1 Introduction

Harmonics, which are caused by nonlinear loads and occur at frequencies that are multiples of the grid frequency, are important quality parameters for today's power systems. They cause heating in cables, increase in dielectric losses and malfunctions in the systems. Solid insulators are materials that are widely used in electrical networks, electrical equipment and substations. They are vital for power equipment as they separate the conductive parts from each other and from the ground, provide mechanical support and protect the equipment from other external influences. Material selection and insulation system design should be done meticulously for the reliability, continuity and economy of power systems. Tests to determine parameters such as lifetime, partial discharge values, puncture strength, dissipation factor, which are of great importance for the selection of insulation material, are carried out on the basis of pure sinusoidal voltages [1]. However, power systems are not ideal. Current and voltage wave forms contain harmonic components. It should not be forgotten that the selected material will be forced by harmonic components as well as its nominal value, and when evaluating its dielectric properties, the electrical stress of the bonds between PE molecules along with the harmonic effect should also be taken into account [2, 3]. For example, it has been observed that if the voltage applied to the insulation material contains more than a certain percentage of harmonic content, the breakdown can occur even if the breakdown voltage of the relevant material is not reached [4, 5].

In a study examining harmonic distortions that contribute to the formation of electrical trees in XLPE cables, the effect of 5th order harmonics on the reduction of cable life has been clarified. In addition, the classification of the electric trees (ET) formed for harmonic and non-harmonic cases has been made [6, 7]. In another study, the effects of 3–5 and 7th order harmonics on partial discharge (PD) measurements have been revealed and the observed negative effect on the life of the cable is presented [8, 9]. Meanwhile, in the study examining the breakdown of materials by Birle used as insulation material in power cables by harmonic distortion voltage, dielectric losses were used to compare insulators [10]. In addition, the negative effects that may occur during the operation of direct current (DC) cables used in submarine power transmission have been simulated with the help of a mathematical model. Problems that may occur during operation with the resonance effect of harmonic components have been examined and it has been stated that there is a significant difference in behavior between steel armored cables and copper armored cables [11]. The effect of DC voltages overlapping with characteristic harmonics on PD activity and ET developments in DC XLPE dielectric test samples has experimentally investigated by Fard [12]. In general, it was stated that the structure of the developing electric trees and the related PD activity depends on the waveform, harmonic content and polarity of the applied measurement voltages. It is concluded that in the case of alternating voltage, the synergic effect of the accumulated field loads and the electric field exposed by the external voltage source is more likely to start an electrical tree than conditions under pure DC voltages [12, 13]. In addition to this, it has been stated that with the increase of the 3–5-7–11 and 13th total harmonic distortion (THD) ratio generated by the power electronics equipment, the partial discharge initial voltage (PDIV) value decreases and the PD amplitude value increases [14]. In a study investigating the breakdown effect of harmonics occurring at different phase angles under different voltage types on cable samples with artificial defects, it was stated that DC voltages have a distorting effect. Secondly, it was concluded that the impulse voltages came and the alternating current (AC) voltages were the last to affect the least [15, 16].

An experimental study dealing with harmonic distortion of the voltage applied to cardboard samples showed that dielectric losses are not only due to the fundamental component. It has also been shown that higher order harmonic components play a major role in these losses. It has been suggested that this effect may be related to the polar character of water molecules, which are heavily involved in heat dissipation [17]. Apart from this, the samples created using XLPE insulation were aged at 80 °C for 90 h and breakdown strength measurements were made with voltage that has harmonic distortion. In the study where life of cable samples is compared for harmonic and non-harmonic situations, it was emphasized that influence of harmonic should be taken into account in the design phase of insulation systems [18, 19]. In another study, the errors caused by the voltage distorted by harmonic orders in dielectric losses evaluated at operating frequencies were examined. Based on the measurement results performed on epoxy samples, it has been tried to determine the effects of harmonics. In addition, the error rates on the measurement results of 3rd-5th-7th order harmonic distortion were shared. In addition, breakdown voltage of XLPE and epoxy resin samples is investigated. It has been revealed that harmonics negatively affect the breakdown voltages of insulating materials commonly used in cable systems [20, 21]. In a study conducted in 2021 by Linde, dielectric losses of epoxy polymer (EP) and functionally filled silicon rubber (f-SiR) samples were examined under harmonic distorted voltages and accordingly in terms of heat source density within the material. The results show that epoxy polymer samples behave linearly depending on the electric field strength and therefore allow good predictability of dielectric losses. The f-SiR samples that are examined exhibit a nonlinear behavior when an electric field threshold is exceeded. Direct loss measurements under voltage with harmonic distortion reveal a sharp increase in dielectric loss with increasing electric field strength [22].

Many studies in which overvoltage aging process is performed with 3–4–5 times the rated voltage in different aging processes have contributed to the literature in recent years. In these studies, the changing of the mechanical and dielectric parameters of the cables were investigated [23,24,25,26,27]. As a result of the literature review, it has been revealed that it is critical to examine the effect of overvoltages in grid on power cables under harmonic voltages. For this reason, the dielectric performance of power cables that have been aged with overvoltage should be examined. In light of BS EN 60,071, IEEE 1407 Guide and HD 605 standards, the aging process has been established in line with the laboratory facilities and the sustainability of the tests, taking into account the studies in the literature [28,29,30,31]. In this context, 12/20.8 kV XLPE power cable samples were aged using 60 kV overvoltage (5·U0) at Yıldız Technical University High Voltage Laboratory. Dielectric parameter measurements were performed after each aging cycle. The dielectric parameters (PK, tanδ and C) of the aged cable samples were measured. By using OMICRON CPC100/CP-TD1 measuring device, the effects of harmonics with different measurement voltages have been examined. The performance of aged cables is analyzed under harmonic voltages and the results are presented. The disruptive effects created by harmonics have been revealed.

2 Theory of study

In this section, the relationship between theoretical knowledge and measurements is emphasized. First, harmonic distortion has defined. Afterward, theoretical calculations about the effect of harmonic distortion on dielectric parameters of cable are specified.

2.1 Harmonic distortion

Today, harmonics, whose negative effects are increasing in power systems, are defined as periodic waveform components of the grid current and voltage at multiples of the fundamental frequency. Harmonics distort current and voltage waveforms in distribution systems. The main harmonic sources are listed as devices using semiconductor elements, arc furnaces, welding machines, converters, drivers, lighting elements working with the gas discharge principle, etc. They cause problems such as waveform distortion, voltage drop, control and measurement errors, malfunctioning of elements, loss, heating, insulation stress and shortening of life in the systems they are in [32]. In power systems, you can see the instantaneous values of voltage and current without harmonic components in Eqs. 1 and 2. Equation 3 describes ω which depends on the grid frequency.

$$v\left(t\right)=\sqrt{2}\bullet V\bullet \mathrm{sin}\left(\omega t+\varphi \right)$$
(1)
$$i\left(t\right)=\sqrt{2}\bullet I\bullet \mathrm{sin}\left(\omega t+\delta \right)$$
(2)
$$\omega =2\bullet \pi \bullet f$$
(3)

Here, "V" is the effective voltage value (V), “I” is effective value of current (A), "φ" and “δ” are the phase angle (°), "f" is the frequency of distribution system (Hz). Although many diagnostic and testing methods are available for the examination of an electrical insulating material, the effect of harmonics is often neglected. However, insulating materials are also challenged by harmonic components in practice and their dielectric properties can change at different frequency values. Harmonics have disruptive effect on voltage and current as you can see in Eqs. 4 and 5.

$$v\left(t\right)=\sqrt{2}\bullet {V}_{1}\bullet \mathrm{sin}\left(\omega t+{\varphi }_{1}\right)+\sqrt{2}\bullet {V}_{3}\bullet \mathrm{sin}\left(3\omega t+{\varphi }_{3}\right)+\dots +\sqrt{2}\bullet {V}_{i}\bullet \mathrm{sin}\left(i\omega t+{\varphi }_{i}\right)$$
(4)
$$i\left(t\right)=\sqrt{2}\bullet {I}_{1}\bullet \mathrm{sin}\left(\omega t+{\delta }_{1}\right)+\sqrt{2}\bullet {I}_{3}\bullet \mathrm{sin}\left(3\omega t+{\delta }_{3}\right)+\dots +\sqrt{2}\bullet {I}_{i}\bullet \mathrm{sin}\left(i\omega t+{\delta }_{i}\right)$$
(5)

Here, “V1” is effective value of voltage at mains frequency (V), “i” is harmonic order, “Vi” is effective value of voltage at harmonic frequency of the order i (V),, “I1” is effective value of current at mains frequency (A), “Ii” is effective value of current at harmonic frequency of the order i (A). Therefore, the performance of insulating materials at different harmonic contents should be investigated and this performance should be taken into account when choosing materials. The main quantities used in the determination of harmonic limits are defined as total harmonic distortion (THD) and total demand distortion (TDD) in the relevant standards and regulations [33, 34]. THD of a voltage waveform with harmonic content is expressed by Eq. 6 below. In addition, TDD associated with the current is given in Eq. 7 [32].

$$\%\mathrm{THD}=\frac{\sqrt{\sum_{i=2}^{n}{V}_{i}^{2}}}{{V}_{1}}\bullet 100$$
(6)
$$\%\mathrm{TDD}=\frac{\sqrt{\sum_{i=2}^{n}{I}_{i}^{2}}}{{I}_{L}}\bullet 100$$
(7)

Here, IL is maximum demand load current at fundamental frequency component and “n” is content of highest harmonic component in the distribution system (it is recommended to take 50) [33].

2.2 Effect of harmonics on dielectric parameters of power cable

Insulation materials do not actually behave ideally and pass a small amount of current through them. As a result of the current flowing on the insulation material, active power losses occur and turn into heat energy. In the studies in the literature, it is seen that the dielectric parameters are examined by parallel modeling in the investigations on underground cables. In this context, theoretical information and formulations about the parallel equivalent circuit model are shared in this section [2, 6, 11]. In this case, the equivalent circuit of insulating material containing parallel resistor and capacitor can be modeled as shown in Fig. 1 [35, 36].

Fig. 1
figure 1

Equivalent circuit and phasor diagram of insulating material

Here, R (Ω) is the resistance representing dielectric losses, C (F) is the capacitance of insulation, U (V) is the voltage applied, IR (A) is the current causing dielectric losses, IC (A) is the current flowing through C, I (A) is the total current flows through insulation and δ (º) is the phase angle between IC and I. Using parallel equivalent circuit parameters, dissipation factor (tan δ) and dielectric losses (PK) can be calculated as given in Eq. 8 and Eq. 9, respectively [35].

$$ {\text{Tan}} \delta = \frac{{I_{R} }}{{I_{C} }} = \frac{\frac{U}{R}}{U \cdot \omega \cdot C} = \frac{1}{\omega \cdot R \cdot C} $$
(8)
$$ P_{k} = \omega \cdot C \cdot U^{2} \cdot {\text{Tan}} \delta $$
(9)

However, if there is harmonic content in the system, harmonic components should also be added to tanδ and dielectric loss calculation. Calculations of the power loss (PK) and tanδ parameters belong to each harmonic component are shown in Eqs. 10 and 11. Here, i is harmonic order.

$$ {\text{Tan}} \delta = \frac{{I_{R} }}{{I_{C} }} = \frac{{\frac{{U_{i} }}{R}}}{{U_{i} \cdot i \cdot \omega \cdot C}} = \frac{1}{i \cdot \omega \cdot R \cdot C} $$
(10)
$$ P_{Ki} = i \cdot \omega \cdot C \cdot U_{i}^{2} \cdot {\text{Tan}} \delta $$
(11)

Another dielectric loss element in insulating materials is polarization. When an alternating electric field is applied to the material, the charge dipoles change direction every half cycle and move in the opposite direction. The frequency of this movement is determined by the frequency of the applied voltage and the losses caused by infiltration during the operation are called polarization losses. After a threshold frequency value, at very high frequencies where the voltage half-wave lasts for a very short time, the dipoles cannot follow the electric field and cannot change their position with respect to the field. In other words, with the frequency, polarization losses increase up to a point and decrease after a point [35].

3 Experimental setup

In this section, detailed information about the preparation of the cable samples, the properties of the aging process and the measurement system have shared in the experimental studies carried out in High Voltage Laboratory of Yıldız Technical University. In the experimental study, cable samples with 12/20.8 kV rated voltage had used. Detailed information on the parameters of the cable samples have stated in Table 1.

Table 1 Parameters of cable samples

Considering the laboratory facilities and the sustainability of the tests, the samples has aged with overvoltage by 15 min intervals, five times the rated voltage (5·U0) using the test set-up given in Fig. 2. 5·U0 overvoltage at 50 Hz frequency was applied to the cable insulation with the help of a variac connected to the primary of the 220 V/100 kV, 10 kVA high voltage test transformer. In order to ensure measurement consistency and reliability, three samples were prepared from the specified cable and overvoltage aging process was performed for each sample. Laboratory test setup prepared for aging and dielectric measurements are shown in Figs. 2 and 3.

Fig. 2
figure 2

Schematic representation of experimental test set-up used for overvoltage aging

Fig. 3
figure 3

Laboratory test set-up

Before starting the aging process, dielectric parameters of three unaged cable samples had been measured and thereafter, dissipation factor (tanδ), capacitance (Cp), dielectric losses (PK) and resistance (Rp) had been measured after each 15 min aging cycle. As seen in Fig. 3, dielectric measurements were carried out by Omicron CPC100/CP-TD1 device during all cycles of aging. Measurement sensitivities of the device are shown in Table 2 [36]. Here, Ix defines current during capacitance measurement.

Table 2 CPC100/ CP-TD1 measuring sensitivity

The high voltage probe of the device is connected to the cable conductor and the measurement probe to the cable shield. The device can measure with a frequency of 50–400 Hz and a range of 2–12 kV. Thus, changes of dielectric parameters at different frequencies (Hz) and voltages (kV) could examined and the working range with the greatest change was determined. For this, measurements in each cycle were carried out separately at 2, 4, 6, 8, 10 and 12 kV. 50, 100, 150, 200, 250, 300, 350 and 400 Hz are used as the measurement frequency for each of these voltages. The effects of frequency and voltage changes were investigated by obtaining Rp, tanδ, Cp and PK measurement results in 2–12 kV and 50–400 Hz intervals with 2 kV and 50 Hz steps. Electrical parameters (tanδ, Pk, Cp and Rp) of cable insulation are related to the test temperature. For this reason, laboratory ambient temperature is recorded during the measurements as 25 ± 2 °C.

4 Measurement results

In this section, the measurement results of dielectric parameters made at different voltages and frequencies are presented depending on the number of aging cycles. The measurement results have been evaluated under a separate heading for each dielectric parameter, about PK, tanδ, Cp and Rp by taking the average of cable samples.

4.1 Dielectric losses (PK)

PK measurement results and data were analyzed depending on frequency and voltage to examine the effect of aging in cables. As can be seen in Fig. 4, it is seen that a cable sample with 12 kV rated voltage, which is aged with overvoltage, has increased by 10% in the PK increase since the first aging. The negative effects of overvoltage on the cable have continued throughout 80 aging process. The data tables contain all frequency data of the cable sample at rated voltage and all voltage data at rated frequency.

Fig. 4
figure 4

PK measurements results due to aging: a at 12 kV, b at 50 Hz

Figure 4a shows the results of PK measurements made at a voltage of 12 kV in the frequency range 50–400 Hz. When the measurements made before the aging process were compared with the measurements after the 80th aging cycle, an increase of 181.4% at 50 Hz, 150% at 100 Hz, 132% at 150 Hz, 118% at 200 Hz, and 105% at 250 Hz. This ratio was observed as 91.5% at 300 Hz, 78.5% at 350 Hz and 67.5% at 400 Hz. It has been revealed that the PK values increasing as the Watt value with the increase in frequency exhibit different behaviors as the percentage increase amount. All measurement data, according to frequency, are presented in detail in Table 3, with 10 aging cycles each. Figure 4b shows the results of PK measurements made at a frequency of 50 Hz in the voltage range of 2–12 kV. When the measurements made in the 80th aging cycle are compared according to the cable condition before aging, 98.4% at 2 kV voltage, 130% at 4 kV voltage, 146.6% at 6 kV voltage, 160.6% at 8 kV voltage, 169.5% at 10 kV voltage, 181.4% at 12 kV voltage, rate increased. It has been observed that the PK in the cable increase with the increase in the measuring voltage. All measurement data, according to voltage, are presented in detail in Table 4.

Table 3 PK (mW) measurement data for changing frequency at 12 kV voltage
Table 4 PK (mW) measurement data for changing voltage at 50 Hz frequency

In the pre-aging measurements in Table 3, according to the value of the PK value at 50 Hz; 56.2% at 100 Hz, 104% at 150 Hz, 146.3% at 200 Hz, 186.5% at 250 Hz, 228.7% at 300 Hz, 271.4% at 350 Hz, and 400 Hz It was observed that it increased by 321.3%. After 80 aging processes, the increase rates for 100–150–200–250–300–350–400 Hz frequency values changed as 38.8%–68.4%–90.8%–108.5%–123.8%–135.7 –150.9%, respectively. When the pre-aging measurements in Table 4 are examined, according to the value of PK at 2 kV voltage; it is seen that it increases by 819.3% at 6 kV and by 3432.5% at 12 kV. After 80 aging processes, the increase rates for 6 kV and 12 kV voltage values changed as 1042.7–4909.7%, respectively.

4.2 Dissipation factor (tanδ)

In this section, tanδ measurement results and data, which allow us to evaluate the insulation quality of the cable, are examined depending on frequency and voltage, in order to examine the negative effect of overvoltage on XLPE cables. In Fig. 5, which is formed due to aging; Fig. 5a shows the results of tanδ measurements made at 12 kV in the frequency range of 50–400 Hz, and Fig. 5b shows the measurement results at 50 Hz in the voltage range of 2–12 kV.

Fig. 5
figure 5

Tanδ measurements results due to aging: a at 12 kV, b at 50 Hz

When the measurement results were examined, it was observed that the increase in tanδ value at 50–400 Hz measurement frequency as a result of 80 aging processes was 180%—149%—132%—118%—105%—91%—78%—67%, respectively. It is seen that as the number of aging cycles increases, tanδ value increases, but as the frequency increases, the rate of increase in the measurement results decreases. This situation indicates that measurements made at different frequencies reveal the harmonic effect and frequency-dependent changes should be examined in detail. The data of the measurement results are shared in Table 5, including 10 aging cycles in the frequency range of 50–400 Hz. In Fig. 5b; the rate of increase in tanδ measured between 2 and 12 kV after the 80th aging cycle was 98% at 2 kV, 129% at 4 kV, 146% at 6 kV, 161% at 8 kV, at 10 kV 171.2% and 180.2% at 12 kV. All measurement data, according to voltage, are presented in detail in Table 6, with 10 aging cycles. In this context, it was observed that tanδ and PK values showed similar characteristics.

Table 5 Tanδ measurement data for changing frequency at 12 kV voltage
Table 6 Tanδ Measurement Data for Changing Voltage at 50 Hz Frequency

In the pre-aging measurements in Table 5, according to the value of tanδ at 50 Hz; 21.7% at 100 Hz, 31.8% at 150 Hz, 38.2% at 200 Hz, 42.4% at 250 Hz, 44.9% at 300 Hz, 46.6% at 350 Hz, and 400 Hz It is seen that it decreased by 47%. After 80 aging processes, the decrease rates for 100–150–200–250–300–350–400 Hz frequency values changed as 30.4%-43.6%-52%-57.9%-62.4%-66%-68.3%, respectively.

When the pre-aging measurements in Table 6 are examined, according to the tanδ value at 2 kV voltage; it is seen that it changes by 2% at 6 kV and 12 kV. In the measurements made after the 80 aging process, the tanδ value increased by 26.6%–38.5% for the 6 kV and 12 kV voltage values, respectively.

4.3 Cable capacitance (C p)

The measurement results of the Cp value, which has a very important place in the reactive power balance and allows us to examine the capacitive behavior of cables due to aging, depending on voltage and frequency are presented in Fig. 6. The data of the measurement results are shared in Table 7, including 10 aging cycles in the frequency range of 50–400 Hz and measurement data, according to voltage, are presented in detail in Table 8.

Fig. 6
figure 6

Cp measurements results due to aging: a at 12 kV, b at 50 Hz

Table 7 Cp (pF) measurement data for changing frequency at 12 kV voltage
Table 8 Cp (pF) measurement data for changing voltage at 50 Hz frequency

When the data of the measurement results were examined, it was shown that the Cp value did not change depending on aging. This is observed in all variations with measuring frequency and measuring voltage. In this context, the negligibility of the changes in the Cp value is among the results obtained.

When the measurement results of Cp are examined, it is seen that the changes in Cp values are between 0.4 and 1% after all aging cycles. Considering that the measured size is on the pico level, it becomes evident that these rates of change can be neglected. It has been observed that the Cp value behaves independently of the measurement voltage and measurement frequency.

4.4 Resistance (R p)

In this section, resistance (Rp) value measurement results from cable parameters are shared. When the measurement results of Rp are examined, it has been observed that the Rp value showed inversely behavior with the PK value as expected.

Figure 7a shows the results of Rp measurements made at a voltage of 12 kV in the frequency range 50–400 Hz. When the measurements made before the aging process were compared with the measurements after the 80th aging cycle, a decrease of 90.3% at 50 Hz, 86.5% at 100 Hz, 83.6% at 150 Hz, 79.6% at 200 Hz, and 75.2% at 250 Hz. This ratio was observed as 72.9% at 300 Hz, 70.7% at 350 Hz and 65.9% at 400 Hz. It has been revealed that the Rp values decreasing as the MΩ value with the decrease in frequency exhibit different behaviors as the percentage decrease amount. All measurement data, according to frequency, are presented in detail in Table 9, with 10 aging cycles each.

Fig. 7
figure 7

Rp measurements results due to aging: a at 12 kV, b at 50 Hz

Figure 7b shows the results of Rp measurements made at a frequency of 50 Hz in the voltage range of 2–12 kV. When the measurements made in the 80th aging cycle are compared according to the cable condition before aging, 96.5% at 2 kV voltage, 96.8% at 4 kV voltage, 96.9% at 6 kV voltage, 95.1% at 8 kV voltage, 92.4% at 10 kV voltage, 90.3% at 12 kV voltage, rate decreased.

The data of the measurement results are shared in Table 9, including 10 aging cycles in the frequency range of 50–400 Hz and measurement data, according to voltage, are presented in detail in Table 10. Considering Eq. 10 and 11, it is clearly seen that the changes in Rp values are complementary to the measurement results. In the pre-aging measurements in Table 9, according to the value of Rp at 50 Hz; it is seen that it decreased by 47.9% at 100 Hz, 64.6% at 150 Hz, 75% at 200 Hz, 81.2% at 250 Hz, 84% at 300 Hz, 86% at 350 Hz, and 400 Hz, 88.6%. After 80 aging processes, the decrease rates for 100–150–200–250–300–350–400 Hz frequency values changed as 27.8%–40.4%–47.5%–52%–55.3%–57.6%–60.1%, respectively. When the pre-aging measurements in Table 10 are examined, according to the value of Rp at 2 kV voltage; it is seen that it increased by 11.2% at 6 kV and by 74.1% at 12 kV. After 80 aging processes, the increase rates for 6 kV and 12 kV voltage values changed as 21.4%–28.3%, respectively.

Table 9 Rp (MΩ) Measurement Data for Changing Frequency at 12 kV Voltage
Table 10 Rp (MΩ) Measurement Data for Changing Voltage at 50 Hz Frequency

It is seen that the resistance value decreases with increasing frequency, and the current increases with increasing measuring voltage, so the dielectric loss values, which are directly proportional to the square of the current, increase. It has been determined that the dielectric performance is dosed by affecting the cable impedance due to harmonic orders. The reason for this increase in the beginning phase of the aging process is that the bonds between PE molecules are exposed to electrical stress, which leads to them becoming stretched, and results in dielectric losses. As the frequency is increased, the vibrational movements due to the electric field on atomic and molecular basis also increase [3, 26, 37].

5 Discussion

In this section, in order to examine the behavior of measurement results of the pre-aging and 80th aging cycles, the gradient of data is specified in figures created depending on the frequency and voltage. In addition, evaluations were made on data of 10 aging cycles and it was interpreted which harmonic component had more negative effects on cable at which voltage.

5.1 Dielectric losses (PK)

In Fig. 8, PK measurement results for pre-aging and post-80 aging are shared. Figure 8a is frequency dependent at 12 kV measuring voltage, while Fig. 8b shows the data in voltage dependent form at 50 Hz frequency.

Fig. 8
figure 8

Measurements results of PK: a due to frequency, b due to voltage

While the gradient of the frequency-dependent measurement data was calculated as 2.1704 before aging, this value increased to 2.8159 after the 80th aging. In this context, it reveals that the gradient of the PK value increases at different frequency values and that the harmonic components affect the aging of the cable. Although the gradient of the pre-aging data was 23.7291 in the PK value examined depending on the stress, it was found that this value was 66.9056 after 80 aging cycles. Thus, the negative effect of voltage on PK is clearly understood. The increasing gradient value has enabled us to understand the negative effect of the change in the effective value of the voltage on the cable due to the effect of harmonic components.

In frequency-dependent analysis of measurement data, as the number of aging cycles increases at the fundamental frequency (50 Hz), the PK value occurring in the cable also increases. The amount of increase was determined as 95.4%–128%–143.3%–147.1%–156.9%–166.8%–175.8% and 181.4% for cycles from 10 to 80, respectively. In this context, the amount of increase between aging cycles is also very important. For example, while the PK value increased by 128% after 20 cycles, there was an increase of 19.1% in the 40th aging cycle compared to the 20th aging. At the end of 60 cycles, an increase of 19.7% occurred compared to the 40th cycle, while an increase of 14.6% was observed in the 80th aging cycle compared to the 60th cycle. When this situation is examined in terms of harmonic component frequencies, it is revealed that the 3rd (150 Hz) harmonic component produces the highest increase in the data analyzed every 20 cycles comparatively. The increase in PK at 150 Hz frequency was 94.6% at the end of the first 20 aging. The 3rd component harmonic is followed by the 5th (250 Hz) and 7th (350 Hz) harmonic components, respectively. When it comes to the 40th aging cycle, the 3rd, 5th and 7th order harmonics showed a similar increase compared to the 20th aging, and this rate is 13%. At the end of 80 aging cycles, it was found that the 3rd harmonic component was the factor that most affected the PK value.

When the voltage-dependent evaluation of the PK data was made, it was noticed that the PK value exhibited similar characteristics at all voltage values until the 60th aging cycle. For example, while it varies between 107 and 122% in the 20th cycle, it contains very close values between 20 and 30% in the 40th cycle. After the 60th cycle, it has been revealed that increasing voltage value is an important factor in the increase in PK.

5.2 Dissipation factor (tanδ)

In Fig. 9, the change in frequency and voltage domain of the tanδ measurement results pre-aging and the 80th aging cycle are given and their behavior with gradient lines has been examined. The gradient of the frequency-dependent tanδ value was determined as −7.29e−06 before aging. The negative gradient value proved its decreasing behavior. At the end of 80th aging cycle, the gradient on the frequency domain has reached the value −29.56e−06. Thus, it was revealed that the aging effect increased the amount of decrease. In addition, it has been observed that the effect of aging is not only at the rated frequency, but also the presence of a negative effect on harmonic frequencies. When the voltage dependent tanδ value is examined, it is determined that the gradient is −1.75e−05. Because of this value is negative, it revealed the decrease in the value of tanδ due to the voltage. At the end of 80th aging cycle, this value reached 44.07e−05. It has been observed that with the increase in the voltage domain, the amount of increase also increased. The display of this behavior in the rated frequency depending on the voltage is an indication that more negative effects will occur as a result of the increase in the effective value of the voltage with the contribution of harmonic components.

Fig. 9
figure 9

Measurements results of tanδ: a due to frequency, b due to voltage

As stated in Eq. 8, tanδ value decreases as the frequency increases. This situation is clearly seen when the first 20 aging cycles are examined in the measurement results. However, the rate of decrease in the tanδ value after the 20th cycle is around 1%. After the 40th aging cycle, the most decrease occurs in the 5th and 7th harmonic components, and this rate is 2.7%. When the 80th cycle is reached, it is seen that the 3rd order harmonic component causes the highest decrease with 1.5%. This ratio is 0.7% for the 5th harmonic and 0.6% for the 7th harmonic. As a result, it has been revealed that 3–5–7 harmonic components have a negative effect on the tanδ value.

In the voltage-dependent investigations, it was observed that tanδ value exhibited a very similar behavior to the PK and the increase–decrease amounts were very close to each other. There are differences between 0.5 and 0.8% of change rates. In this context, just like the PK value, it turns out that the voltage increase is an effective factor on tanδ.

5.3 Cable capacitance (C p)

In Fig. 10, the measurement results of the Cp value depending on the voltage and frequency are shared.

Fig. 10
figure 10

Measurements results of Cp: a due to frequency, b due to voltage

In frequency-based analysis, the gradient of Cp change before aging is −0.0090. After 80 aging cycles, the gradient value was calculated as −0.0205. It was observed that the Cp value changed inversely with the frequency and the Cp value decreased as the frequency increased. The fact that the measurement data is in the pico order indicates that the amount of change can be neglected. When the voltage-dependent Cp value was examined, the calculated gradient values were calculated as 0.0871 and 0.3543 for pre-aging and after 80th aging, respectively. In this context, it was observed that the Cp value increased with increasing voltage. Due to the small amount of increase, it was accepted that it could be ignored.

In the analysis of the changes in Cp value depending on aging in voltage and frequency-dependent investigations, the rate of change was determined as 1% at most. No significant results were obtained in the comparison of the measurements made at different frequencies and the examination of the measurements made at different voltages. Considering that the measured Cp value is in the pico order, it is concluded that the change amounts can be neglected and the harmonic components do not affect the Cp value even after the aging process.

5.4 Resistance (R p)

In Fig. 11, the change in frequency and voltage domain of the Rp measurement results pre-aging and the 80th aging cycle are given and their behavior with gradient lines has been examined.

Fig. 11
figure 11

Measurements results of Rp: a due to frequency, b due to voltage

The gradient of the frequency-dependent Rp value was determined as -4.5026 before aging. The negative gradient value proved its decreasing behavior. At the end of 80th aging cycle, the gradient on the frequency domain has reached the value −0.3096. Thus, it was revealed that the aging effect decreased the amount of decrease. When the voltage-dependent Rp value is examined, it is determined that the gradient is −695.035. Because of this value is negative, it revealed the decrease in the value of Rp due to the voltage. At the end of 80th aging cycle, this value reached −7.3803.

It is seen that the resistance value decreases with increasing frequency, and the current increases with increasing measuring voltage, so the dielectric loss values, which are directly proportional to the square of the current, increase. It has been determined that the dielectric performance is dosed by affecting the cable impedance due to harmonic orders.

6 Conclusion

In this study, aging process was performed on 12/20.8 kV XLPE power cable samples with 60 kV overvoltage (5·U0) in Yıldız Technical University High Voltage Laboratory. Dielectric parameter measurements were performed after each aging cycle. The dielectric parameters (PK, tanδ, Cp and R) of the aged cable samples were measured. By using OMICRON CPC100/CP-TD1 measuring device, the effects of harmonics with different measurement voltages have been examined. Disruptive effect of harmonics have been revealed by the analyses made by aging cycles.

Evaluation of measurement results can be made from three different perspectives. The first point of view is to examine the effect of aging on the cable according to frequency and voltage. In this case, the conclusion to be drawn from the study is that the effect of overvoltage at the rated voltage and frequency is seen quite clearly. The second point of view is the comparison of measurements made at different frequencies according to the number of aging cycles and the evaluation of according to each other. In this case, it is seen that the 3rd–5th–7th harmonics orders are effective for the tanδ and PK value based on measurement results. The third and last point of view is to investigate the negative effect on the cable as a result of the increase in the effective value of the voltage together with the harmonic components. In this study, it is clearly seen that PK, tanδ and Cp values increase with the voltage value during the measurement of dielectric parameters. However, the rate of increase in the capacity value is considered to be negligible. In this case, the results obtained from this study are stated below as items.

  • The negative effect of overvoltage on underground cables has been proven by the change in dielectric parameters depending on aging.

  • As a result of tanδ measurements, it was observed that the dielectric quality of the cable insulation material deteriorated due to overvoltage.

  • After the 40th aging cycle, the highest decrease in tanδ value occurred in the 5th and 7th harmonic components and this rate was 2.7%. When it comes to the 80th cycle, it is seen that the 3rd order harmonic component causes the highest decrease with 1.5%. As a result, the distortion occurring at the frequency of 150–250–350 Hz has a more negative effect on the tanδ value.

  • The PK formed in the cable insulation material increased due to the overvoltage.

  • The increase in PK at 150 Hz frequency was 94.6% at the end of the first 20 aging. It is revealed that the 3rd (150 Hz) harmonic component produces the highest increase in the data analyzed every 20 cycles comparatively. But, when looking to values of 80th aging cycles, it has been determined that the harmonics of 3–5–7 degrees are factor that most affects the PK value.

  • The effect of frequency and voltage changes on tanδ and PK is quite similar.

  • The Cp value was not affected by the overvoltage aging process.

  • The Cp value was not affected by harmonic components, acting independently of the measurement voltage and frequency.

  • The frequency effect increased with increasing voltage value due to harmonic components.

  • Effects of harmonic orders should not be ignored in the creation of maintenance and replacement activities about power cables.

The study showed that more attention should be paid to the effects of harmonics in distribution systems containing harmonics of 3–5–7th order. As a result, it is necessary to accept that the dielectric parameters of the equipment in the power system change due to harmonic components and to observe this change closely. In this context, it is emphasized that the insulation quality of the equipment used in power systems should be evaluated by including harmonic components. In this context, increasing effects of harmonic order due to aging should be considered in the evaluation of economic losses in power systems.