Abstract
Wind energy outweighs other kinds of renewable energy for endless harvestable potential. The integration of wind power into electric grids poses unique challenges because of its stochastic nature, causing a highly erratic generation of power. It affects the power quality and planning of power systems. This article outlines technical issues of wind power integration in the electric grid, providing the power quality interaction of the Doubly fed induction generator (DFIG) in the electric grid perspective. The prevalence of the DFIG in such large numbers necessitates this. An overview of different control strategies for power quality improvement of DFIG, application of energy storage schemes (ESS) and Wind power forecasting techniques, their requirements and advantages for facilitating increased penetration of DFIG in the electric grid is given. Robust integration and deeper penetration of wind power into the future electric grid necessitate balancing power quality improvement, energy storage technology, and wind power forecasting technique of the wind energy system.
Similar content being viewed by others
Avoid common mistakes on your manuscript.
1 Introduction
Wind energy is mainly favored wind energy with respect to its technical and economical characteristics (Alam et al. 2020; Chen et al. 2019). Figure 1 depicts the various components of a wind energy system. However, the inherent variability of wind power, lack of control thereof and prediction complexity () make it difficult to store, posing a significant challenge in the proper operation of the electric grid. Employment of doubly fed induction generator (DFIG) in large variable-speed wind energy systems, as well as in stand-alone applications, is because of its ability to provide reactive power during grid faults and voltage support in low voltage conditions (Cardenas et al. 2013; Ren21 R 2016; Ahmed et al. 2020). DFIG configuration shown in Fig. 2 is a preferred choice in high-power grid-connected Wind energy conversion systems (WECS) due to the enormous economic gains (Ren21 R 2016). Nevertheless, the monetary gain is not considered in the case of stand-alone wind turbine systems, where the power level is relatively low (ranging from a few kilowatts to a few hundred kilowatts) (Carpinone et al. 2010).
DFIG can also extract the best wind power for extended wind speeds, reduced mechanical stress and four-quadrant operation. Table 1 summarize additional DFIG advantages over other wind turbine generator technologies (Failed 2021; Polinder et al. 2006; Datta and Ranganathan 2002; Zou et al. 2013). However, various power quality (PQ) issues persist due to DFIG's interaction with the electric grid. They vary under different conditions of wind and electric grid characteristics. Suitable Power quality improvement strategies are necessary to overcome this limitation for deeper penetration of wind power in the robust grid of the future. Improved power quality manages voltage compliance and eliminates pockets of mitigation of low voltage, while poor power quality can cause various problems resulting in unstable utility systems and power disruption (Herbert et al. 2007). Poor grid power quality affects wind energy system generators’ performance causing increased losses for the utilities and other consumers (Standard 2001).
Voltage unbalances, system harmonics and the harmonic grid introduces oscillations in the DFIG system output power, stator power, dc-link voltage and electromagnetic torque, resulting in unwarranted torque harmonics and inaccuracy in the active/reactive power generation, worsening the performance of DFIGs (Ackermann 2005; Nian et al. 2012).
In Fig. 3, the interaction between grid-connected DFIG and power quality phenomenon in correlation to the electric grid characteristics is established. IEC 61400-21 (Standard 2001) assesses the grid-connected wind energy systems regarding power quality. In addition, it describes the process for evaluating the wind turbine power quality features by analyzing flicker, wind turbine switching operation, and harmonics as illustrated in IEC 61000-4-7. This article attempts to provide an overview of different issues related to the interconnection of the DFIG wind energy systems in the electric grid. Additionally, categorization of control strategies for DFIG power quality improvement for increased wind power penetration in the electric grid was done.
In addition, technologies of ESS and methodologies of wind power forecasting were taken into consideration for an unprecedented number of options for energy production and consumption. This is due to the fact that in the not-too-distant future, the codes for the electric grid will take into account the possibility of microgrids, island grids, and ESS technologies qualifying for integration into the primary electric grid. This will enable the main grid to achieve optimal performance and provide grid resiliency to power quality issues.
The paper's organization is as follows: Sect. 2 evaluates various interconnection and power quality issues of grid-connected DFIG, paving the way to identify the most potential problems, followed by Sect. 3, where different control strategies for power quality improvement are discussed with respect to their advantages and drawbacks. Energy utilization of the DFIG wind energy system was outlined in the same section. It was accomplished using wind power forecasting tools and energy storage strategies (ESS). This was done to ensure the smooth functioning and continued development of DFIG wind energy systems, with the goals of achieving optimal performance and grid resilience in the face of power quality challenges. The conclusion is presented in Sect. 4, along with the future scope.
2 Grid connection issues for DFIG
Wind power penetration exceeding 10% affects the economic operation of a power system (Zou et al. 2013; Herbert et al. 2007). It involves voltage management, production efficiency, transmission and distribution efficiency, power reserves and wasteful energy (Ackermann 2005). Host utilities should tolerate system disturbances and maintain a smooth voltage profile at the interconnection point. In addition, protection against voltage flicker caused by wind gusts, along with stability for post-fault electromechanical swings in the electric grid, is necessary. Control is essential to eradicate torque and reactive power pulsations (Nian et al. 2012) under the unbalance in the stator currents for a DFIG-based wind energy system. This is because large oscillations occur because of disturbance in a weak system (Glover et al. 2012).
Interaction of the electric utility with the wind energy system influences power quality and is mitigated best at the point of interconnection of a wind energy system to the utility (Georgilakis 2008) since the wind energy power factor and active output power output influences reactive power, which in turn causes voltages variations at PCC of the wind energy system (Liu and Kong 2014a). The power quality of the WECS and how stiff or weak the electric grid is at the point of wind energy system connection influence the voltage quality of the electric grid (Glover et al. 2012; Etxegarai et al. 2015). In more substantial parts of the electric grid, the sensitivity of customers to the power quality issues resulting thereof wind power connection reduces. Grid strength is characterized by the Short-circuit power level, applicable to the point of common coupling (PCC) of the electric grid (Etxegarai et al. 2015). Short-circuit power level measures current passing in a network installed with a wind energy system under fault conditions. Its consideration is vital for power quality issues on the grid and is represented as,
Ssc—Short-circuit power level, Ugrid—Grid voltage, Isc*—Short-circuit current, Zgrid—Grid impedance.
From above equation, the voltage at PCC under normal grid operation:
UPCC—Voltage at PCC, Iload—Current through load, Iturb—Current through turbine.
The above equation implies that lower grid impedance causes load and turbines to have less impact on PCC voltage, and a more robust grid has a higher short-circuit power level related directly to the ability of the grid to withstand disturbances.
Short-circuit power level may be low at PCC in wide-area weak power grids as the AC system impedance may be high relative to AC power (Pepermans et al. 2005). However, Short-circuit ratio (SCR) is more convenient to justify generation connected to the PCC. The grid topology or size of each country or region decides the ratio between the grid short circuit capacity of the grid and the wind power installed. It represents the grid strength with respect to the amount of wind power interconnected (Farias et al. 2010) as,
Ssc—Short circuit capacity, Sn—Rated power of wind turbine.
SCR values above 20 (Tande et al. 2007) to 25 (Feltes and Fernandes 2012) indicate a strong grid and weak for SCR values below 6–10, though these values vary in various literature. Low SCR is a concern for values of 5 or below (Farias et al. 2010). The system weakens with outages as reactance between the turbines and the system increase, resulting in lower levels of the SCR. DFIG interaction with the weak grid is accounted for by design parameters, nature of wind, and grid condition, as illustrated in Fig. 4.
DFIG wind energy systems are nonlinear and the presence of uncertainties results from wind speed causing electromagnetic torque to be a nonlinear function of the stator and rotor currents (Xiaodong et al. 2010). For a DFIG wind energy system, an unbalanced stator current could result from slight stator voltage imbalances that are unaccounted in the control system of DFIG. Unequal heating on the stator winding as well as torque and power pulsation in the generator results in unbalancing beyond a limit. Wind energy systems switch out of the network, further weakening the grid performance (Abo-Khalil et al. 2007). The various power quality issues of grid-connected DFIG discussed below:
2.1 Harmonics
Harmonics generated by DFIG wind energy systems are termed as higher-order fundamental frequency integer multiples. The back-to-back (B2B) configuration of DFIG introduces harmonics. Both stator and rotor of DFIG have harmonic components under different conditions:
-
Non-sinusoidal rotor voltage injection (Rotor harmonic components) (Xiaodong et al. 2010)
-
Unbalanced grid voltage (Stator harmonic components) (Pepermans et al. 2005)
-
Harmonically distorted grid voltage and its interaction with unbalanced grid voltage (Stator harmonic components) (Fathabadi 2014).
Harmonics due to the switching operation of the diode rectifier (mainly low order harmonics) and the rotating magnetic fields stemming from the rotor current harmonics induce rotor current and stator current harmonics. The dc-link voltage oscillations are less concerned as they are small (Yang et al. 2012). Limitations in control of rotor voltage and GSC current components cannot eliminate all the harmful effects caused by distorted grid voltage.
Variations in reactance due to slots generate harmonics in DFIG, whose magnitude and frequency depend on rotor speed and vary from balanced to unbalanced load conditions (Agrawal et al. 2015). 6 k ± 1 order harmonics generated by six-step switching cause quasi-sine wave rotor voltage. Machine design limitation creates non-sinusoidal air gap flux causing harmonics called MMF space harmonics. Mechanical design of the DFIG and RSC gives rise to stator harmonics and inter-harmonics. The design of stator, rotor windings, and slots generate MMF space harmonics and slot harmonics (Agrawal et al. 2015; Shafiullah et al. 2013).
2.2 Unbalanced voltages
-
Asymmetrical and/or unbalanced grid voltage is the first abnormal condition that affects the operation of a DFIG.
-
The distorted grid voltage is the second abnormal condition, which results in an effective decrease in the DFIG performances (Abo-Khalil et al. 2007).
-
The third abnormal problem is non-sinusoidal rotor voltage injection that effectively reduces the performance of a DFIG (Tande et al. 2007).
Ample torque and stator oscillations, unbalanced stator and rotor currents due to unbalanced voltages result in increased machine losses (Rodríguez et al. 2012), and DC-link voltage pulsation affects its life. To understand the behavior of the output active and reactive powers of DFIG connected to an unbalanced grid, the symmetrical components theory is necessary (Georgilakis 2008; Fathabadi 2014). In order to achieve tracking of instantaneous active and reactive powers reference values for eliminating resulting oscillations, proper strategies applied, utilizing the DFIG’s rotor voltage or rotor current, acting as control inputs (Farshadnia and Taher 2014).
2.3 Voltage dips
Voltage dips are brief reductions in voltage, lasting from a cycle to a second or so, or tens of milliseconds to hundreds of milliseconds, usually calculated for each half-period and measured by the RMS value; The duration is defined by the length of time the voltage is less than 90% of the nominal value (Sun et al. 2005). Voltage dips at the PCC result in high current flow in DFIG stator winding propagating through the rotor due to the magnetic coupling. Assessment of sudden voltage reduction assumes that a voltage change factor, ku (ψk) (Tande 2005) characterizes each wind turbine:
d—depth of voltage dip, ku(ψk)—voltage change factor, Sn—rated apparent power of the wind turbine, Sk—short-circuit apparent power of the grid.
The above equation does not consider the number of wind energy systems as a simultaneous startup is unlikely in a wind farm at the exact same time (Xie et al. 2013).
Severe voltage dips induce emf in the rotor windings as the maximum value of induced rotor voltage during the dip, Vr0 occurs at the instant of voltage dip and rotates in reverse with respect to rotor windings. Under rating of converter for a voltage lower than Vr0, cause rotor currents to be uncontrolled transitorily resulting in over-currents. The amplitude of these over-currents depends on the depth of the dip, maximum voltage of the converter, machine parameters and protection elements (Lopez et al. 2007). Stator flux cannot evolve to its final steady-state as quickly as stator voltage under sudden voltage dip.
In the steady-state operation of DFIG, for sudden voltage dip, sudden rotor voltage change should accompany a sudden change in stator voltage to avoid a significant increase in rotor current (Vidal et al. 2013). Supervising the rotor over current and dc-link overvoltage through PLL or synchronizing methods detects grid voltage dip (Abad and Iwanski 2014). During an asymmetric voltage dip, a voltage dc component or combination of dc and reverse-rotating ac components in air-gap flux, depending on the fault type, induces a high voltage in the rotor windings at rotational and/or double the rotational frequency, which causes the RSC to lose its ability to control the amount of current flowing through it (Kanjiya et al. 2014). This necessitates the consideration of stator flux dynamics. The design methodology necessary for DFIG to withstand voltage dips should have the following approach (Vidal et al. 2013):
-
DFIG design: for rapid stator flux damping.
-
B2B converter design: increased dc-bus voltage and current at maximum ratings.
2.4 Flicker
The visual fluctuations (frequency spectrum of 0.05–35 Hz (Tohidi and Behnam 2016; Ammar et al. 2011) in the light intensity (Saqib and Saleem 2015) because of periodic disturbances in the network voltage caused by grid power flow changes are termed as flicker. Continuous switching or start-up (at cut-in speed and rated speed) operations (Kasem et al. 2010) of wind energy systems cause flicker. IEC 61400-21 provides a calculation methodology for flicker emission of wind energy systems under both operation cases (Saqib and Saleem 2015). Specific frequencies cause small but persistent voltage fluctuations to be annoying. Flicker becomes a PQ issue at the PCC of a wind farm for short-circuit ratio (SCR) less than 10 and grid impedance ratio less than 2. Flicker emission levels reduction involves:
-
Increase in distribution line voltage levels higher than 35 kV
-
Higher inertia of large WTs
-
Injection of net active power into the grid from energy storage
-
Exchange of reactive power with grid (Díaz-González et al. 2012; Rodríguez Amenedo 2003).
Dynamic changes arising from wind speed fluctuations (causes flicker for frequencies lower than that of drive train), turbine mechanical design (flicker due to tower shadow effect), and rotational speed of the machine (3p torque oscillations between 0.5 and 1.5 Hz) are sources of flicker emission (Rodríguez Amenedo 2003; Bevrani et al. 2010). Other factors are power output of WT at connection point or PCC and type of WT technology. Flicker emission studies consider renewable energy generators' operation under the unity power factor accounting for its intermittency and grid impedance angle, operating power factor and short-circuit capacity (International Electrotechnical Commission 2008). The flicker level is quantified by the short-term flicker severity value Pst, and allowable voltage change as a function of frequency is Pst = 1. The flicker emission from variable-speed turbines is low compared to flicker emission from fixed-speed turbines. A normalized measure of the flicker emission during wind turbine continuous operation is given as,
Pst—flicker emission of the wind turbine, Sn—rated apparent power of the wind turbine, Sk—short-circuit apparent power of the grid.
A normalized measure of the flicker emission due to a single switching operation:
Tp—voltage variation duration due to switching operation; Pst—flicker emission of the wind turbine; Sn—rated apparent power of the wind turbine; Sk—short-circuit apparent power of the grid.
IEC 61,000–3-7 (International Electrotechnical Commission 2008) has standards of 0.35 and 0.25 for short-term flicker severity index and long-term flicker severity at wind farm PCC. In Fig. 5, the performance evaluation of the grid-connected DFIG wind energy system concerning power quality disturbances is shown.
Similarly, Fig. 6 shows the impact of individual PQ disturbances on DFIG stator voltages and currents.
3 Power quality and utilization of grid connected DFIG
3.1 Control strategies for PQ improvement
The selection of control strategies for PQ improvement depends on the power quality issues and interconnection point of the DFIG in the electric grid. Usage of control strategy for power quality (PQ) improvement regulates active power and reactive power, also accounting for a proper level of Dc link voltage (Bevrani et al. 2010). Different control strategies for the same are discussed below.
3.1.1 Direct power control (DPC)
Conventional DPC methods utilize a predefined lookup table for voltage vector selection to take into account voltage unbalance and control the generator output quantities. For DPC, feedback variables constitute torque and active and reactive powers of the DFIG stator (Yan et al. 2021; Razali et al. 2015). Accurate and prompt calculation of the active and reactive power is detrimental to the performance of the direct power control (DPC) scheme. It does not depend on DFIG system parameters. It is a reasonable solution for sudden voltage disturbance and imbalance ride-through applications for DFIG wind energy systems (Gao et al. 2021a). However, this scheme is unsuitable for generator speed control, and the performance of maximum power point tracking (MPPT) can be degraded. It also requires high switching frequencies increasing the computational burden (Razali et al. 2015).
A modified DPC with sequence domain control (SDC) (Baggu et al. 2015) for the GSC of DFIG is suitable for both continuous and sudden disturbances like system faults. A VPI-based DPC strategy (Gao et al. 2021b) for DFIG successfully achieves the smooth, active and reactive power output of DFIG under the harmonic voltage. A Coordinated DPC scheme (Li et al. 2018) for RSC and GSC of DFIG uses a single-side resonant controller (reduced-order vector integrator (ROVI)) to avoid the complex calculations of the power compensating components. An SVM-DPC with a PI-R controller (Nian et al. 2015a) incorporates multiple complex coefficient filters (MCCF) for a grid-connected voltage-source inverter and compromises the fundamental negative sequence current and the output power ripples. An improved DPC with duty cycle control (Zhang et al. 2019a) for a PWM rectifier obtains Active and reactive power regulation, power ripple reduction and more sinusoidal grid current at a much lower sampling frequency achieving strong robustness against inductance variations.
The main DPC scheme with an auxiliary demagnetizing current control scheme (Nian et al. 2015b) for RSC of DFIG provides shorter and smoother dynamic responses of the DFIG under transient frequency variation along with damping of the natural flux linkages. In (Yan et al. 2019), the RSC control by a modified DPC scheme and GSC control with a PI-R controller tuned at sixth the network voltage frequency significantly improves DFIG performance connected to a harmonic network. In (Mohammadi et al. 2014), an innovative combined control considering the structure of VC (stator-voltage-oriented frame (SVOF)) and DPC has been presented for the RSC of the DFIG providing a compromise of the advantages of the two methods. Sliding mode control based DPC (Shehata 2015) for RSC of DFIG provides low harmonics current in DFIG and minimal power oscillations.
A simple and robust integral sliding mode current-based (ISMC + CB-DPC) approach (Zhang et al. 2019b) for a DFIG-based wind energy system provides a better transient response and eliminates steady-state errors. In (Yongchang and Jiang 2021), the synchronous reference frame defines the oscillating terms of the B2B (back-to-back) converter of DFIG. This allows for simplified power terms extraction allowing for an improved DPC technique that achieves the control targets of reduction in unbalanced stator current, torque and power pulsations, and constant power output under network unbalance. Work (Xiong and Sun 2016) presents an improved DPC combined with a nonlinear back-stepping-based algorithm for DFIG under harmonic grid voltage. It provides decoupling control of the active and reactive power of the DFIG in the absence of a PI controller. It achieves performance comparable to the resonant-based controller for harmonic current suppression. Research work (Zhang and Jiang 2021) proposes space vector modulated direct power control based on proportional-integral-resonant (PI-RES) controller for VSC under unbalanced network conditions. This strategy introduces a particular ac reactive power reference component to reduce dc-bus voltage ripple and active power harmonic components simultaneously.
3.1.2 Sliding mode control (SMC)
Sliding mode control has reduced reference values for maximum power tracking controller to obtain reduced induced torque oscillations. It has several advantages such as fast dynamic response, good disturbance rejection, and robustness against parameter variations or grid disturbances and easy implementation. However, the chattering phenomenon is the main drawback, causing low power quality and instability of systems (Zin et al. 2013).
For harmonic compensation, SMC combines with conventional control. The active and reactive power control using the SMC combined with the PI control is investigated in Zhang et al. (2020) for fast load-voltage regulation and unbalanced voltage compensation. Work (Babaei et al. 2010) proposed a combination of SMC and PR control strategies to regulate the load voltage rapidly under unbalanced and distorted voltage. To enhance the transient and steady-state responses in a stand-alone mode, the sliding mode repetitive control scheme eliminates periodic harmonic disturbance (Teodorescu et al. 2011). Multi-resonant SMC scheme (Shtessel et al. 2014) reduces tracking error and THD under grid-connected mode.
A novel SMHC scheme that is a non-selective harmonic compensation method (Kang and Kim 2015) enhances the power quality in a grid-connected inverter when non-linear loads pollute the grid. It eliminates mainly harmful low-order harmonics with robustness and fast dynamics. An ISMPC algorithm (Hemdani et al. 2015) operating with constant switching frequency for a three-phase grid-connected power converter provides a fast transient response, low current THD, and robustness against parameter variations and external disturbances. Under an unbalanced and harmonically distorted grid, an SMC-based control algorithm (Martinez et al. 2012) was proposed for DFIG converters.
A complete solution based on SMC controls the DFIG converters' average active and reactive powers with constant switching frequency (Martinez et al. 2013) and provides robustness against parameter deviations. Model reference adaptive system observer-based sliding-mode control (MRAS-SMC) (Susperregui et al. 2014) for DFIG achieves improved performance and fault detection mechanism for sudden or excessive parameter variations in grid-connected and islanded modes. A robust discrete sliding mode control (Pande et al. 2013) for DFIG under (1) parametric uncertainties, (2) system disturbances and (3) voltage sag in the grid voltage demonstrate the controller's effectiveness in providing a fast system transient response, with the real and reactive powers tracking their references smoothly even in the presence of speed variations. A robust ISMC (Kassem et al. 2013) controls the flow of active and reactive power between the DFIG and the grid for variations in machine parameters. This achieves reduced chattering with an appropriate finite gain and zero steady-state error.
Undesirable mechanical stresses and the chattering phenomena of SMC can be avoided using a higher-order sliding mode control (HOSMC) (Abdeddaim and Betka 2013) for controlling the RSC of DFIG and achieving flexibility between the ‘‘Tracking mode’’ and the ‘‘Power regulation mode’’ without the negative effects of synchronous speed overshoot. Research work (Djerioui et al. 2014) provides a technique of sliding mode observer for implementing sliding mode controller of PWM rectifier. This article presents the design of a sliding mode controller using a technique that aims to simplify the control procedure. This includes (1) control of virtual flux, (2) direct control of power switches, and (3) reducing the number of sensors required for robust control against load and line variations. Control of RSC and the GSC of the DFIG to overcome inter-area oscillation for a multi-machine network with a new fast adaptive FABTSMCPCS (Fast adaptive back-tracking sliding mode control) (Patnaik and Dash 2016) utilizes dynamic equations in terms of the active and reactive power components of the stator and GSC of DFIG. It also overcomes unpredictable wind speed variation and consequent power output fluctuation in the absence of PLL.
3.1.3 Repetitive control (RC)
Repetitive control is based on the internal mode principle (Wieland et al. 2011). Periodic disturbances are rejected, and references are tracked at the same time. The repetitive controller has significant gains for harmonics at integer multiples of the fundamental frequency (Wang et al. 2009). Conventional RC regulator modification is necessary for grid frequency deviation in order to compensate for deterioration in the capability of DFIG stator harmonic current suppression.
Odd-harmonic RC (Hornik and Zhong 2011; Escobar et al. 2008), which takes advantage of the fact that the frequency spectrums of the vast majority of AC systems only contain odd harmonics, has an inherent time delay equal to half the period of an entire cycle. As a result, its dynamic response is significantly faster than that of conventional RC. However, that may not be sufficient to deal with disturbances caused by the grid voltage, such as swell or sag. This could result in the inverter generating an output current much higher than the reference current. Relying on RC alone to deal with such disturbance could cause the current error to be too high during the RC convergence time, which could cause an overcurrent fault. Work in Chen et al. (2013) eliminates the 6n ± 1 harmonic components using RC. For a Dual mode-structure RC (Sha et al. 2011) convergence rate for error is improved.
A cascaded current–voltage control strategy for inverters using an H ∞ repetitive controller (Zhong and Hornik 2013). It simultaneously improves the power quality of the load voltage, and current exchanged with the grid. Sinusoidal current injected into the utility grid using a current control strategy (PI controller + RC) (Trinh and Lee 2014). Fast convergence and high tracking accuracy achieved with robust RC incorporating time-varying sampling periods (Kurniawan et al. 2014). Digital nk ± m—order harmonic repetitive control (nk ± mRC) scheme (Lu et al. 2014) efficiently mitigates nk ± m—order harmonic frequencies in PWM converters. An improved RC regulator (Song and Nian 2015a) based on a conventional RC regulator for DFIG achieves good stator current harmonic suppression for the entire harmonic frequency spectrum. Research work (Abusara et al. 2015) implements a frequency adaptive odd-harmonic RC with a feed-forward loop at the fundamental frequency to ensure the current bounds for the convergence period of the RC. Authors in Song and Nian 2015b suppress stator current harmonic distortion of DFIG based on the BRC regulator.
3.1.4 Predictive control
The predictive control minimizes the forecast error to track the reference current without any error. It provides many benefits like reduction in torque and flux, active/ reactive power ripples, constant switching frequency, and excellent steady-state and transient responses. Nevertheless, it is sensitive to parameter changes due to the mathematical approach. The least-square method for parameter estimation improves the accuracy of control. A predictive dc-link voltage control (Yin et al. 2014) prevents Dc-link voltage fluctuation with the exact execution of the current reference. Work in Shi et al. (2020) implements a simple and robust Predictive Direct Virtual Torque and Power Control (PDVTC + PDPC) for RSC of DFIG to improve the power quality (Voltage and Frequency) in no-load mode; regulate active and reactive power in grid-connected mode.
Model predictive control (MPC) popularity is due to its flexible control scheme and accommodates system constraints and non-linearity easily. Depending on the application, the control objective varies (Cortes et al. 2012). It predicts the system behavior with the aid of a model to obtain the control signal by minimizing the objective function and selecting optimal switching states with a cost function as a criterion (Rojas et al. 2013). MPC performs an optimization procedure to calculate optimal control actions at each sampling interval. However, variable switching frequency achieves acceptable control results with relatively high sampling frequency and is unable to incorporate the modeling errors.
Research in Rahoui et al. (2021) proposes a model predictive control strategy for grid-connected inverters for renewable power generation to achieve islanded operation, grid synchronization and grid-connected operation. This done by changing the cost function appropriately to achieve different control objectives. Work in Liu and Kong 2014b presents an IOFL MPC for DFIG under normal and unbalanced grid conditions. Duty cycle control utilized in an improved low-complexity model predictive power control (MPPC) (Zhang et al. 2014a) for grid-connected power converters to reduce power ripples and current THD in conventional FCS-MPC. Model predictive current control (MPCC) has advantages, such as flexibility in controlling different variables, inherent decoupling behavior, fast dynamic response and easy inclusion of non-linearities and constraints (Pavlou et al. 2012). It is of some significance to achieve the source voltage sensorless control of the MPCC.
Unlike the traditional modulation-based algorithm, the MPCC needs the mathematical model of the converter to predict future currents. Hence, inaccuracy of the model parameters affects the control effect of the MPCC (Rodriguez et al. 2013). Because of this, the accuracy of the source voltage observation is further impacted. Owing to the above reasons, multivariable observation is necessary for the source voltage sensorless control of the MPCC. In the traditional current control strategy, multivariable observation has been widely studied. Some articles proposed parallel adaptive observation (Xiao et al. 2016), in which more than one observer estimates parameters and exchanges observation results. An improved MPCC (Liu et al. 2014) for a grid-connected converter with the newly designed HPO containing two parallel observers: linear extended-state observer (LESO) and adaptive filtering parameter observer (AFPO) is presented for wind energy system providing good stability, accuracy and reliability.
Authors in Song et al. (2013) introduce a robust model predictive current controller. Enhanced performance and disturbance compensation of the control obtained with an extended-state observer (ESO) with SVPWM. Work in Errouissi et al. (2017) utilizes a disturbance observer and predicts the stator current in the synchronous reference frame in the presence of model uncertainty and external perturbations. This achieved using Taylor series expansion over a finite time horizon. Simple design parameters aid the steady-state and transient performances.
3.1.5 Model predictive direct power control (MPDPC)
Model predictive DPC (MPDPC) effectively selects voltage vector and is more accurate (Ran et al. 2021; Camacho and Alba 2013; Xiao et al. 2021). Steady-state performance enhanced even in power ripples and current harmonics. It utilizes a cost minimization function for the selection of optimum voltage vectors. However, the possibility of applying of single voltage vector during the whole control period demands a high sampling frequency (Zhang and Qu 2015a). This can be avoided by introducing duty cycle control, achieving improved steady-state performance with lower sampling frequency (Zhang et al. 2013). An MPDPC strategy (Hu et al. 2015) for DFIGs considers the complete model of the DFIG and converter into account to respond quickly to grid conditions such as grid voltage unbalance.
Research work in Zhang and Qu 2015b uses APOE and proposes an MPDPC for PWM rectifiers to achieve sinusoidal grid currents and constant active power without modification to the original power references. MPDPC scheme with power compensation (Hu et al. 2015) for RSC of DFIG makes use of optimization cost function for selection of selects appropriate voltage vector. Authors in Arif et al. (2015) present a finite control set model predictive control (FS-MPDPC) for grid-connected converters. This is to address the uncertain grid parameters of a weak grid by integrating the estimation approach. However, neglecting the supply inductance reduces MPC performance and is detrimental to the grid voltage magnitude and phase.
MPDPC approach (Estrada et al. 2021; Aguilera and Quevedo 2011) avoids windup issues or linearization of the system for proper tuning of the PI controllers by eliminating the external PI-based dc-link voltage controller. However, MP-DPC is vulnerable to variations in model parameters. Work in Zhang et al. 2014b achieves a high control precision and error-free power control by eliminating steady-state errors and restrains power ripple, torque ripple and current harmonics of DFIG by using a three-vector based low-complexity model predictive direct power control (LC-MPDPC) strategy. DFIG operation under unbalanced grid conditions has to achieve the control targets of current harmonics and power and torque ripples. Research in Sun and Wang (2016) proposes a low-complexity model predictive direct power control (LC-MPDPC) strategy combined with power compensation. This provides a superior steady-state and dynamic performance for changes in control targets.
DFIG under unbalanced grid voltage conditions is controlled by the model predictive direct power control (MPDPC) method and a power compensation scheme (Hu et al. 2015), eliminating the need for coordinate transformation and extraction of negative stator sequence currents. This improves the power quality of stator currents injected into the grid and achieved excellent steady-state and dynamic performance.
3.1.6 Predictive direct power control (P-DPC)
For the combination and implementation of predictive control with the DPC approach, active voltage vector selection is indispensable and based on the knowledge of the position of the grid-voltage vector (Song et al. 2014). Authors in Bouafia et al. (2010) presented a deadbeat predictive DPC technique. Work in Zhi et al. (2010) and (Eltamaly et al. 2020) proposed P-DPC techniques with a predictive selection of voltage vector sequences. Active and reactive powers' values (predicted and the reference values) are utilized for framing the cost function, which is then minimized to calculate the action time sequence required for the switching signal. Work in Aguilera et al. (2013) proposed a generalized P-DPC strategy based on a cost-function minimization strategy for rectifiers by analyzing power characteristics. Research work in Hu and Zhu (2011) and (Hu and Zhu 2013) introduced compensation terms in the conventional P-DPC.
Predictive Direct Power Control with cost-function minimization (Song et al. 2014) achieves rapid dynamic response and excellent steady-state performance for three-phase grid-connected converters. An improved three-vectors-based P-DPC (Vazquez et al. 2015) has better overall harmonic performance and reduces both active and reactive power ripples. A new P-DPC controller, named optimal switching sequence, OSS-DPC (Hu 2013), has excellent closed-loop performance under transient and steady states by eliminating the problem of an optimal sequence selected from the grid voltage sector information. Dead-beat predictive DPC strategy (Martinez-Rodriguez et al. 2014) improves voltage vector sequences for reversible grid-connected converters.
An adaptive DPC (positive-sequence-based solution (pos-DPC)) (Kazemi et al. 2010) for a three-phase PWM rectifier guarantees robustness against parameter uncertainties under unbalanced grid voltage operation with adaptive laws. Authors in Zhang et al. 2014c propose a novel approach of a single switching table to realize three vectors for reducing active and reactive power ripples. This results in a simple and robust PDPC control structure with reduced switching frequency making it useful for high-power wind energy applications under unbalanced grid voltage. A comparison of the control as mentioned above strategies for PQ improvement for specific performance parameters shown in Table 2. Table 3 gives an overview of the advantages and disadvantages of the same.
3.1.7 Miscellaneous control strategies
Several other strategies are available in various literature, which are applicable to address the power quality of the DFIG wind energy system. Research work in Liu et al. (2013) implements a control methodology suitable for large-scale modular structure DFIG converters to control dc-link capacitor with reference to GSC of DFIG under unbalanced grid conditions. providing stability for DFIG even under step change in active grid output power at the DFIG terminals. A grid-voltage feed-forward adaptive current control (Vrionis et al. 2014) improves the controller performance for grid-connected LCL-filtered inverters in the weak grid. DC-Capacitor Current Control (Bejaoui et al. 2013) for GSC of DFIG is robust to the deviations in measuring the current of the dc-capacitor.
A Novel Control based on the linear-quadratic method (Hu et al. 2013) for the coordinated control of RSC and GSC of DFIG enables adaptation to special grid situations. Work in Nian and Song (2013) presents a Coordinated Control (proportional–integral regulator + dual-frequency resonant compensator) in the positive (dq) + reference frame for DFIG achieving RSC and GSC regulation for both the positive-/negative-sequence currents and fifth-/seventh-order harmonic currents. Optimized PI-R current regulator (Zhou et al. 2015) adopted under distorted grid voltage for the RSC of DFIG under fifth- and seventh-order sequences harmonic components ensures stable and reliable DFIG operation under distorted grid voltage conditions. A cost-effective internal model principle (IMP)-based optimal selective harmonic controller (Valouch et al. 2015) for grid-connected inverter compensates selected harmonic frequencies.
A current control technique (Cheng and Nian 2015) based on the extended reactive power theory for grid-connected converters eliminates power ripple, mitigates grid current harmonic distortion of grid currents and realizes simultaneous control of grid phase current peaks. A reduced-order generalized integrator (Maccari et al. 2015) for the RSC and GSC of DFIG has enhanced performance and high output power quality. A robust DLQR (Zhu et al. 2016) suitable for current control of grid-connected three-phase inverters ensures good tracking of reference and rejection of disturbances ensuring stability under grid parametric uncertainty and variations. Research work in Song and Nian 2015c presents a Dual-Loop Control Strategy (conventional current loop and an additional flux loop) for DFIG converters under grid Voltage Disturbances to improve stator active and reactive power and eliminate stator flux oscillations.
A modularized control strategy based on the VPI regulator for the DFIG system (Wang et al. 2016) avoids extraction of grid voltage negative and harmonic components. Work in Nian et al. (2016) presents a control strategy for voltage imbalance at the point of common coupling (PCC) for DFIG based on a resonant feedback regulator. It negates the generation of negative sequence rotor current references by providing direct rotor voltage reference. This results in independence from DFIG parameters. Moreover, the short-circuit ratio (SCR) at the PCC also taken into consideration. In (Cheng et al. 2017), for a DFIG under network unbalance, a direct stator current vector control strategy based on reduced-order vector integrator (ROVI) and PI controller employed. Instantaneous power theory commands the stator currents eliminating dependence on generator parameters. This improves the control, achieving control system stability, elimination of PLL, robustness against frequency disturbances and parameter deviations, and the rejection of voltage unbalance.
Work in Abulanwar et al. (2016) provides an advanced voltage control strategy for improving DFIG power quality connected in a weak grid. It implemented at the point of common coupling (PCC) of DFIG to the weak grid. It overcomes the voltage fluctuations at PCC and shows better damping for wind shear and tower effect oscillations. In (Yao et al. 2015) reference grid current replaces the grid current for use in grid current controller for three-phase grid-connected inverter, based on space vector pulse-width modulation (SVPWM). This achieves a waveform with better power quality and improves the dynamic response of the grid-connected inverter. Research work in Cai and Erlich (2015) provides an adaptive control strategy for grid side converter of DFIG connected in a weak grid. This is necessary to achieve controller stability and provide reinforcement to power system stability. The control analysis carried out for different grid weaknesses, assessed by online grid station measurement.
Authors in Yan et al. (2016) propose an improved grid-voltage feed-forward strategy based on a simplified repetitive predictor for compensating harmonics in grid-connected inverters caused by distorted grid voltage. It utilizes a second-order Butterworth low-pass filter in the conditioning circuit. It introduces three predictive steps considering delays in the conditioning circuit, control of the digital controller, and the zero-order hold ZOH characteristic of PWM, respectively. Work (Nian et al. 2015c) presents decoupled control of rotor-side converter (RSC) and grid-side converter (GSC) for a doubly fed induction generator (DFIG) under unbalanced grid voltage conditions using resonant regulators. Extracting positive and negative sequence components is not required leading to less computational load and system complexity. It also provides independence from generator parameters.
3.2 Energy utilization
DFIG wind energy system should provide synchronized power output such that the power generated is more reliable and cost-effective. The potential of a DFIG-WECS to provide secure and reliable energy to the consumers while maintaining its quality is enormous and has a significant bearing on its operations. Optimization achieved by improving operational performance and energy management, utilizing modern control techniques such as a centralized system controller. In this context, they benefit from using energy storage technologies (ESS) to provide electrical energy during high load demand periods for low wind speeds (Luo et al. 2015).
3.2.1 Energy storage technology (ESS)
It enables storing energy in various mediums and converts it back to its original form when necessary. Their integration is necessary for increased wind power penetration into the power systems (Luo et al. 2015). The energy storage devices can store the excess generated energy and supply the stored energy to the consumers when there is a shortage of power generation. ESS supplies a compensating power ΔPc for reducing or eliminating the wind power variability Pw, and maintaining power in the grid, Pgrid almost constant (Suberu et al. 2014).
ESS technologies’ integration is in the intermediate DC link of the DFIG wind energy system for power exchange and utilizes grid side converter as an interface (Wee et al. 2013). ESS is also utilized for stabilization of weak wind grid and helps steady-state and dynamic stability in a weak grid, and acts as an energy storage system during wind power curtailment.
In the case of a wind energy system linked to medium voltage distribution lines, wind power output equals the transmission capacity of the power grid, resulting in a weak grid connection with load-sensitive voltage control. Maturity of the technology, energy status, and socio-economic standards of a given site, its adaptation to the location of interest, any operational constraints and the supplier’s profile are detrimental to ESS implementation in a project (Lu et al. 2009). All the existing ESS technologies classified under different categories based on (Medina et al. 2014):
-
Time duration: Short-term, Medium-term, and Long-term.
-
Form of energy storage: Mechanical, Chemical, and Electrical.
There are several storage techniques in use today, depending on the needs of the power system. Some of the existing ESS technologies are compressed air energy storage (CAES), advanced adiabatic compressed air energy storage (AA-CAES), battery energy storage scheme (BESS), Super-capacitors, super magnetic energy storage (SMES), Flywheel, Pumped Storage and Hydrogen storage (Zhao et al. 2015). To achieve the future goal of delivering reliable power consistently, whatever the wind power generation, careful selection of ESS technologies with desired operation conditions and storage capacity and power ratings of the storage devices are required (Rodrigues et al. 2014).
Table 4 portrays the benefits of ESS in both technical and economic aspects. The introduction of EES as a grid code requirement is necessary in order to give freedom of choice to the power plant owners or the grid operator as regards the technology that matches the desired application. It is also necessary for a proper forecasting tool to support the decision process of specifying power and energy requirements of EES, for developing the optimum management of ESS, and to diminish the impacts of wind forecast errors more effectively.
3.2.2 Wind power forecasting
Accurate, reliable, online wind power forecasting methods are necessary due to the increasing penetration level of wind power into power systems. This enables power system operators to maintain the economical, efficient and secure operation of the power system. Wind power forecasting is essential to reduce reserve generation requirements, efficient provision of balancing services, efficient use of existing transmission, active management of wind and demand, and sizing dedicated storage technologies (Ren et al. 2014).
The wind power forecasting methods utilize physical and statistical models to attain the objective. The output of the wind power forecasting method is the wind power forecast, providing hourly predictions for look-ahead times up to 48 h. The forecasts can be provided for individual wind farms or all wind farms in a particular region or supply area (Zhang et al. 2014d; Dragoon 2010). The requirements for wind power forecasting methods can be outlined as follows:
-
The forecasts should be of wind power output (in MW), rather than wind speed, with look-ahead times extending to 48 h.
-
The forecasts should be readily available for individual wind farms, regional groupings of wind farms, and the total wind power installed in a TSO’s area.
-
The forecasts should be accurate and supplied with an associated level of confidence dispatchers tend to be more conservative when dealing with significant forecast uncertainties.
-
The forecast should predict changes in wind power reliably.
-
There should be a good understanding of the meteorological conditions, leading to poor quality forecasts.
-
Historical data should be used to improve the forecast over time.
Evaluation of wind power forecasts consists of four functions: performance assessment, model diagnosis, model selection, and model ranking (Zhang et al. 2014d; Wan et al. 2021). Figure 7 depicts the physical flow of information in a wind power forecasting system. The wind power forecasting methods can be classified based on time scale as follows:
-
Very-short term: seconds to minutes, applicable to wind turbine control and power system frequency control
-
Short-term: hours to days, applicable to economic dispatch, reserve requirements, day-ahead electricity market
-
Medium-term: days to weeks, applicable to unit commitment and maintenance scheduling
-
Long-term: weeks to months or years, wind power planning, and power system planning
3.2.2.1 Types of wind power forecasting methods
The first is the physical method that uses numerous physical considerations for the best forecasting accuracy. The second technique is a statistical method that attempts to determine the link between the online measured power data. This technique utilizes both classic statistical models (such as ARIMA models, ARCH models, Kalman Fitters (KF), etc.) and machine learning (ML) models (Artificial neutral networks—ANN, Support vector machine-SM) (Costa et al. 2008; Bazionis et al. 2022; González-Ordiano et al. 2021; Jiang et al. 2021; Wang et al. 2021; Wan et al. 2021; Du et al. 2019). Table 5 tries to project the advantages and drawbacks of forecasting approaches to ascertain an optimal approach for the appropriate application. Future wind power forecasting methods should consider the following factors to enable proper sizing of ESS technologies for application in wind energy systems:
-
(1)
Improving and extending physical, statistical, and hybrid forecasting approaches for reducing forecasting errors and enabling long-term planning.
-
(2)
Probabilistic forecasting and ensemble forecasts, with aid from several NWPs, improve accuracy in wind power forecasts and reduce reserve capacity (Xiao et al. 2015; González-Ordiano et al. 2021).
-
(3)
Forecasts at the regional level in order to evaluate any possible effects on the dependability of the system. The reference sites' choices and combinations should be considered in regional forecasting. Increasing the spatial and time resolution of NWPs, better taking into account local phenomena, would help to improve the forecast. Further research on automatic adaptive parameter estimation is required since wind speed and power forecasting are site-dependent (Jung and Broadwater 2014; Jiang et al. 2021).
-
(4)
Additional use of online wind measurement data has the potential for improved forecasts, especially for very short-term and short-term wind power forecasting.
-
(5)
New approaches for complex terrains to help improve forecasting accuracy.
-
(6)
It is also required to implement a new performance monitoring strategy that makes use of PMUs in order to monitor renewable energy facilities that are connected to the grid in real-time. The optimal PMU placement may also help to monitor the renewable energy systems in real-time and parallelly benefit in improving the power quality (Theodorakatos et al. 2020, 2021; Babu and Bhattacharyya 2015a, 2015b, 2015c, 2020; Babu et al. 2021, 2022a, 2022b, 2022c).
4 Conclusion and future scope
DFIGs and their competitive advantages make them the favorite choice for wind energy conversion systems that can be connected to large power networks. An overview of the various problems that are associated with the interconnection of the DFIG wind energy system in the electric grid has been provided in this article. Additionally, an attempt has been made to classify and summarise control strategies for DFIG power quality improvement in order to achieve increased wind power penetration in the electric grid. They could be extended for robust future grid operation with the support of ESS technologies improving the reliability of the wind energy system. Accommodation of new storage technologies takes into account an unprecedented number of options for energy production and consumption. ESS technologies aid wind power penetration in the following manner,
-
ESS with high power ramp rates helps smooth power wind power by mitigating the voltage and frequency variations at the connection point and strengthening the wind energy system. This improves the stability and enables ESS integration into grid codes.
-
Wind energy systems with ESS have improved penetration while maintaining a continuous power supply.
By reducing mistakes in wind power prediction, power reserve requirements can be reduced, making the ESS cost-effective. Research should focus on the coordination between the forecasting tools and the energy storage system to minimize the power imbalance and to ensure economic size optimization of the ESS. This would enable improved performance of the energy storage technologies. Power quality aspects in this regard cannot be overlooked, as in the near future the electric grid codes would be modified with respect to micro-grids, island grids and ESS technologies to qualify for integration in the primary electric grid for upholding the system reliability.
Further research for increased wind power penetration should address the following:
-
Advances in power electronic devices and control techniques.
-
Advancement in power converter topologies for minimizing power conversion losses in wind energy system configuration.
-
Enhanced supply of quality power by designing and implementing advanced control strategies.
-
Subsidy on renewable energy products from the state and central governments.
-
Focus on cost reduction of ESS technologies.
-
Improving and extending physical, statistical, and hybrid forecasting approaches with aid from several NWPs for reducing forecasting errors, reducing reserve capacity and enabling long-term planning.
-
Regional forecasting for the purpose of evaluating the possible influence on system dependability by employing automatic adaptive parameter estimates to cut down on the reliance on wind speed and power forecasts at the site.
-
New approaches for complex terrains for use in online wind measurement data for improving forecasting accuracy.
New regulations and policies, frequent extreme weather events, island grids, and utilization of utility grids as the backup to shape the future of DFIG wind energy systems to benefit both utility systems and individual consumers of energy safely and reliably. Successful operation and evolution of DFIG wind energy systems require using control strategies for PQ improvement assisted by ESS technologies and wind power forecasting methods to achieve optimum performance and provide grid resiliency to power quality issues.
Data and material availability
Not applicable
Code availability
Not applicable.
References
Abad G, Iwanski G (2014) Properties and control of a doubly fed induction machine. power electronics for renewable energy systems. Transp Ind Appl 270–318
Abdeddaim S, Betka A (2013) Optimal tracking and robust power control of the DFIG wind turbine. Int J Electr Power Energy Syst 49:234–242
Abo-Khalil AG, Lee DC, Jang JI (2007) Control of back-to-back PWM converters for DFIG wind turbine systems under unbalanced grid voltage. In: Industrial electronics, 2007. ISIE 2007. IEEE international symposium on 2007, IEEE, pp 2637–2642
Abulanwar S, Hu W, Chen Z, Iov F (2016) Adaptive voltage control strategy for variable-speed wind turbine connected to a weak network. IET Renew Power Gener 10(2):238–249
Abusara M, Sharkh S, Zanchetta P (2015) Adaptive repetitive control with feedforward scheme for grid-connected inverters. IET Power Electron 8(8):1403–1410
Ackermann T (ed) (2012) Wind power in power systems. Wiley, New Jersey
Agrawal S, Mohanty SR, Agarwal V (2015) Harmonics and inter harmonics estimation of DFIG based standalone wind power system by parametric techniques. Int J Electr Power Energy Syst 67:52–65
Aguilera RP, Quevedo DE (2011) On stability and performance of finite control set MPC for power converters. In: Predictive control of electrical drives and power electronics (PRECEDE), Workshop on 2011, IEEE, pp 55–62
Aguilera RP, Quevedo DE, Vázquez S, Franquelo LG (2013) Generalized predictive direct power control for ac/dc converters. In: ECCE Asia Downunder (ECCE Asia), IEEE, pp 1215–1220
Ahmed SD, Al-Ismail FSM, Shafiullah M, Al-Sulaiman FA, El-Amin IM (2020) Grid integration challenges of wind energy: a review. IEEE Access 8:10857–10878
Alam MS, Al-Ismail FS, Salem A, Abido MA (2020) High-level penetration of renewable energy sources into grid utility: challenges and solutions. IEEE Access 8:190277–190299
Ammar M, Venne P, Abbey C, Joos G (2011) A methodology for assessing the impact of distributed wind power on voltage flicker. In: CIGRE 2011 bologna symposium-the electric power system of the future: integrating supergrids and microgrids, September 13, 2011-September 15
Arif B, Tarisciotti L, Zanchetta P, Clare JC, Degano M (2015) Grid parameter estimation using model predictive direct power control. IEEE Trans Ind Appl 51(6):4614–4622
Babaei E, Kangarlu MF, Sabahi M (2010) Mitigation of voltage disturbances using dynamic voltage restorer based on direct converters. IEEE Trans Power Delivery 25(4):2676–2683
Babu R, Bhattacharyya B (2020) Optimal placement of PMU for complete observability of the interconnected power network considering zero-injection bus: a numerical approach. Int J Appl Power Eng 9(2):135–146
Babu R, Raj S, Dey B, Bhattacharyya B (2021) Modified branch-and-bound algorithm for unravelling optimal PMU placement problem for power grid observability: a comparative analysis. CAAI Trans Intell Technol 6(4):450–470
Babu R, Gupta VK, Subbaramaiah K (2022a) An approach to unravel the optimal PMU placement problem for full observability of power network in view of contingencies. Int J Syst Assur Eng Manag 13(3):1170–1186
Babu R, Raj S, Dey B, Bhattacharyya B (2022b) Optimal reactive power planning using oppositional grey wolf optimization by considering bus vulnerability analysis. Energy Convers Econ 3(1):38–49
Babu R, Kumar V, Shiva CK, Raj S, Bhattacharyya B (2022c) Application of sine-cosine optimization algorithm for minimization of transmission loss. Technol Econ Smart Grids Sustain Energy 7(1):1–12
Babu R, Bhattacharyya, B (2015a) Optimal placement of phasor measurement unit using binary particle swarm optimization in connected power network. In: 2015a IEEE UP section conference on electrical computer and electronics (UPCON), IEEE, pp 1–5
Babu Rohit, Biplab Bhattacharyya (2015b). Phasor measurement unit allocation with different soft computing technique inconnected power network 110–117
Babu R, Bhattacharyya B (2015c) Allocation of phasor measurement unit using A-star method in connected power network. In 2015c IEEE workshop on computational intelligence: theories, applications and future directions (WCI), IEEE, pp 1–6
Baggu MM, Chowdhury BH, Kimball JW (2015) Comparison of advanced control techniques for grid side converter of doubly-fed induction generator back-to-back converters to improve power quality performance during unbalanced voltage dips. IEEE J Emerg Sel Top Power Electron 3(2):516–524
Bazionis IK, Karafotis PA, Georgilakis PS (2022) A review of short-term wind power probabilistic forecasting and a taxonomy focused on input data. IET Renew Power Gener 16(1):77–91
Bejaoui M, Marinescu B, Slama-Belkhodja I, Monmasson E (2013) Control of doubly-fed induction generator for wind energy in network context. IET Renew Power Gener 8(2):109–118
Bevrani H, Ghosh A, Ledwich G (2010) Renewable energy sources and frequency regulation: survey and new perspectives. IET Renew Power Gener 4(5):438–457
Bouafia A, Gaubert JP, Krim F (2010) Predictive direct power control of three-phase pulsewidth modulation (PWM) rectifier using space-vector modulation (SVM). IEEE Trans Power Electron 25(1):228–236
Cai LJ, Erlich I (2015) Doubly fed induction generator controller design for the stable operation in weak grids. IEEE Trans Sustain Energy 6(3):1078–1084
Camacho EF, Alba CB (2013) Model predictive control. Springer
Cardenas R, Peña R, Alepuz S, Asher G (2013) Overview of control systems for the operation of DFIGs in wind energy applications. IEEE Trans Ind Electron 60(7):2776–2798
Carpinone A, Langella R, Testa A, Giorgio M (2010) Very short-term probabilistic wind power forecasting based on Markov chain models. In: Probabilistic methods applied to power systems (PMAPS), 2010 IEEE 11th international conference on 2010, IEEE, pp 107–112
Chen D, Zhang J, Qian Z (2013) Research on fast transient and 6n±1 harmonics suppressing repetitive control scheme for three-phase grid-connected inverters. IET Power Electron 6(3):601–610
Chen X, Mcelroy MB, Wu Q, Shu Y, Xue Y (2019) Transition towards higher penetration of renewables: an overview of interlinked technical, environmental and socio-economic challenges. J Modern Power Syst Clean Energy 7(1):1–8
Cheng P, Nian H (2015) Collaborative control of DFIG system during network unbalance using reduced-order generalized integrators. IEEE Trans Energy Convers 30(2):453–464
Cheng P, Nian H, Wu C, Zhu ZQ (2017) Direct stator current vector control strategy of DFIG without phase-locked loop during network unbalance. IEEE Trans Power Electron 32(1):284–297
Cortes P, Rodriguez J, Silva C, Flores A (2012) Delay compensation in model predictive current control of a three-phase inverter. IEEE Trans Ind Electron 59(2):1323–1325
Costa A, Crespo A, Navarro J, Lizcano G, Madsen H, Feitosa E (2008) A review on the young history of the wind power short-term prediction. Renew Sustain Energy Rev 12(6):1725–1744
Datta R, Ranganathan VT (2002) Variable-speed wind power generation using doubly fed wound rotor induction machine-a comparison with alternative schemes. IEEE Trans Energy Convers 17(3):414–421
Díaz-González F, Sumper A, Gomis-Bellmunt O, Villafáfila-Robles R (2012) A review of energy storage technologies for wind power applications. Renew Sustain Energy Rev 16(4):2154–2171
Djerioui A, Aliouane K, Bouchafaa F (2014) Sliding mode direct power control strategy of a power quality based on a sliding mode observer. Int J Electr Power Energy Syst 56:325–331
Dragoon K (2010) Valuing wind generation on integrated power systems. William Andrew
Du P, Wang J, Yang W, Niu T (2019) A novel hybrid model for short-term wind power forecasting. Appl Soft Comput 80:93–106
Eltamaly AM, Al-Saud MS, Abo-Khalil AG (2020) Dynamic control of a dfig wind power generation system to mitigate unbalanced grid voltage. IEEE Access 8:39091–39103
Errouissi R, Al-Durra A, Muyeen SM, Leng S, Blaabjerg F (2017) Offset-free direct power control of DFIG under continuous-time model predictive control. IEEE Trans Power Electron 32(3):2265–2277
Escobar G, Hernandez-Briones PG, Martinez PR, Hernandez-Gomez M, Torres-Olguin RE (2008) A repetitive-based controller for the compensation of 6l+/-1 harmonic components. IEEE Transact Ind Electron 55(8):3150–3158
Estrada L, Vazquez N, Vaquero J, Hernandez C, Arau J, Huerta H (2021) Finite control set – model predictive control based on sliding mode for bidirectional power inverter. IEEE Trans Energy Convers 36(4):2814–2824
Etxegarai A, Eguia P, Torres E, Iturregi A, Valverde V (2015) Review of grid connection requirements for generation assets in weak power grids. Renew Sustain Energy Rev 41:1501–1514
Farias MF, Battaiotto PE, Cendoya MG (2010) Wind farm to weak-grid connection using UPQC custom power device. In: Industrial technology (ICIT), 2010 IEEE international conference on 2010, IEEE, pp 1745–1750
Farshadnia M, Taher SA (2014) Current-based direct power control of a DFIG under unbalanced grid voltage. Int J Electr Power Energy Syst 62:571–582
Fathabadi H (2014) Control of a DFIG-based wind energy conversion system operating under harmonically distorted unbalanced grid voltage along with nonsinusoidal rotor injection conditions. Energy Convers Manag 84:60–72
Feltes JW, Fernandes BS (2012) Wind turbine generator dynamic performance with weak transmission grids. In: Power and energy society general meeting, 2012, IEEE, pp 1–7
Gao S, Zhao H, Gui Y, Zhou D, Terzija V, Blaabjerg F (2021a) A novel direct power control for DFIG with parallel compensator under unbalanced grid condition. IEEE Trans Industr Electron 68(10):9607–9618
Gao S, Zhao H, Gui Y, Zhou D, Blaabjerg F (2021b) An improved direct power control for doubly fed induction generator. IEEE Trans Power Electron 36(4):4672–4685
Georgilakis PS (2008) Technical challenges associated with the integration of wind power into power systems. Renew Sustain Energy Rev 12(3):852–863
Glover et al. 2012Glover JD, Sarma MS, Overbye T (2012) Power system analysis & design, SI version. Cengage Learning
González-Ordiano JÁ, Mühlpfordt T, Braun E, Liu J, Çakmak H, Kühnapfel U, Düpmeier C et al (2021) Probabilistic forecasts of the distribution grid state using data-driven forecasts and probabilistic power flow. Appl Energy 302:117498
Hemdani A, Dagbagi M, Naouar WM, Idkhajine L, Belkhodja IS, Monmasson E (2015) Indirect sliding mode power control for three phase grid connected power converter. IET Power Electron 8(6):977–985
Herbert GJ, Iniyan S, Sreevalsan E, Rajapandian S (2007) A review of wind energy technologies. Renew Sustain Energy Rev 11(6):1117–1145
Hornik T, Zhong QC (2011) A current-control strategy for voltage-source inverters in microgrids based on H∞ and repetitive control. IEEE Trans Power Electron 26(3):943–952
Hu J (2013) Improved dead-beat predictive DPC strategy of grid-connected DC–AC converters with switching loss minimization and delay compensations. IEEE Trans Industr Inf 9(2):728–738
Hu J, Zhu ZQ (2011) Investigation on switching patterns of direct power control strategies for grid-connected DC–AC converters based on power variation rates. IEEE Trans Power Electron 26(12):3582–3598
Hu J, Zhu ZQ (2013) Improved voltage-vector sequences on dead-beat predictive direct power control of reversible three-phase grid-connected voltage-source converters. IEEE Trans Power Electron 28(1):254–267
Hu J, Xu H, He Y (2013) Coordinated control of DFIG’s RSC and GSC under generalized unbalanced and distorted grid voltage conditions. IEEE Trans Industr Electron 60(7):2808–2819
Hu J, Zhu J, Dorrell DG (2015) Predictive direct power control of doubly fed induction generators under unbalanced grid voltage conditions for power quality improvement. IEEE Transactions on Sustainable Energy 6(3):943–950
International Electrotechnical Commission, IEC (2008) 61000–3–7. Electromagnetic Compatibility (EMC), Part 3: Limits –Section 7: assessment of emission limits for the connection of fluctuating installations to MV, HV and EHV power systems, 2nd ed
Jiang P, Liu Z, Niu X, Zhang L (2021) A combined forecasting system based on statistical method, artificial neural networks, and deep learning methods for short-term wind speed forecasting. Energy 217:119361
Jung J, Broadwater RP (2014) Current status and future advances for wind speed and power forecasting. Renew Sustain Energy Rev 31:762–777
Kang SW, Kim KH (2015) Sliding mode harmonic compensation strategy for power quality improvement of a grid-connected inverter under distorted grid condition. IET Power Electron 8(8):1461–1472
Kanjiya P, Ambati BB, Khadkikar V (2014) A novel fault-tolerant DFIG-based wind energy conversion system for seamless operation during grid faults. IEEE Trans Power Syst 29(3):1296–1305
Kasem AH, El-Saadany EF, El-Tamaly HH, Wahab MA (2010) Power ramp rate control and flicker mitigation for directly grid connected wind turbines. IET Renew Power Gener 4(3):261–271
Kassem AM, Hasaneen KM, Yousef AM (2013) Dynamic modeling and robust power control of DFIG driven by wind turbine at infinite grid. Int J Electr Power Energy Syst 44(1):375–382
Kazemi MV, Yazdankhah AS, Kojabadi HM (2010) Direct power control of DFIG based on discrete space vector modulation. Renew Energy 35(5):1033–1042
Kurniawan E, Cao Z, Man Z (2014) Design of robust repetitive control with time-varying sampling periods. IEEE Trans Ind Electron 61(6):2834–2841
Li L, Nian H, Ding L, Zhou B (2018) Direct power control of DFIG system without phase-locked loop under unbalanced and harmonically distorted voltage. IEEE Trans Energy Convers 33(1):395–405
Liu X, Kong X (2014a) Nonlinear model predictive control for DFIG-based wind power generation. IEEE Trans Autom Sci Eng 11(4):1046–1055
Liu X, Kong X (2014b) Nonlinear model predictive control for DFIG-based wind power generation. IEEE Transactions on Autom Sci Eng 11(4):1046–1055
Liu C, Xu D, Zhu N, Blaabjerg F, Chen M (2013) DC-voltage fluctuation elimination through a DC-capacitor current control for DFIG converters under unbalanced grid voltage conditions. IEEE Trans Power Electron 28(7):3206–3218
Liu T, Xia C, Shi T (2014) Robust model predictive current control of grid-connected converter without alternating current voltage sensors. IET Power Electron 7(12):2934–2944
Lopez J, Sanchis P, Roboam X, Marroyo L (2007) Dynamic behavior of the doubly fed induction generator during three-phase voltage dips. IEEE Trans Energy Convers 22(3):709–717
Lu MS, Chang CL, Lee WJ, Wang L (2009) Combining the wind power generation system with energy storage equipment. IEEE Trans Ind Appl 45(6):2109–2115
Lu W, Zhou K, Wang D, Cheng M (2014) A generic digital nk±m order harmonic repetitive control scheme for PWM converters. IEEE Trans Ind Electron 61(3):1516–1527
Luo X, Wang J, Dooner M, Clarke J (2015) Overview of current development in electrical energy storage technologies and the application potential in power system operation. Appl Energy 137:511–536
Maccari LA, do Amaral Santini CL, Pinheiro H, de Oliveira RC, Montagner VF (2015) Robust optimal current control for grid-connected three-phase pulse-width modulated converters. IET Power Electron 8(8):1490–9
Martinez MI, Tapia G, Susperregui A, Camblong H (2012) Sliding-mode control for DFIG rotor-and grid-side converters under unbalanced and harmonically distorted grid voltage. IEEE Trans Energy Convers 27(2):328–339
Martinez MI, Susperregui A, Tapia G, Xu L (2013) Sliding-mode control of a wind turbine-driven double-fed induction generator under non-ideal grid voltages. IET Renew Power Gener 7(4):370–9
Martinez-Rodriguez PR, Escobar G, Valdez-Fernandez AA, Hernandez-Gomez M, Sosa JM (2014) Direct power control of a three-phase rectifier based on positive sequence detection. IEEE Trans Industr Electron 61(8):4084–4092
Medina P, Bizuayehu AW, Catalão JP, Rodrigues EM, Contreras J (2014) Electrical energy storage systems: technologies' state-of-the-art, techno-economic benefits and applications analysis. In: System sciences (HICSS), 2014 47th Hawaii international conference on 2014 IEEE, pp 2295–2304
Mohammadi J, Vaez-Zadeh S, Afsharnia S, Daryabeigi E (2014) A combined vector and direct power control for DFIG-based wind turbines. IEEE Trans Sustain Energy 5(3):767–775
Nian H, Song Y (2013) Optimised parameter design of proportional integral and resonant current regulator for doubly fed induction generator during grid voltage distortion. IET Renew Power Gener 8(3):299–313
Nian H, Quan Y, Hu J (2012) Improved control strategy of DFIG-based wind power generation systems connected to a harmonically polluted network. Electric Power Syst Res 86:84–97
Nian H, Shen Y, Yang H, Quan Y (2015a) Flexible grid connection technique of voltage-source inverter under unbalanced grid conditions based on direct power control. IEEE Trans Ind Applications 51(5):4041–4050
Nian H, Cheng P, Zhu Z (2015b) Direct power control of doubly fed induction generator without phase-locked loop in synchronous reference frame during frequency variations. IET Renew Power Gener 9(6):576–586
Nian H, Cheng P, Zhu ZQ (2015c) Independent operation of DFIG-based WECS using resonant feedback compensators under unbalanced grid voltage conditions. IEEE Trans Power Electron 30(7):3650–3661
Nian H, Wang T, Zhu ZQ (2016) Voltage imbalance compensation for doubly fed induction generator using direct resonant feedback regulator. IEEE Trans Energy Conver 31(2):614–626
Pande VN, Mate UM, Kurode S (2013) Discrete sliding mode control strategy for direct real and reactive power regulation of wind driven DFIG. Electr Power Syst Res 100:73–81
Patnaik RK, Dash PK (2016) Fast adaptive back-stepping terminal sliding mode power control for both the rotor-side as well as grid-side converter of the doubly fed induction generator-based wind farms. IET Renew Power Gener 10(5):598–610
Pavlou KG, Vasiladiotis M, Manias SN (2012) Constrained model predictive control strategy for single-phase switch-mode rectifiers. IET Power Electron 5(1):31–40
Pepermans G, Driesen J, Haeseldonckx D, Belmans R, D’haeseleer W (2005) Distributed generation: definition, benefits and issues. Energy policy 33(6):787–98
Polinder H, Van der Pijl FF, De Vilder GJ, Tavner PJ (2006) Comparison of direct-drive and geared generator concepts for wind turbines. IEEE Trans Energy Convers 21(3):725–733
Rahoui A, Bechouche A, Seddiki H, Ould Abdeslam D (2021) Virtual flux estimation for sensorless predictive control of PWM rectifiers under unbalanced and distorted grid conditions. In: IEEE journal of emerging and selected topics in power electronics, vol 9, no 2, pp 1923–1937
Ran X, Bo Xu, Liu K, Zhang J (2021) An improved low-complexity model predictive direct power control with reduced power ripples under unbalanced grid conditions. IEEE Trans Power Electron 37(5):5224–5234
Razali AM, Rahman MA, George G, Rahim NA (2015) Analysis and design of new switching lookup table for virtual flux direct power control of grid-connected three-phase PWM AC–DC converter. IEEE Trans Ind Appl 51(2):1189–1200
Ren C, An N, Wang J, Li L, Hu B, Shang D (2014) Optimal parameters selection for BP neural network based on particle swarm optimization: a case study of wind speed forecasting. Knowl Based Syst 56:226–239
Ren21 R (2016). Global status report. Renewable energy policy network for the 21st century. https://www.ren21.net Accessed. 2016
Rodrigues EMG et al (2014) Energy storage systems supporting increased penetration of renewables in islanded systems. Energy 75:265–280
Rodríguez J, Kennel RM, Espinoza JR, Trincado M, Silva CA, Rojas CA (2012) High-performance control strategies for electrical drives: an experimental assessment. IEEE Trans Ind Electron 59(2):812–820
Rodriguez J, Kazmierkowski MP, Espinoza JR, Zanchetta P, Abu-Rub H, Young HA, Rojas CA (2013) State of the art of finite control set model predictive control in power electronics. IEEE Trans Ind Inform 9(2):1003–1016
Rodríguez Amenedo JL, Burgos Díaz JC, Arnalte Gómez S (2003) Sistemas eólicos de producción de energía eléctrica. Rueda
Rojas CA, Rodriguez J, Villarroel F, Espinoza JR, Silva CA, Trincado M (2013) Predictive torque and flux control without weighting factors. IEEE Trans Ind Electron 60(2):681–690
Saqib MA, Saleem AZ (2015) Power-quality issues and the need for reactive-power compensation in the grid integration of wind power. Renew Sustain Energy Rev 43:51–64
Sha D, Wu D, Liao X (2011) Analysis of a hybrid controlled three-phase grid-connected inverter with harmonics compensation in synchronous reference frame. IET Power Electron 4(7):743–751
Shafiullah GM, Oo AM, Ali AS, Wolfs P (2013) Potential challenges of integrating large-scale wind energy into the power grid–a review. Renew Sustain Energy Rev 20:306–321
Shehata EG (2015) Sliding mode direct power control of RSC for DFIGs driven by variable speed wind turbines. Alex Eng J 54(4):1067–1075
Shi X, Zhu J, Li L and Dah-Chuan LU D (2020) Low-complexity dual-vector-based predictive control of three-phase PWM rectifiers without duty-cycle optimization. In: IEEE Access, vol 8, pp 77049–77059
Shtessel Y, Edwards C, Fridman L, Levant A (2014) Sliding mode control and observation. Birkhäuser, New York
Song Y, Nian H (2015a) Enhanced grid-connected operation of DFIG using improved repetitive control under generalized harmonic power grid. IEEE Trans Energy Convers 30(3):1019–1029
Song Y, Nian H (2015b) Sinusoidal output current implementation of DFIG using repetitive control under a generalized harmonic power grid with frequency deviation. IEEE Trans Power Electron 30(12):6751–6762
Song Y, Nian H (2015c) Modularized control strategy and performance analysis of DFIG system under unbalanced and harmonic grid voltage. IEEE Trans Power Electron 30(9):4831–4842
Song Z, Xia C, Liu T (2013) Predictive current control of three-phase grid-connected converters with constant switching frequency for wind energy systems. IEEE Trans Ind Electron 60(6):2451–2464
Song Z, Chen W, Xia C (2014) Predictive direct power control for three-phase grid-connected converters without sector information and voltage vector selection. IEEE Trans Power Electron 29(10):5518–5531
Standard IE (2001) 61000-4-21 Wind turbine generator systems—part 21: measurement and assessment of power quality characteristics of grid connected wind turbines. International Electrotechnical Commission. 2001.
Suberu MY, Mustafa MW, Bashir N (2014) Energy storage systems for renewable energy power sector integration and mitigation of intermittency. Renew Sustain Energy Rev 35:499–514
Sun D, Wang X (2016) Low-complexity model predictive direct power control for DFIG under both balanced and unbalanced grid conditions. IEEE Trans Industr Electron 63(8):5186–5196
Sun T, Chen Z, Blaabjerg F (2005) Flicker study on variable speed wind turbines with doubly fed induction generators. IEEE Trans Energy Convers 20(4):896–905
Susperregui A, Jugo J, Lizarraga I, Tapia G (2014) Automated control of doubly fed induction generator integrating sensorless parameter estimation and grid synchronisation. IET Renew Power Gener 8(1):76–89
Tamvada K (2021)Transient control of DFIG rotor side converter, In: 2021 International Conference on Electrical, Computer, Communications and Mechatronics Engineering (ICECCME), pp. 1–6
Tande JO (2005) Power quality standards for wind turbines. Wind power in power systems. vol 8, p 79
Tande JO, Di Marzio G, Uhlen K (2007) System requirements for wind power plants. SINTEF Energy Res
Tascikaraoglu A, Uzunoglu M (2014) A review of combined approaches for prediction of short-term wind speed and power. Renew Sustain Energy Rev. 34:243–254
Teodorescu R, Liserre M, Rodriguez P (2011) Grid converters for photovoltaic and wind power systems. Wiley
Theodorakatos NP, Lytras M, Babu R (2020) Towards smart energy grids: a box-constrained nonlinear underdetermined model for power system observability using recursive quadratic programming. Energies 13(7):1724
Theodorakatos NP, Lytras M, Babu R 2021 A generalized pattern search algorithm methodology for solving an under-determined system of equality constraints to achieve power system observability using synchrophasors. In: Journal of physics: conference series, IOP Publishing, Vol 2090, No. 1, p 012125
Tohidi S, Behnam MI (2016) A comprehensive review of low voltage ride through of doubly fed induction wind generators. Renew Sustain Energy Rev 57:412–419
Trinh QN, Lee HH (2014) An enhanced grid current compensator for grid-connected distributed generation under nonlinear loads and grid voltage distortions. IEEE Trans Indust Electron 61(12):6528–6537
Valouch V, Bejvl M, Šimek P, Škramlík J (2015) Power control of grid-connected converters under unbalanced voltage conditions. IEEE Trans Industr Electron 62(7):4241–4248
Vazquez S, Marquez A, Aguilera R, Quevedo D, Leon JI, Franquelo LG (2015) Predictive optimal switching sequence direct power control for grid-connected power converters. IEEE Trans Industr Electron 62(4):2010–2020
Vidal J, Abad G, Arza J, Aurtenechea S (2013) Single-phase DC crowbar topologies for low voltage ride through fulfillment of high-power doubly fed induction generator-based wind turbines. IEEE Trans Energy Convers 28(3):768–781
Vrionis TD, Koutiva XI, Vovos NA (2014) A genetic algorithm-based low voltage ride-through control strategy for grid connected doubly fed induction wind generators. IEEE Trans Power Syst 29(3):1325–1334
Wan C, Qian W, Zhao C, Song Y, Yang G (2021) Probabilistic forecasting based sizing and control of hybrid energy storage for wind power smoothing. IEEE Trans Sustain Energy 12(4):1841–1852
Wang Y, Gao F, Doyle FJ III (2009) Survey on iterative learning control, repetitive control, and run-to-run control. J Process Control 19(10):1589–600
Wang J, Yan JD, Jiang L (2016) Pseudo-derivative-feedback current control for three-phase grid-connected inverters with LCL filters. IEEE Trans Power Electron 31(5):3898–3912
Wang Y, Zou R, Liu F, Zhang L, Liu Q (2021) A review of wind speed and wind power forecasting with deep neural networks. Appl Energy 304:117766
Wee KW, Choi SS, Vilathgamuwa DM (2013) Design of a least-cost battery-supercapacitor energy storage system for realizing dispatchable wind power. IEEE Trans Sustain Energy 4(3):786–796
Wieland P, Sepulchre R, Allgöwer F (2011) An internal model principle is necessary and sufficient for linear output synchronization. Automatica 47(5):1068–1074
Xiao L, Wang J, Dong Y, Wu J (2015) Combined forecasting models for wind energy forecasting: a case study in China. Renew Sustain Energy Rev 44:271–288
Xiao X, Zhang Y, Wang J, Du H (2016) An improved model predictive control scheme for the PWM rectifier-inverter system based on power-balancing mechanism. IEEE Trans Industr Electron 63(8):5197–5208
Xiao D, Alam KS, Norambuena M, Rahman MF, Rodriguez J (2021) Modified modulated model predictive control strategy for a grid-connected converter. IEEE Trans Industr Electron 68(1):575–585
Xiaodong Y, Zhi W, Qun L, Jiankun L, Jingbo Z, Wei G. Simulation and analysis of wind farm reactive power and voltage problems based on detailed model. In Electricity Distribution (CICED), 2010 China International Conference on 2010 (pp. 1–7). IEEE.
Xie D, Xu Z, Yang L, Østergaard J, Xue Y, Wong KP (2013) A comprehensive LVRT control strategy for DFIG wind turbines with enhanced reactive power support. IEEE Trans Power Syst 28(3):3302–3310
Xiong P, Sun D (2016) Backstepping-based DPC strategy of a wind turbine-driven DFIG under normal and harmonic grid voltage. IEEE Trans Power Electron 31(6):4216–4225
Yan Q, Wu X, Yuan X, Geng Y (2016) An improved grid-voltage feedforward strategy for high-power three-phase grid-connected inverters based on the simplified repetitive predictor. IEEE Trans Power Electro 31(5):3880–3897
Yan S, Chen J, Yang T, Hui SY (2019) Improving the performance of direct power control using duty cycle optimization. IEEE Trans Power Electron 34(9):9213–9223
Yan S, Yang Y, Hui SY, Blaabjerg F (2021) A review on direct power control of pulse-width modulation converters. IEEE Trans Power Electron 36(10):11984–12007
Yang L, Xu Z, Ostergaard J, Dong ZY, Wong KP (2012) Advanced control strategy of DFIG wind turbines for power system fault ride through. IEEE Trans Power Syst 27(2):713–722
Yao Z, Xiao L, Guerrero JM (2015) Improved control strategy for the three-phase grid-connected inverter. IET Renew Power Gener 9(6):587–92
Yin L, Zhao Z, Lu T, Yang S, Zou G (2014) An improved DC-link voltage fast control scheme for a PWM rectifier-inverter system. IEEE Trans Ind Appl 50(1):462–473
Yongchang Z, Jiang T (2021) Robust predictive stator current control based on prediction error compensation for a doubly fed induction generator under non-ideal grids. IEEE Trans Industr Electron 69(5):4398–4408
Zhang Y, Jiang T (2021) Robust predictive rotor current control of a doubly fed induction generator under an unbalanced and distorted grid. IEEE Trans Energy Convers 37(1):433–442
Zhang Y, Qu C (2015a) Direct power control of a pulse width modulation rectifier using space vector modulation under unbalanced grid voltages. IEEE Trans Power Electron 30(10):5892–5901
Zhang Y, Qu C (2015b) Model predictive direct power control of PWM rectifiers under unbalanced network conditions. IEEE Trans Industr Electron 62(7):4011–4022
Zhang Y, Xie W, Li Z, Zhang Y (2013) Model predictive direct power control of a PWM rectifier with duty cycle optimization. IEEE Trans Power Electron 28(11):5343–5351
Zhang Y, Xie W, Li Z, Zhang Y (2014a) Low-complexity model predictive power control: double-vector-based approach. IEEE Trans Ind Electron 61(11):5871–5880
Zhang Y, Xie W, Li Z, Zhang Y (2014b) Low-complexity model predictive power control: double-vector-based approach. IEEE Trans Industr Electron 61(11):5871–5880
Zhang Y, Hu J, Zhu J (2014c) Three-vectors-based predictive direct power control of the doubly fed induction generator for wind energy applications. IEEE Trans Power Electron 29(7):3485–3500
Zhang Y, Wang J, Wang X (2014d) Review on probabilistic forecasting of wind power generation. Renew Sustain Energy Rev 32:255–270
Zhang Y, Jiao J, Xu D (2019a) Direct power control of doubly fed induction generator using extended power theory under unbalanced network. IEEE Trans Power Electron 34(12):12024–12037
Zhang Y, Jiao J, Liu J (2019b) Direct power control of PWM rectifiers with online inductance identification under unbalanced and distorted network conditions. IEEE Trans Power Electron 34(12):12524–12537
Zhang Y, Wang Z, Jiao J, Liu J (2020) Grid-voltage sensorless model predictive control of three-phase PWM rectifier under unbalanced and distorted grid voltages. IEEE Trans Power Electron 35(8):8663–8672
Zhao H, Wu Q, Hu S, Xu H (2015) Rasmussen CN. Review of energy storage system for wind power integration support. Appl Energy 137:545–553
Zhi D, Xu L, Williams BW (2010) Model-based predictive direct power control of doubly fed induction generators. IEEE Trans Power Electron 25(2):341–351
Zhong QC, Hornik T (2013) Cascaded current–voltage control to improve the power quality for a grid-connected inverter with a local load. IEEE Trans Ind Electron 60(4):1344–1355
Zhou K, Yang Y, Blaabjerg F, Wang D (2015) Optimal selective harmonic control for power harmonics mitigation. IEEE Trans Industr Electron 62(2):1220–1230
Zhu R, Chen Z, Tang Y, Deng F, Wu X (2016) Dual-loop control strategy for DFIG-based wind turbines under grid voltage disturbances. IEEE Trans Power Electron 31(3):2239–2253
Zin AA, HA MP, Khairuddin AB, Jahanshaloo L, Shariati O (2013) An overview on doubly fed induction generators, controls and contributions to wind based electricity generation. Renew Sustain Energy Rev 27:692–708
Zou Y, Elbuluk ME, Sozer Y (2013) Simulation comparisons and implementation of induction generator wind power systems. IEEE Trans Ind Appl 49(3):1119–1128
Funding
Not applicable.
Author information
Authors and Affiliations
Contributions
The paper was designed by the first author, and the work of the article was approved by the second author.
Corresponding author
Ethics declarations
Conflicts of interest
Not applicable.
Additional information
Publisher's Note
Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.
Rights and permissions
Springer Nature or its licensor holds exclusive rights to this article under a publishing agreement with the author(s) or other rightsholder(s); author self-archiving of the accepted manuscript version of this article is solely governed by the terms of such publishing agreement and applicable law.
About this article
Cite this article
Tamvada, K., Babu, R. Control of doubly fed induction generator for power quality improvement: an overview. Int J Syst Assur Eng Manag 13, 2809–2832 (2022). https://doi.org/10.1007/s13198-022-01754-7
Received:
Revised:
Accepted:
Published:
Issue Date:
DOI: https://doi.org/10.1007/s13198-022-01754-7