1 Introduction

The ever-increasing demand for energy and the constant depletion of resources are driving a shift toward more efficient power generation. Combined cycle gas turbine (CCGT) power plants enhance the performance of simple gas turbine plants that utilize the fuel energy in an efficient way [5]. The efficiency of CCGT plants has been achieved by up to 64% [44]. Higher efficiency encompasses cheaper generation and fewer emissions. CCGT power plants are designed to run on specific operating conditions to fetch maximum efficiency. Ambient temperature is one of those significant operating conditions [6]. Environmental conditions, on the other hand, are not always advantageous. As the ambient air temperature rises, the performance of gas turbine power plants decreases [2]. It is essential to mitigate the adverse effects of high ambient air temperature by cooling it before intake to the air compressor [24]. Several researchers performed studies to observe the impact of ambient temperature on the performance of CCGT.

Erdem and Sevilgen [13] examined the electricity generation rate of a gas turbine (GT) power plant based on varying ambient temperatures corresponding to seven different climate conditions. The electricity generation rate is reduced by 2.87–0.71% in hot regions. The same is improved by 0.27–10.28% when the temperature of the inlet air is decreased to 10 °C. Along with the ambient temperature, the performance in terms of entropy generation rate and power output is also affected by the turbine inlet temperature (TIT) and pressure ratio. Choudhary and Sanjay [7] analyzed an integrated GT with a solid oxide fuel cell on the basis of these parameters (TIT and pressure ratio). And, when analyzing only the gas turbine component, the minimum entropy generation occurred at TIT of 1650 K and pressure ratio of 20. Rai et al. [34] investigated the impact of increasing ambient temperature on the power output of a CCGT plant consisting of two gas turbines and a steam turbine. The study revealed a decline in the overall and individual turbine power outputs. De Sa and Al Zubaidy [8] endorsed an empirical relationship for GT power production capacity when ambient temperature differs from ISO conditions (1.01 bar, 15 °C, and RH = 60%) [6]. For every 1 K above ISO that the ambient temperature went up, the GT lost 0.1% of its thermal efficiency and 1.47 MW of gross power output. Ehyaei et al. [10] modeled a CCGT thermodynamically and investigated the effect of inlet fogging. By performing optimization simultaneously, net power output, 1st law, and 2nd law efficiencies were reported to be increased by 17.24, 3.6, and 3.5%, respectively, for three months (June to August) of warm weather.

Mohapatra and Sanjay [30] compared two techniques of inlet air cooling (IAC), i.e., evaporative cooling and vapor compression cooling. In comparison with evaporative IAC, vapor compression IAC increased GT plant-specific work and thermal efficiency by 18.4 and 4.18%, respectively, while evaporative IAC increased these factors by 10.48 and 4.18%, respectively. Baakeem et al. [4] performed a comparative study of various IAC technologies coupled with a GT power plant in Riyadh. The optimized cooling capacity and air temperature were found to be 36 kW/m3s−1 and 8 °C, respectively. This study proposed a wet-cooled condenser coupled to a sub-cooling multistage compressor refrigeration system and a single-effect water-LiBr vapor absorption refrigeration system (VARS).

Since compressors utilize electricity from power plants as input, VARS is a well-known alternative to vapor compression refrigeration systems [35]. Researchers suggested an extensive range of inexpensive heat sources to drive a VARS, including Geothermal and solar energy. Kadam et al. [19] analyzed and compared thermo-economically the vapor compression refrigeration (VCR) system, VARS, and their hybrids for district cooling applications. It was discovered that VARS has the highest exergetic efficiency among all configurations. In addition, the integration of VARS with renewable energy resources was found to reduce both the environmental impact and the total cost. Matjanov [26] analyzed three heat source schemes for VARS: gas turbine exhaust, HRSG waste gases, and solar energy. The utilization of gas turbine waste heat in the absorption chiller was not preferable owing to the reduction in CHP efficiency. The most effective scheme was operating an absorption chiller on HRSG waste gases if the temperature of HRSG exhaust increased beyond 120 °C.

Singh [38] investigated a CCGT power plant integrated with an ammonia-water VARS. The study revealed that for the same fuel consumption, the total work output, 1st law efficiency, and exergy efficiency improved by 2.8, 1.193, and 1.133%, respectively. Mohapatra and Sanjay [31] analyzed a 3-pressure level HRSG integrated CCGT power plant equipped with an aqua ammonia VARS. At higher ambient temperatures, the total exergy destruction of the combined cycle was noticed to be higher. Also, the effect of ambient relative humidity was reported to be negligible on the performance of several components of the CCGT power plant. Meraj et al. [27] investigated the effect of increasing ambient temperatures on the single-effect water-LiBr VARS. It was reported that as ambient temperature rises, the coefficient of performance (COP) decreases. Elberry et al. [12] examined a dual-pressure HRSG combined cycle power plant incorporated with a single-effect water-LiBr absorption chiller. This study suggested that the HRSG exhaust gas temperature lower than 122 °C is the best scenario to employ a single effect VARS. However, Kaushik and Arora [20] reported the COP of a double-effect water absorption chiller is 1.6 to 1.7 times that of a single-effect absorption chiller. Further, Talukdar and Gogoi [42] compared a vapor power cycle equipped with single-effect and double-effect water-LiBr VARS for HPG temperatures ranging from 120 to 150 °C. The double-effect VARS had a superior COP (i.e., 1.411) than the single-effect system, which had a COP of 0.809. Similarly, the combined system’s exergetic efficiency was reported to be 35.23% for double-effect integration versus 35.19% for single-effect integration.

However, numerous works of literature discuss the study of CCGT performance improvement via inlet air cooling; several gaps have been identified but have not yet been addressed. In order to address these gaps, the present analysis aims to undertake a unique approach, hence showcasing its novelty. The gaps and attempts to address them are listed below:

  1. (1)

    The prevailing approach in previous studies by Singh [38] and Mohapatra and Sanjay [31] has predominantly involved the utilization of an Ammonia-water based VARS for cooling the inlet air. Despite the fact that water-LiBr VARS exhibits greater suitability from a performance standpoint. Hence, this analysis employs a water-LiBr-based absorption system.

  2. (2)

    Even though the HRSG exhaust temperature typically ranges between 120 and 160 °C [18], most studies have focused on single-effect VARS (water-LiBr or ammonia-water). None of the researchers have utilized water-LiBr double-effect VARS, despite the fact that it has a higher COP than a single-effect system and can exploit the HRSG exhaust energy more efficiently. Therefore, double-effect type VARS has been considered in the present analysis.

  3. (3)

    Moreover, the dual-pressure HRSG-based CCGT plant has been analyzed with the incorporation of double-effect water-LiBr VARS. Thus, the apprehended thermodynamic system is novel.

  4. (4)

    The integrated CCGT system itself has not yet been analyzed. In addition to analyzing this system thermodynamically, a comparison of exergy-based sustainability is made to calculate the improvement of the new system in comparison with the standalone CCGT plant.

In this study, a thorough 1st law analysis is performed, followed by a 2nd law analysis of the CCGT both with and without inlet air cooling. Moreover, the performance of these two scenarios has been compared to analyze the effects of ambient air temperature. Furthermore, several exergy-based sustainability indicators are computed, and their effects have been discussed.

2 System description

The system considered for analysis is a CCGT power plant, i.e., a conjunction of a gas turbine cycle (GTC) and a steam turbine cycle (STC). GTC comprises an air compressor, a combustion chamber, and a gas turbine. The air is compressed and then directed to the combustor section, where it is mixed with fuel (i.e., natural gas). The hot gas that results from the combustion chamber is guided toward the gas turbine, where it gets expanded. After expansion in the gas turbine, the exhaust flue gas from the gas turbine is further directed to STC. The STC includes a dual-pressure HRSG, a high-pressure steam turbine (HPST), a low-pressure steam turbine (LPST), a steam condenser, a deaerator, and feed water pumps. In the HRSG, heat exchange between the gas stream and the water stream is accomplished at two pressure levels. The economizer, evaporator, and superheater are intrinsic components of each pressure level. Steam from the high-pressure section expands in HPST up to lower pressure, and then it is mixed with low-pressure steam to further expand in LPST, as shown in Fig. 1. Wet steam at the outlet of LPST is condensed in the steam condenser. The condensate is then fed to a deaerator with the help of a condensate extraction pump (CEP).

Fig. 1
figure 1

Schematic diagram of CCGT with double-effect water-LiBr Absorption refrigeration system

In conjunction with CCGT, a double-effect water–LiBr VARS is employed to cool the compressor inlet air. It consists of an evaporator, absorber, condenser, high-pressure generator (HPG), and low-pressure generator (LPG). Two solution heat exchangers transfer heat from a hot solution to a cold solution. A compressor’s intake air is cooled by an inlet air cooler. As depicted in Fig. 1, the HRSG exhaust is utilized as a heat input in the HPG vapor absorption system via a heat exchanger.

In this study, the following assumptions are taken into account:

  1. (i)

    The kinetic and potential energies of each stream are neglected.

  2. (ii)

    Except for the combustion chamber, chemical exergy is neglected.

  3. (iii)

    The effectiveness of the condenser, absorber, and evaporator in VARS is assumed to be 100%.

  4. (iv)

    The gas leaving the HPG of VARS is maintained at a minimum temperature of 393 K.

2.1 Energy analysis

2.1.1 Air compressor

Air is fed to the compressor at a pressure, \({P}_{1}\) and temperature, \({T}_{1}\). The exit temperature, \({T}_{2}\) is a function of the polytropic efficiency of the compressor \(\left({\eta }_{\mathrm{AC}}\right)\), pressure ratio \(\left({r}_{p}\right)\) and specific heat ratio of air \(\left({\gamma }_{\mathrm{comp}}\right)\) as follows:

$$T_{2} = T_{1} \times \left( {1 + \frac{1}{{\eta_{{{\text{AC}}}} }}\left( {r_{p}^{{\frac{{\gamma_{{{\text{comp}}}} - 1}}{{\gamma_{{{\text{comp}}}} }}}} - 1} \right)} \right)$$
(1)

where \(\eta_{{{\text{AC}}}}\) is isentropic efficiency of air compressors as given below [22]:

$$\eta_{{{\text{AC}}}} = 0.91 - \frac{{r_{p} - 1}}{300}$$
(2)

The required work rate for the compressor is defined as the function of the air mass flow rate \(\left( {\dot{m}_{{\text{a}}} } \right)\), the specific heat \(\left( {C_{{\text{p,comp}}} } \right)\), temperature difference, and mechanical efficiency of the compressor \(\left( {\eta_{m} } \right)\).

$$\dot{W}_{C} = \frac{{\dot{m}_{a} C_{{\text{p,comp}}} \left( {T_{2} - T_{1} } \right)}}{{\eta_{m} }}$$
(3)

Here, \(C_{{\text{p,comp}}}\) [41] and \(\gamma_{{{\text{comp}}}}\) are determined as follows. Hence,

$$C_{{{\text{pa}}}} = 1.04841 - \left( {\frac{3.3871T}{{10^{4} }}} \right) + \left( {\frac{{9.4537T^{2} }}{{10^{7} }}} \right) - \left( {\frac{{5.49031T^{3} }}{{10^{10} }}} \right) + \left( {\frac{{7.9298T^{4} }}{{10^{14} }}} \right)$$
(4)
$$C_{{{\text{va}}}} = C_{{{\text{pa}}}} - 0.287$$
(5)
$$C_{{\text{p,vap}}} = 1.8778 - \left( {\frac{5.112T}{{10^{4} }}} \right) + \left( {\frac{{1.9157T^{2} }}{{10^{6} }}} \right) - \left( {\frac{{1.367T^{3} }}{{10^{9} }}} \right) + \left( {\frac{{3.723T^{4} }}{{10^{14} }}} \right)$$
(6)
$$C_{{\text{v,vap}}} = C_{{\text{p,vap}}} - 0.4614$$
(7)
$$C_{{\text{p,comp}}} = C_{{{\text{pa}}}} + \omega_{a,i} C_{{\text{p,vap}}}$$
(8)
$$C_{{\text{v,comp}}} = C_{{{\text{va}}}} + \omega_{a,i} C_{{\text{v,vap}}}$$
(9)
$$\gamma_{{{\text{comp}}}} = \frac{{C_{{\text{p,comp}}} }}{{C_{{\text{v,comp}}} }}$$
(10)

where \(C_{{\text{p,vap}}}\) and \(C_{{\text{v,vap}}}\) represent the specific heat of water vapor at constant pressure and constant volume, respectively. \(\omega_{a,i}\) represents the specific humidity of air at the compressor’s inlet.

2.1.2 Combustion chamber

The flue gas properties from the exit of the combustion chamber are a function of the lower heating value (LHV) of fuel, airflow rate, and efficiency of the combustor \(\left({\eta }_{\mathrm{CC}}\right)\). The following equation exhibits the energy balance in the combustion chamber:

$$\dot{m}_{a} C_{{{\text{pa}}}} T_{2} + \dot{m}_{f} \eta_{{{\text{CC}}}} .{\text{LHV}} = \left( {\dot{m}_{a} + \dot{m}_{f} } \right)C_{{{\text{pg}}}} T_{3}$$
(11)

The exit pressure is estimated by taking the pressure drop \(\left( {{\Delta }P_{{{\text{CC}}}} } \right)\) into account across the combustion chamber, represented as:

$$P_{3} = P_{2} \left( {1 - {\Delta }P_{{{\text{CC}}}} } \right)$$
(12)

Moreover, the properties of combustion products are evaluated via chemical and thermodynamic equilibrium. The chemical reaction of hydrocarbon fuel is considered, according to Ahmadi et al. [1], followed by its chemical equilibrium. Specific heat of combustion products is obtained from the standard theory of mixture by taking the specific heat of all constituents individually for different temperatures [43] as follows:

$$C_{{{\text{pg}}}} = f_{h} *\left[ {y_{1} .C_{p,1} + y_{2} .C_{p,2} + y_{3} .C_{p,3} \ldots \ldots y_{n} .C_{p,n} } \right]$$
(13)

where i = 1,2,3…represents the constituents and \({y}_{i}=\frac{{m}_{i}}{m}\)

\({f}_{h}\) is known as the humidity correction factor [31] and represented as

$$f_{h} = 1 + 0.05\varphi$$
(14)

where \(\varphi\) is relative humidity at the exit of the inlet air cooler.

2.1.3 Gas turbine

Similar to the compressor, the outlet temperature from the gas turbine is a function of the polytropic efficiency of the gas turbine \(\left( {{\upeta }_{{{\text{GT}}}} } \right)\), pressure ratio \(\left( {\frac{{P_{3} }}{{P_{4} }}} \right)\) across the gas turbine, and the specific heat ratio of the gas \(\left( {{\upgamma }_{{\text{g}}} } \right).\)

$$T_{4} = { }T_{3} \times { }\left( {1 - \eta_{{{\text{GT}}}} \left( {1 - \left( {\frac{{P_{3} }}{{P_{4} }}} \right)^{{\frac{{1 - \gamma_{g} { }}}{{\gamma_{g} }}}} } \right)} \right)$$
(15)

A correlation for isentropic efficiency of the gas turbine as a function of \(\left(\frac{{P}_{3}}{{P}_{4}}\right)\) can be given as [22]:

$$\eta_{{{\text{GT}}}} = 0.90 - \frac{{\left( {\frac{{P_{3} }}{{P_{4} }}} \right) - 1}}{250}$$
(16)

The expansion work rate from the gas turbine is estimated by considering the flue gas flow rate \(\left( {\dot{m}_{g} } \right)\), gas-specific heat \(\left( {C_{{{\text{pg}}}} } \right)\), the temperature difference between entry and exit, and mechanical efficiency \(\left( {\eta_{m} } \right)\).

$$\dot{W}_{{{\text{GT}}}} = \dot{m}_{g} C_{{{\text{pg}}}} \left( {T_{3} - T_{4} } \right).\,\eta_{m}$$
(17)

2.1.4 Heat recovery steam generator

Each component of the dual pressure HRSG maintains energy balance for the gas and water streams. The equations are listed in Table 1.

Table 1 Energy balance equations in HRSG components

2.1.5 Steam turbines

The work generation rate from HPST is obtained by the expansion of steam coming from the high-pressure section of HRSG up to lower pressure. This steam is adiabatically mixed with low-pressure steam coming from the low-pressure section of HRSG. Likewise, the mixed steam is expanded in LPST to produce further work. The energy equations of both steam turbines are as follows:

$$\dot{W}_{{{\text{HPST}}}} = \eta_{m} .{ }\eta_{{\text{isen,hpst}}} .\dot{m}_{{\text{s,hp}}} \left( {h_{{\text{hp,sh, ex}}} - h_{{\text{lp,sh, ex}}} } \right)$$
(18)
$$\dot{m}_{{\text{s,lp}}} + \dot{m}_{{\text{s,hp}}} = \dot{m}_{s}$$
(19)

Here, \(\dot{m}_{s}\) is the total mass flow rate of steam that is to be expanded in LPST.

$$\dot{W}_{{{\text{LPST}}}} = { }\eta_{m} .{ }\eta_{{\text{isen,lpst}}} .\left( {\dot{m}_{s} \left( {h_{{\text{lp,sh, ex}}} - h_{{\text{lpst, dea,pres}}} } \right) + \left( {\dot{m}_{s} - \dot{m}_{{\text{s,dea}}} } \right)\left( {h_{{\text{lpst, dea,pres}}} - h_{{\text{lpst, ex}}} } \right)} \right)$$
(20)

2.1.6 Steam condenser

The exiting steam from LPST is condensed in the steam condenser. The energy balance between the steam and cooling water is depicted as follows:

$$\left( {\dot{m}_{s} - \dot{m}_{{\text{s,dea}}} } \right)\left( {h_{{\text{lpst, ex}}} - h_{{\text{cond, ex}}} } \right) = \dot{m}_{{{\text{cw}}}} C_{{\text{p,cw}}} \left( {t_{{\text{cw,in}}} - t_{{\text{cw,out}}} } \right)$$
(21)

2.1.7 Deaerator

The deaerator removes dissolved gases such as O2 and CO2 from the condensate by using steam bled from the LPST; as a result, feed water is obtained at deaerator pressure. Deaerator pressure is calculated using the deaerator temperature ratio for the optimum heat recovery from the exhaust [23]:

$$\theta_{{{\text{dea}}}} = \frac{{T_{{\text{fw,dea,ex}}} - T_{{{\text{cond}}}} }}{{T_{{\text{fw,sat,hp}}} - T_{{{\text{cond}}}} }}$$
(22)

The mass flow rate of steam bled for deaeration is calculated with the help of energy balance as follows:

$$\dot{m}_{{\text{s,dea}}} \left( {h_{{\text{s,dea,in}}} - h_{{\text{cep,ex}}} } \right) = \dot{m}_{s} \left( {h_{{{\text{fw}}}} - h_{{\text{cep,ex}}} } \right)$$
(23)

2.1.8 Condensate extraction pump

The work input rate in CEP is given as:

$$\dot{W}_{{{\text{cep}}}} = { }\frac{{\left( {\dot{m}_{s} - \dot{m}_{{\text{s,dea}}} } \right)\left( {h_{{\text{cep,ex}}} - h_{{\text{cond, ex}}} } \right)}}{{\eta_{{\text{m,cep}}} }}$$
(24)

2.1.9 Boiler feed pumps

The required work input rate for low- and high-pressure boiler feed pumps (BFP), respectively, is written as:

$$\dot{W}_{{\text{BFP,lp}}} = \frac{{\dot{m}_{{\text{s,lp}}} \left( {h_{{\text{hrsg,lp}}} - h_{{{\text{fw}}}} } \right)}}{{\eta_{{\text{m,BFP,lp}}} }}$$
(25)
$$\dot{W}_{{\text{BFP,hp}}} = \frac{{\dot{m}_{{\text{s,hp}}} \left( {h_{{\text{hrsg,hp}}} - h_{{{\text{fw}}}} } \right)}}{{\eta_{{\text{m,BFP,hp}}} }}$$
(26)

The total work output of standalone CCGT is given as:

$$\dot{W}_{{{\text{CCGT}}}} = \dot{W}_{{{\text{GT}}}} - \dot{W}_{C} + \dot{W}_{{{\text{HPST}}}} + \dot{W}_{{{\text{LPST}}}} - \dot{W}_{{\text{BFP,lp}}} - \dot{W}_{{\text{BFP,hp}}} - \dot{W}_{{{\text{cep}}}}$$
(27)

The efficiency of standalone CCGT is established as

$$\eta_{{{\text{CCGT}}}} = \frac{{\dot{W}_{{{\text{CCGT}}}} }}{{\eta_{{{\text{CC}}}} .\dot{m}_{f} {\text{LHV}}}}$$
(28)

2.1.10 Double-effect water-LiBr VARS

The working fluid for series flow double-effect VARS comprises a refrigerant (Water) and an absorbent (LiBr) [37]. It is modeled using the approach and assumptions of Gomri and Hakimi [17]. The thermodynamic properties (enthalpy and entropy) of water-LiBr solution at different points are calculated using the correlations suggested by Pátek and Klomfar [33].

The concentrations of strong solution (function of the absorber and evaporator temperature) and weak solution (function of VARS condenser and LPG temperature) are calculated as follows [25]:

$$X_{{{\text{ss}}}} = \frac{{49.04 + 1.125t_{a} - t_{e} }}{{134.65 + 0.47t_{a} }}$$
(29)
$$X_{{{\text{ws}}}} = \frac{{49.04 + 1.125t_{{{\text{LPG}}}} - t_{c} }}{{134.65 + 0.47t_{{{\text{LPG}}}} }}$$
(30)

The concentration of the medium solution \(\left( {X_{{{\text{ms}}}} } \right)\) lies between \(X_{{{\text{ws}}}}\) and \(X_{{{\text{ss}}}}\). \(X_{{{\text{ms}}}}\) is calculated using an iterative method unless the energy balance in LPG reaches up to 10−4 kW [17]. Hence, the mass flow rate of weak, strong, and medium solutions is calculated using the concentration values. The energy balance in LPG is given as follows:

$$Q_{{{\text{LPG}}}} = m_{9} h_{9} + m_{19} h_{19} = m_{20} h_{20} + m_{22} h_{22} + m_{23} h_{23}$$
(31)

The concentration value should be less than the critical concentration to eliminate crystallization at any point in the system. The critical concentration as a function of temperature (in °C) was developed by a dynamic simulation model for double-effect VARS [15]. It can be expressed as:

$$X_{C} = 0.0809 \times t + 61.341$$
(32)

The heat load in HPG and evaporator is given by:

$$Q_{{{\text{HPG}}}} = m_{{\text{g,HPG}}} C_{{{\text{pg}}}} \left( {T_{5} - T_{6} } \right) = m_{9} h_{9} + m_{17} h_{17} - m_{16} h_{16}$$
(33)
$$Q_{{{\text{evap}}}} = m_{{\text{a,evap}}} C_{{{\text{pa}}}} \left( {T_{0} - T_{1} } \right) = m_{12} h_{12} - m_{11} h_{11}$$
(34)

The energy balance in the condenser and absorber is written as follows:

$$Q_{{{\text{cond}}}} = m_{{\text{w,cond}}} C_{{{\text{pw}}}} \left( {{\Delta }T_{{\text{w,cond}}} } \right) = m_{21} h_{21} + m_{22} h_{22} - m_{10} h_{10}$$
(35)
$$Q_{{{\text{abs}}}} = m_{{\text{w,abs}}} C_{{{\text{pw}}}} \left( {{\Delta }T_{{\text{w,abs}}} } \right) = m_{12} h_{12} + m_{25} h_{25} - m_{13} h_{13}$$
(36)

The overall performance of VARS is estimated by evaluating its COP, represented as:

$${\text{COP}} = \frac{{Q_{{{\text{evap}}}} }}{{Q_{{{\text{HPG}}}} + \dot{W}_{{{\text{SP}}}} }}$$
(37)

where \(\dot{W}_{{{\text{SP}}}}\) is work input rate to the solution pump and expressed as:

$$\dot{W}_{{{\text{SP}}}} = m_{13} \frac{{\left( {P_{{{\text{HPG}}}} - P_{{{\text{abs}}{.}}} } \right)}}{{n_{{{\text{sp}}}} \rho_{13} }}$$
(38)

Now, the total work output of an inlet air cooling integrated system (i.e., CCGTV) is calculated as

$$\dot{W}_{{{\text{CCGTV}}}} = \dot{W}_{{{\text{CCGT}}}} - \dot{W}_{{{\text{SP}}}}$$
(39)
$$\eta_{{{\text{CCGTV}}}} = \frac{{\dot{W}_{{{\text{CCGTV}}}} }}{{\eta_{{{\text{CC}}}} .\dot{m}_{f} {\text{LHV}}}}$$
(40)

2.2 Exergy analysis

Exergy analysis is the thermodynamic analysis that rationally evaluates a system using the first and second laws of thermodynamics. It enables the evaluation and comparison of processes and scope for improvement by eliminating component-wise irreversibility [1]. In a control volume, the exergy balance is written as:

$$\frac{{{\text{d}}E_{{{\text{CV}}}} }}{{{\text{d}}t_{j} }} = \Sigma \left( {1 - \frac{{T_{0} }}{{T_{i} }}} \right)\dot{Q}_{i} - \left( {\dot{W} - P_{0} \frac{{{\text{d}}V_{{{\text{CV}}}} }}{{{\text{d}}t}}} \right) + \mathop \sum \limits_{i} \dot{m}_{i} e_{i} - \mathop \sum \limits_{e} \dot{m}_{e} e_{e} - \dot{E}x_{D}$$
(41)

If the rate of energy exchange across the control volume is zero, the equation will be obtained as [21]:

$$\dot{E}x_{Q} + \mathop \sum \limits_{i} \dot{m}_{i} e_{i} = \mathop \sum \limits_{e} \dot{m}_{e} e_{e} + \dot{E}x_{W} + \dot{E}x_{D}$$
(42)

where e is exergy and \(\dot{E}x_{D}\) is exergy destruction rate in kW.

$$\dot{E}x_{D} = T_{0} \dot{S}_{{{\text{gen}}}}$$
(43)
$$\dot{E}x_{Q} = \left( {1 - \frac{{T_{0} }}{{T_{i} }}} \right)\dot{Q}_{i}$$
(44)
$$\dot{E}x_{W} = \dot{W} - P_{0} \frac{{{\text{d}}V_{{{\text{CV}}}} }}{{{\text{d}}t}}$$
(45)
$$e_{{{\text{ph}}}} = \left( {h - h_{0} } \right) - T_{0} \left( {s - s_{0} } \right)$$
(46)

2.2.1 Plant fuel exergy

The exergy assessment of combustion is calculated by considering the physical exergies of flowing streams and the chemical exergy of fuel [14]. The total exergy component of fluid is written as:

$$\dot{E}x_{{{\text{total}}}} = \dot{E}x_{{{\text{ph}}}} + \dot{E}x_{{{\text{ch}}}}$$
(47)

The physical exergy of fuel is calculated using the ideal model of gas [32].

$$\dot{E}x_{{{\text{ph}}}} = \dot{m}_{f} C_{p}^{h} \left( {T - T_{0} } \right) - \dot{m}_{f} T_{0} \left[ {C_{p}^{s} \ln \frac{T}{{T_{0} }} - R\ln \frac{P}{{P_{0} }}} \right]$$
(48)

The mean specific heat for calculating enthalpy and entropy is depicted as:

$$C_{p}^{h} = \frac{1}{{T - T_{0} }}\mathop \int \limits_{{T_{0} }}^{T} C_{p} {\text{d}}T$$
(49)
$$C_{p}^{s} = \frac{1}{{\ln \frac{T}{{T_{0} }}}}\mathop \int \limits_{{T_{0} }}^{T} C_{p} {\text{d}}T$$
(50)

The chemical exergy fuel \(\left( {{\text{ex}}_{{\text{f}}}^{{{\text{ch}}}} } \right)\) is calculated using the following relation [3]:

$$\xi \, = \frac{{ex_{{\text{f}}}^{{{\text{ch}}}} }}{{{\text{LHV}}}}$$
(51)

the value of ξ is close to unity for common gaseous fuels [9]. The value ξ is taken as 1.06 for methane.

An experimental correlation is useful to calculate the value of ξ for any gaseous fuel with a composition \({C}_{x}{H}_{y}\) [14]:

$${\upxi } = 1.033 + 0.0169\frac{y}{x} - \frac{0.0698}{x}$$
(52)

The expressions for exergy destruction rate and energetic efficiency for each component of CCGT are represented in Table 2.

Table 2 Equations for exergy destruction rate and exergetic efficiency for various components

2.3 Exergy-based sustainability indicators

Exergy analysis is an attractive method to assess the sustainability level of several energy systems. Sustainability is described as a policy of supplying energy resources at a reasonable cost and with little or no environmental impact [28]. Several sustainability indicators have been examined for the CCGT system based on the theoretical foundation for exergy analysis. Moreover, the effect of inlet air cooling on these parameters has been discussed.

The following exergy-based sustainability indicators [40] considered for this study are:

  1. (i)

    Fuel depletion ratio

  2. (ii)

    Exergetic improvement potential

  3. (iii)

    Environmental effect factor

  4. (iv)

    Environmental sustainability index

2.3.1 Fuel depletion ratio

The fuel depletion ratio is the ratio of the exergy destruction rate in a component to the fuel exergy. A lower fuel depletion ratio is preferred because it indicates that the system has destroyed less exergy corresponding to fuel exergy. Consequently, more exergy is available at the output [40].

$${\text{Fuel depletion ratio}} = \frac{{\dot{E}x_{{\text{D,componet}}} }}{{\dot{E}x_{{{\text{fuel}}}} }}$$
(53)

2.3.2 Environmental effect factor

Environmental effect factor \(\left( {r_{{{\text{eef}}}} } \right)\) is a crucial sustainability factor that is defined as the ratio between waste exergy ratio (WER) and exergetic efficiency. It specifies the severity of environmental damage because of exergy destruction. As a result, \(r_{{{\text{eef}}}}\) is preferred to have low value.

$${\text{WER}} = \frac{{\text{Total exergy waste}}}{{\text{Total exergy input}}}$$
(54)
$$r_{{{\text{eef}}}} = \frac{{{\text{WER}}}}{{\eta_{{{\text{ex}}}} }}$$
(55)

2.3.3 Environmental sustainability index

It is another vital parameter to assess the sustainability level of the system. As a definition, it is represented by the reciprocal of \(r_{{{\text{eef}}}}\). This index has a value between 0 and 1. A higher exergetic efficiency indicates less waste exergy and a lesser environmental impact, resulting in an increased environmental sustainability index (ESI) of the system. Therefore, an ESI close to 1 indicates a more environmentally sustainable system [39].

$${\text{ESI}} = \frac{1}{{r_{{{\text{eef}}}} }}$$
(56)

2.3.4 Exergetic improvement potential rate

The exergetic improvement potential is associated with the combined effect of exergetic efficiency and the exergy destruction rate. A higher improvement potential advocates that the system requires improvement over time [40]. Hence, a low exergetic improvement potential is preferred.

$${\text{Exergetic improvement}} {\text{potential rate}} = \left( {1 - \eta_{{{\text{ex}}}} } \right) \times \dot{E}x_{D}$$
(57)

Figure 2 presents a flowchart that outlines the sequential steps of the thermodynamic simulation process in a logical manner. The flowchart ultimately leads to a comparison of performance parameters and sustainability indicators under different situations, specifically with and without inlet air cooling.

Fig. 2
figure 2

A mathematical framework and flow-chart of the thermodynamic simulation process

3 Model validation

Validation of the numerical model established for this system is a necessary step to remove ambiguities and build confidence in the accuracy of the results. The results of this study are validated with previously published papers on related topics. The model of water-LiBr double-effect VARS has been validated by an experimental study of the micro-scale absorption chiller by Yin et al. [45]. The input parameters of Yin et al. [45] are used for generating results from the program made in MATLAB. Table 3 shows the comparison of results obtained from the present model and experimental results of Yin et al. [45] for validation. The simulated results exhibit a maximum deviation of 5.34% from the experimental data. Moreover, the gas cycle-specific work and thermal efficiency of the present study are compared with those substantiated by Mohapatra and Sanjay [29] at ambient conditions of 303 K and RH = 20%, as shown in Fig. 3. Both parameters are in good agreement with each other, within 4% of the variation. The COP of the water-LiBr vapor absorption system decreases with an increase in ambient temperature, as compared to the trend with Ren et al. [36]. The variation of \({r}_{\mathrm{eef}}\) and \(\mathrm{ESI}\) against the exergetic efficiency of the system shows a similar trend to those reported by Eke et al. [11].

Table 3 Model validation of Water-LiBr double-effect VARS
Fig. 3
figure 3

Comparison of gas cycle specific work and efficiency results from the present study with Mohapatra and Sanjay [29]

4 Results and discussion

The performance of the standalone CCGT system along with its integration with a double-effect vapor absorption system is investigated with realistic input data. The input parameters for the analysis are presented in Table 4. Utilizing governing equations, a MATLAB program was developed for the analysis, and input data were used to obtain the results.

Table 4 Input data for the simulation [16, 31, 37]

4.1 Effect of ambient temperature and IAC on energy parameters

Based on the thermodynamic equations mentioned in Sect. 2.1, energy analysis is the primary criterion for the assessment of the CCGT and CCGTV. Energy performance encapsulates the total work output and thermal efficiency as the key performance parameters for the comparison of both cases.

The plant-specific work output as a function of ambient temperature is depicted in Fig. 4. The compressor’s inlet temperature rises as the ambient temperature rises, resulting in more compression work. As a result, the specific work output rate in CCGT decreases. When the compressor inlet temperature (CIT) is fixed at 288 K via inlet air cooling, the CCGTV specific work increases by 2.07 to 5.04% when the ambient temperature rises from 290 to 306 K. On the contrary, CCGTV-specific work decreases across the range because, in order to keep CIT at 288 K, VARS must fetch more heat from the HRSG as the ambient temperature rises. As shown in Fig. 4, increased temperature exhaust is required at the HRSG exit. It eventually leads to less STC-specific work. The COP of VARS as a function of ambient temperature is also shown in Fig. 5. When the ambient temperature rises from 290 to 306 K, the COP falls to 0.83 from 1.44. The reason for this is that as the ambient temperature rises, the evaporator must absorb more heat from the surrounding air in order to maintain CIT at 288 K. To increase the heat intake from the evaporator, the VARS must generate more refrigerant, which ultimately increases the heat supplied by the HRSG exhaust at the HPG. However, as the ambient temperature rises, the heat input in HPG rises faster than the heat intake in the evaporator, resulting in a decrease in the COP of VARS.

Fig. 4
figure 4

Effect of ambient temperature on specific work output

Fig. 5
figure 5

Effect of ambient temperature on the COP of VARS and HRSG exhaust temperature

Similarly, in Fig. 6, the thermal efficiency is shown as a function of ambient temperature. The thermal efficiency of CCGTV is found to be higher than CCGT, which also indicates lesser fuel consumption per unit of work output. At 290 K, an improvement of 1.58% is observed, which increases to 1.64% at 296 K and then decreases to 1.23% at 306 K. Thus, when the temperature difference between cooled air and ambient air (i.e., the degree of cooling) is 8K, the greatest increase in thermal efficiency is observed.

Fig. 6
figure 6

Effect of ambient temperature on the overall thermal efficiency

4.2 Effect of ambient temperature and IAC on exergetic performance

The exergetic performance summarizes the exergy destruction rate and exergetic efficiency of each component and the complete system. Figure 7 depicts the exergetic efficiency of the system as a function of ambient temperature. As the ambient temperature rises, the exergetic efficiency decreases. Since the high CIT decreases the useful exergy (net work output) in CCGT, the resulting exergetic efficiency decreases. After maintaining the CIT at 288 K with the help of inlet air cooling, exergetic efficiency is found to be improved. CCGTV is 1.23 to 1.64% more exergetically efficient than CCGT over the specified ambient temperature range. However, the specific exergy destruction in CCGTV is 0.91% lower than in CCGT at 290 K, and the same becomes 1.46% higher at 306 K. This increase is due to an increased fuel supply in the combustion chamber and the addition of the VARS to the existing CCGT. Table 5 shows the component-wise specific exergy destruction in each component. Among all components, the combustion chamber is shown to be the largest exergy destroyer. In both cases, the contribution of the exergy destruction in the combustion chamber is greater than 60.32% of the total specific exergy destruction. These outcomes are owing to the enormous irreversibilities associated with chemical reactions and heat transfer across substantial temperature differences between compressed air and fuel.

Fig. 7
figure 7

Effect of ambient temperature on exergetic efficiency

Table 5 Specific exergy destruction in various components

4.3 Effect of other influential parameters on the performance

In addition to ambient temperature, the thermodynamic performance of CCGT and CCGTV, as well as the effect of other influential parameters including gas turbine inlet temperature (TIT) and pressure ratios, has been investigated. Figure 8 depicts the variations in specific work output and exergetic efficiency of CCGT and CCGTV. The specific work output and exergetic efficiency both decrease as the ambient temperature rises, which is also validated by previous results. However, increasing the pressure ratio from 20 to 23 marginally reduces the total work output. The reason being as the compressor work increases, the net work production decreases. Also, as a result of the increased pressure ratio, the temperature of compressor exhaust air rises, and the fuel intake would decrease to achieve a TIT of 1750 K. The effect of inlet air cooling has also been shown in the results. Additionally, the reduction in TIT from 1750 to 1600 K has a considerable impact on both performance factors. The decline in gas turbine work production and fuel supply is attributed to the fact that the former diminishes at faster rates than the latter. Along with that, it is noteworthy that for the same pressure ratio, TIT, and the same increase in ambient temperature, the rate of change (i.e., decrease) in both parameters, whether CCGT or CCGTV, is nearly identical.

Fig. 8
figure 8

Effect of TIT, pressure ratio, and inlet air cooling on the specific work output and exergetic efficiency

As a result of inlet air cooling, it is necessary to analyze the variation in several performance factors. This analysis may suggest points in the working range at which multiple parameters are favorable. As the ambient temperature ranges from 290 to 306 K, it is intriguing to learn how each operating and performance parameter increases or decreases when CCGT is replaced by CCGTV with a CIT of 288 K.

Figure 9 depicts the percentage change in those parameters over the degree of cooling ranges from 2 to 18 K. The rate of fuel intake into the combustion chamber increases as the air cools before the compressor. With it, the rate of increment of total work also increases. Since total work consists of GTC and STC-specific works, as the degree of cooling increases, the increase in gas turbine work increases, while the increase in steam turbine work decreases. The increase in gas turbine efficiency is correlated with the constant reduction of compressor work caused by cooled air. The increase in STC-specific work is a result of the increased flue gas rate in the GTC, followed by the HRSG as a result of cooling. However, as the degree of cooling increases, STC-specific work decreases because VARS requires more energy from HRSG exhaust, thereby reducing the steam production rate. And as the cooling approaches a higher degree, the effect of decreasing increment in STC-specific work becomes predominant. As a result, the rate of increase in total work has been observed to decrease as the degree of cooling increases. After 18 K of inlet air cooling, the total work curve could begin to flatten or decrease. In contrast, the increase in the exergetic efficiency of the entire system continues up until 8 K of air inlet cooling. After that, it decreases until the degree of cooling reaches 18 K.

Fig. 9
figure 9

Effect of degree of cooling on variation in several parameters of CCGTV

This result suggests that the optimal degree of cooling for CCGTV, in terms of total work output and exergetic efficiency, is between 8 and 18 K. CCGTV can operate with a cooling degree of 18 K to generate maximum work and with a cooling degree of 8 K to maximize yield in exergetic efficiency. If the price per unit of electricity is high, it may be economically advantageous to operate the CCGTV with 18 K of cooling; if the price per unit of fuel increases, the degree of cooling could approach 8 K in order to balance overall operational costs.

4.4 Effect of IAC on exergy sustainability indicators

The range of fuel depletion ratios for all major components with and without inlet air cooling is shown in Table 6. The total fuel depletion ratio is shown to be 1.38 to 1.26% lower after using inlet air cooling. It suggests that CCGT with inlet air cooling (i.e., CCGTV) ends up destroying less exergy per unit of fuel than standalone CCGT. Therefore, CCGTV turns out to be more exergetically superior to standalone CCGT. The fuel depletion ratio in both the major exergy destroyers, i.e., the combustion chamber and HRSG, is found to be decreased in CCGTV. Figure 10 shows the exergetic improvement potential as a function of ambient temperature. CCGTV has shown lower overall exergetic improvement potential than CCGT. However, the increase in improvement potential in CCGTV is rapid with the increase in ambient temperature. At 290 K, the difference in exergetic improvement potential is 3.07%, which decreases to 0.37% at 306 K. The combustion chamber in CCGTV is found to have marginally increased improvement potential by 0.60 to 1.70%, while HRSG has shown a decline of 2.89 to 8.97% in the same.

Table 6 Comparison of fuel depletion ratios
Fig. 10
figure 10

Effect of ambient temperature on exergetic improvement potential

Figure 11 demonstrates the effect of increased ambient temperature on the environmental effect factor (\({r}_{\mathrm{eef}}\)) and environmental sustainability index (ESI). The \({r}_{\mathrm{eef}}\) varies between 1.285 and 1.331 for CCGT while for CCGTV, it varies between 1.247 and 1.285, showing a reduction of 2.92 to 3.40% over the specified range. On the other hand, ESI varies from 0.777 to 0.751 for CCGT, and 0.803 to 0.778 for CCGTV, showing an improvement of 3.01–3.52%. Thus, a reduction in \({r}_{\mathrm{eef}}\) shows less damage to the environment after cooling the inlet air. Also, the increase in ESI implies that there is a reduction in waste exergy, as decreasing the CIT is an effective way. Figure 12 shows the variation of \({r}_{\mathrm{eef}}\) with exergetic efficiency. As exergetic efficiency increases, the \({r}_{\mathrm{eef}}\) decreases. Also, the range of \({r}_{\mathrm{eef}}\) shifted even lower after the integration of inlet air cooling. It implies that the CCGTV is more exergetically efficient because it releases fewer emissions into the atmosphere. Since ESI is reciprocal to \({r}_{\mathrm{eef}}\), ESI increases with an increase in exergetic efficiency. Therefore, CCGTV has witnessed greater sustainability due to reduced irreversible losses and, hence, efficient utilization of resources.

Fig. 11
figure 11

Effect of ambient temperature on Environmental effect factor and ESI

Fig. 12
figure 12

Variation of exergetic efficiency with Environmental effect factor

5 Conclusion

The CCGT plant has undergone an analysis involving the implementation of inlet air cooling. This process is achieved through the integration of a water-LiBr-based double-effect VARS. The analysis of the system has been conducted using energy, exergy, and exergy-based sustainability indicators. The conclusions that can be inferred from this study are summarized as follows:

  1. (1)

    The integration of a double-effect vapor absorption refrigeration system with the CCGT enables an increase in specific work output and thermal efficiency by a maximum of 5.04 and 1.64%, respectively. Table 7 compares the performance improvement of the current system to that of the single-effect Ammonia-water-based VARS inlet air cooling investigated by Singh [38].

  2. (2)

    To keep CIT at 288 K, the VARS absorbs more heat from the HRSG’s exit, as the COP of the VARS reduces with the rise in ambient temperature. Consequently, a reduction in the steam generation rate has been observed in the bottoming cycle.

  3. (3)

    The combustion chamber is the dominant contributor to irreversibility, accounting for ≥ 60.32% of total irreversibility. The CCGT system with inlet air cooling is 1.23–1.64% more exergetically efficient than a standalone CCGT plant.

  4. (4)

    After using inlet air cooling, the fuel depletion ratio and exergetic improvement potential are found to be reduced by a maximum of 1.38% and 3.07%, respectively.

  5. (5)

    The environmental effect factor for VARS-integrated CCGT has been observed to decrease by 2.92 to 3.40%. Thus, the environmental sustainability index is found to be enhanced.

  6. (6)

    In order to maximize the exergetic efficiency and total work output of CCGTV, the suitable degree of inlet air cooling ranges from 8 to 18 K.

  7. (7)

    Improved exergetic efficiency reduces the adverse environmental effect and promotes the system’s sustainability as a result of efficient utilization of fuel.

Table 7 Improvement in performance by inlet air cooling in the present analysis as compared to the same in Singh [38]

Furthermore, effective fuel utilization would help reduce emissions per unit of power generation. This would reduce the cost of post-combustion carbon capture, ultimately accelerating the achievement of decarbonization goals.

The current work can be viewed as an initial effort toward adopting a thermodynamic approach to analyze the reliability of absorption-based inlet air cooling for CCGT power plants. Additionally, it is suggested that future research in this topic should explore the economic aspect using the exergy costing method. This approach should be combined with a multi-objective optimization framework that aims to maximize exergetic efficiency while simultaneously minimizing overall cost. However, based on the study’s findings, several technical recommendations (also from the industrial and research and development perspectives) can be made. These recommendations are listed below:

  1. (1)

    To enhance the performance of a CCGT plant, warm ambient air should be cooled to the ISO temperature for gas turbines.

  2. (2)

    Utilize a waste heat-powered double-effect absorption refrigeration system instead of a mechanical refrigeration system and single effect absorption systems to cool the warm ambient air.

  3. (3)

    Put emphasis on minimizing exergy destruction in the combustion chamber as it is the largest exergy destroyer.

  4. (4)

    For the intended enhancement of power output and exergetic efficiency, the recommended ambient temperature range for operating the presented system is between 296 and 306 K.