sample S3 under negative DC voltage.

Fig. 3
figure 3

Leakage current measurements on HTV-SiR test samples aged under (a) negative DC and (b) positive DC voltages

The above-described results show that hybrid composites S2 and S3, reinforced with micro- and nano-sized silica filler, suppresses leakage current more effectively than the other studied samples. The reason being the relatively better interaction of filler particles with the base matrix. Moreover, variation of the leakage current is in accordance with the hydrophobicity classification of the test samples. The increasing trend is due to the degradation of low molecular weights and synergetic impact of multiple stresses. This may also be associated with breaking of C–H and Si–CH3 bonds in the molecular structure of HTV-SiR [9].

Polarity effect, showing stronger deterioration of test samples under positive DC stress than the negative DC, is in line with that reported in [6]. The reason being the quicker rate of charge/ion (occurs in air due to numerous background ionization processes as well as other reasons) deposition and accumulation of pollutants on the surface of the insulator [50]. Other possibility might be the electrolytic process (caused by the application of salt-fog and acid rain) in multi-stress aging, affecting surface condition more adversely under positive DC stress as compared to the negative DC as is also reported in [51].

Mechanical properties

The measured values of tensile strength and elongation at break (EAB) for the aged and unaged materials are presented in Figs. 4a and 5a, respectively. As seen, by reinforcing base matrix with the filler particles, its mechanical properties enhance. The relatively highest values (of both tensile strength and EAB) are obtained for hybrid composite S3 (filled with 6 wt.% nano-silica and 15 wt.% micro-silica) and the lowest, for unfilled sample S1. For the other two materials S2 and S4, the values are in between. Moreover, by exposing the test samples to multiple stresses, their mechanical properties deteriorate. The decline in tensile strength and EAB could be associated with the chain scissions, cause sample’s surface to lose its rubbery structure, and oxidation processes stimulated by the UV radiations and other stresses in the environmental chamber [52]. To quantify the decrease in tensile strength and EAB, %age values calculated with respect to the data obtained for unaged samples are presented in Figs. 4b and 5b, respectively. As seen, reduction is the minimum for hybrid composite S3 and the maximum for sample S1 (without any filler), regardless of the polarity of DC voltage. This can be attributed to the stronger interaction of hydrogen bonds of silica filler having silanol groups with the polymer matrix having OH groups [53]. Thus, movement of the main polymer chain is restricted, giving rise to the tensile strength of the studied samples.

Fig. 4
figure 4

Sub-figure (a) shows tensile strength of the unaged test samples and aged materials under bipolar DC voltage while, sub-figure (b) represents %age decrease in tensile strength of the aged HTV-SiR materials

Fig. 5
figure 5

a Elongation at break (%) of the unaged test samples and aged materials under bipolar DC voltage and b % decrease in elongation at break of the aged HTV-SiR materials

Likewise other measurements (described above), effect imposed by the positive DC stress is stronger than the negative DC. For example, after performing aging for 5000 h, the decrease in tensile strength for sample S1 under positive DC and negative DC voltages is 19.78% and 32.3%, respectively. While, the corresponding percentage decreases in EAB are 21.9% and 30.9. This trend is similar even for the other studied samples of HTV-SiR as well.

Thermal analysis

Thermographs of the studied materials before and after their exposure to environmental stresses, obtained using the procedure outlined in Sect. "Thermal Analysis", are shown in Fig. 6. Data of both the TGA and DTG are presented with different scales on the y-axis. Inferring TGA curves, it can be seen that weight of the test samples decreases with the rise in temperature. The maximum loss occurs in the temperature range of 410 ˚C to 550 ˚C. While, both below and above this range, the change is rather weak. The weight loss can mainly be associated with the breakage of methyl (CH3) group from the molecular structure of base polydimethylsiloxane (PDMS) [54].

Fig. 6
figure 6

TGA/DTG curves of the studied test samples. Sub-figures in the left column show data for the unaged samples. While, those in the middle and right columns represent measurements for the materials aged under negative DC and positive DC voltages, respectively. Also, all the figures are labeled with the sample notation

To quantify thermal stability of the test samples, temperature T10 at which the samples lose their 10% weight is given in Table 3. Moreover, the residual mass in %age, termed as percent yield, is also presented in the same table. As seen, the value of T10 is different for the studied materials being dependent on their composition. It is the lowest for unfilled sample S1 and the highest for HTV-SiR S3, containing 6 wt.% nano-silica and 15 wt.% micro-silica. Moreover, the change in T10 brought about by aging is also affected by the composition of materials and polarity of the applied voltage. For sample S1, variation is the maximum, while it is the minimum for sample S3. Polarity effect is also consistent with the results of above-described diagnostic measurements e.g., positive DC stress imposes more influence compared to the negative DC. As far as percent yield is concerned, behavior of the test samples is similar as noted for temperature T10. For instance, residual mass is more for sample S3 than the other materials both in its unaged and aged conditions. Also, weight loss is higher under positive DC voltage compared to the negative DC.

Table 3 Values of T10 and percent yield of the test samples before and after their exposure to aging for 5000 h

Analyzing DTG curves of the unaged materials (sub-figures in the left column), it can be observed that the slope representing weight loss per degree rise in temperature is the maximum (go beyond − 0.5) for unfilled sample S1 and the minimum (close to − 0.3) for hybrid composite S3. Interestingly, the latter also shows two peaks, which may be attributed to the removal of micro- and nano-fillers from the base matrix in two different ranges of temperature. Contrarily, S2 having relatively less amount of micro-silica exhibits only one peak. Curves of the remaining two samples S1 and S4 also displays one peak. Apart from the composition, DTG curves are also affected by the aging conditions of the materials as well as by the polarity of DC voltage.

The above-described variation in TGA/DTG curves with the rise in temperature can be linked with the material decomposition, evaporation of volatile species, chain scission, etc. [55]. Consequently, a reduction in cross-linking as well as in the van der Waal’s forces may occur particularly, at higher ambient temperature. Hence, from the TGA analysis, it is inferred that addition of hybrid filler (e.g., micro- and nano-silica) in certain proportion in the base material may affect its thermal characteristics considerably as validated by the results obtained for samples S3 and S2.

Water immersion tests

Results of the 2-h boiling water immersion test at 100 ˚C and 24-h water immersion test at 25 ˚C are summarized in Tables 4 and 5, respectively. The corresponding increase in %age weight of the test samples is presented in Tables 6 and 7. Analyzing the data (Table 6) for virgin samples, it can be seen that the mass uptake is dependent on their composition. It is the highest (0.68%) for sample S1 (without any additional filler) and the lowest (0.19%) for sample S3, reinforced with hybrid filler containing 6 wt.% nano-silica and 15 wt.% micro-silica. The mass uptake also increases by exposing materials to environmental aging. Furthermore, this increment is higher under positive DC stress compared to the negative DC. For instance, for sample S1, the percentage change under positive DC is 1.53, what that under negative DC is 1.25. Similar polarity effect can also be noticed for the other test samples as well.

Table 4 Results of the 2-h boiling water immersion test performed on the studied materials at 100 ˚C
Table 5 Results of the 24-h water immersion test performed on the studied materials at 25 ˚C
Table 6 Percentage increase in mass uptake during 2-h boiling water immersion test on the unaged samples and aged materials under bipolar DC voltage for 5000 h
Table 7 Percentage increase in mass uptake during 24-h water immersion test on the unaged samples and aged materials under bipolar DC voltage for 5000 h

Comparing percentage values in Table 6 with those in Table 7, it can be inferred that increase in mass uptake of the studied materials is more under 2-h boiling water immersion test than 24-h water immersion test. This tendency is the same regardless of the fact whether the samples are unaged or environmentally aged both under positive and negative DC stresses. The increase in sample’s weight due to water absorption at high temperature may be linked with the enhancement in pre-existing voids [56]. Contrarily, high ambient temperature may also cause more loss of the LMW molecules due to their diffusing into liquid. Consequently, weight of the sample may reduce as is reported in [57].

Increase in the water permeation and mass uptake of the studied materials due to environmental aging can be associated with the loss of hydrophobic properties, resulting in their more attraction for water absorption [58]. It may also be attributed to the pre-existing voids in the samples, offering free space to be occupied by water molecules, degrading thus their electrical performance [59]. Among all the test samples, the co-filled materials S2 and S3 offered the highest resistance to water absorption due to stronger Van der Waal’s forces and lower free volume on their surfaces.

FTIR spectroscopic analysis

FTIR spectra, displaying absorbance vs. wavenumbers, of the studied materials before and after their aging under multiple stresses is shown in Fig. 7. As seen, there exist four peaks corresponding to important functional groups, associated with the desired properties (electrical, mechanical, etc.) of polymeric materials [60], within different wavenumber ranges. Information about these is summarized in Table 8. Inferring the curves (in sub-figures) for virgin samples, it can be seen that maximum values of the absorption peaks are different, being dependent on their compositions. For instance, hybrid filled silicone rubber S3 attains the highest values, while unfilled sample S1 the lowest. For other two materials, these are in-between.

Fig. 7
figure 7

FTIR spectra of the virgin (unaged) samples and aged materials under multiple environmental stresses and bipolar DC voltage for 5000 h. Sub-figures are labeled with the sample notation

Table 8 Percentage decrease in absorption peaks of the functional groups of aged silicone rubbers for 5000 h calculated with respect to the data obtained for virgin samples

By comparing the curves of aged samples with those of the unaged, a decrease in the absorption peaks of all the chemical groups can be noticed. The reason being their degradation due to the impact of environmental and electrical stresses as reported in [61]. To quantify the %age decrease, values calculated with respect to the data obtained for virgin samples are presented in the last two columns of Table 8. As seen, the numbers (representing %age loss in absorption peak) are the highest for sample S1 (without any filler) and the lowest for sample S3 (filled with 6 wt.% nano-silica and 15 wt.% micro-silica) for all the functional groups. The loss in absorption peaks of other two materials S2 and S4 is in between those for samples S1 and S3. Moreover, among the four chemical groups, the highest decrease in absorption peaks is obtained for Si–CH3 and the lowest for Si–O–Si. As far as severity of the impact associated with the polarity of the applied voltage is concerned, it is more under positive DC stress than the negative DC. The above-described results indicated relatively better performance of the hybrid composites compared to the other studied formulations, which may be attributed to the fine silica particles dispersion, resulting in their strong interaction with the polymer base matrix [62].

SEM analysis

SEM micrographs of the test samples were taken at a magnification level of 1000 following the procedure outlined in Sect. "SEM Analysis". The collected data for virgin (unaged) materials are shown in Fig. 8. While, images of the environmentally aged samples under negative and positive DC voltages are displayed in Fig. 9 and Fig. 10, respectively. Analyzing micrographs of the unaged samples, fairly smooth surfaces can be observed. Even though, depending on the composition, there also exist signs of only moderate level of surface roughness due to addition of filler particles in the base matrix. On the other hand, samples exposed to different types of stresses in the environmental chamber for a duration of 5000 h exhibit noticeable surface degradation in the form of cracks and block like structures. These results in high surface roughness, the severity of which is affected by both the sample’s composition and polarity of the applied voltage. For instance, sample S1 (without any filler) under negative DC voltage displays cracks of shallow type over the entire surface. While, under positive DC voltage, it shows deep cracks and surface splits into discrete blocks. Other studied materials also show similar characteristics. Such irregularities can mainly be associated with the chain scission of base matrix and surface oxidation brought about by UV radiations, electrical stresses, high temperature and humidity [63, 64]. Among the investigated formulations, hybrid composite S3 (containing 6 wt.% nano-silica and 15 wt.% micro-silica) offered the highest resistance against surface degradation/roughness due to aging, showing thus good potential for high voltage outdoor applications.

Fig. 8
figure 8

SEM images of the unaged samples of HTV silicone rubber. Sub-figures are labeled with the sample notation

Fig. 9
figure 9

SEM images of the environmentally aged samples under negative DC voltage. Signs of degradation (e.g., cracks, block like structures) are indicated with the red and yellow circles

Fig. 10
figure 10

SEM images of the environmentally aged samples under positive DC voltage. Signs of degradation (e.g., cracks, block like structures) are indicated with the red and yellow circles

Conclusion

The present research work was conducted to assess performance of several types of composites, made of HTV-SiR and micro- and nano-sized silica filler. Following by preparation of the test samples, they were exposed to different environmental stresses/factors (temperature, humidity, UV radiation, acid rain and salt-fog) and bipolar DC voltage for a duration of 5000 h. Thereafter, the aged materials were diagnosed through different techniques to check their integrity in terms of electrical, mechanical, thermal, chemical and morphological properties as well as surface characteristics. Results of the performed measurements and allied analysis exhibited that severity of degradation is suppressed better by hybrid filled composites compared to the other investigated formulations. Moreover, impact created by the positive DC stress was found higher than the negative DC. Among the studied materials, HTV-SiR reinforced with 6 wt.% nano-silica and 15 wt.% micro-silica offered the strongest opposition to aging. Hence, this composition shows good potential for high voltage outdoor insulation in DC transmission lines with better performance and extended life.