Abstract
Recently, microgrid has been emerged with an optimum solution for control and operation of distributed generations (DGs) in large power system. The islanding detection is one of the critical issues in grid connected microgrid. The hybrid islanding detection technique (IDT) uses the advantages of both passive and active techniques. Among passive techniques, the voltage unbalance (VU) IDT is the most effective technique and can be implemented comfortably for systems with load fluctuations. In this paper, a novel hybrid IDT has been developed using VU and rate of change of frequency (ROCOF) for synchronous generators based microgrid system. The proposed hybrid technique is compared with existing hybrid technique based on VU and frequency set point (FSP). In contrast to the current hybrid technique (0.21 s), the proposed technique detects the islanding in 22 ms, according to simulation results. Moreover, the proposed hybrid IDT can be applied for Inverter based DGs such as Solar Photovoltaic, wind energy, etc. in microgrid. The simulation results are obtained using MATLAB/Simulink 2019b.
Access provided by Autonomous University of Puebla. Download conference paper PDF
Similar content being viewed by others
Keywords
1 Introduction
As per IEEE 1547 standard [1], “An island is defined as a condition in which a portion of an area electric power system (EPS) is energized solely by one or more local EPSs through the associated PCCs while that portion of the area EPS is electrically separated from the rest of the area EPS”. The islanding phenomenon can be categorized into unintentional and intentional islanding. Unintentional islanding can be hazardous to construction personnel operating on the main grid and can also result in utility equipment destruction. In literature, various IDTs have been proposed and implemented to detect unintentional islanding. The IDTs are generally classified into remote and local techniques. The implementation of local techniques is performed on distributed generation (DG) side. Further, the local IDTs are categorized into active, passive, and hybrid. The hybrid IDTs merge the advantages of active and passive IDTs or two passive/active IDTs and hence more efficient. A detail review of IDTs has been presented in [2,3,4]. In [5,6,7], the phase locked loop (PLL) is used to calculate ROCOF at point of common coupling (PCC). The ROCOF based IDT is sensitive to load fluctuations and hence the setting of threshold becomes difficult. For islanding detection, the VU based passive IDT utilizes the measurement of negative (NSV) and positive (PSV) sequence of voltage. This passive technique suffers from the disadvantages such as difficult to set threshold, unresponsive to network disturbances, and undesired harmonics in negative sequence component [8]. Recently, the hybridization of two IDTs has been utilized to improve islanding detection time, NDZ, etc. [9]. The hybrid technique using ROCOF over reactive power and d-axis current injection has been utilized to improve islanding detection time. This hybrid technique is best suited for mixed DG environment [10]. The hybrid techniques i.e., Q-f droop and reactive power variations (RPV) [11]; power control loop and signal processing [12]; VU and voltage phase angle (VPA) [13]; wavelet transform and artificial neural network (ANN) [14]; voltage and real power shift [15]; Sandia frequency shift and ROCOF [16]; “wavelet packet transform and probabilistic neural network” [17]; “adaptive neuro-fuzzy inference system” [18]; Voltage unbalance factor [20]; “rate of change of reactive power and Rate of change of active power” [21]; Pattern-recognition method [22]; VU/THD and bilateral reactive power variation [23]; Discrete fractional Fourier transform [24] have been proposed and implemented by various researchers.
The passive technique has several disadvantages such as large NDZ, failed to detect balance islanding and difficult to implement in multiple DG systems. Moreover, the active techniques have also several disadvantages such as degradation in power quality, long detection time, and synchronization issues. In this Paper, an improved hybrid IDT is proposed using VU and ROCOF. The two passive methods are combined together due to easy implementation and have negligible influence on power quality and having fast detection time. The following is how the remainder of the paper is organized: The second section delves further into the passive and active strategies employed. The proposed hybrid technique using VU and ROCOF is explained in Sect. 3. Section 4 is on focused simulation results and analysis. At last, the paper is concluded in Sect. 5.
2 Passive Methods
In this section, the passive methods i.e., VU and ROCOF for islanding detection have been reviewed.
2.1 Voltage Unbalance
The DGs mounted in the microgrid can match the load demands if the power grid is isolated. The voltage unbalance can be observed at terminals of DGs. This passive technique identifies the islanding dependent on the VU of three-phase voltages at PCC. In this method, the ratio of NSV to PSV is utilized to identify islanding event. The voltage unbalance at any time t can be determined from the expression given below:
where VNS and VPS represent the NSV and PSV component of voltages at the DG’s output terminal. The detection time is 53 ms. The disadvantage of this technique is that it is influenced by undesirable harmonics when removing the negative sequence portion of voltage, difficult to set the threshold value.
2.2 Rate of Change of Frequency (ROCOF)
In this passive ID, ROCOF i.e., df/dt over a limited cycle at PCC is observed. If the value of df/dt is larger than threshold value, the inverter should cutoff the power output. The islanding detection time is around 24 ms. From the literature, the optimum threshold value for ROCOF technique is found to be 0.3 Hz/sec with 0.7 s islanding detection time. This technique may lead to erroneous results due to load fluctuations and switching. The df/dt can be determined by Eq. (2).
where \(f\left( {t_k } \right)\) represents the frequency at time of the kth sample, \(f\left( {t_k - \Delta t} \right)\) represents the value of determined frequency before the time of the kth segment, i.e., \(t_k - \Delta t\). This method fails to recognize balanced islands. The setting of threshold values is very critical in this technique to distinguish islanding and switching events.
3 Proposed Hybrid IDT
The proposed hybrid IDT consists of the advantages of VU and ROCOF. Figure 1 displays the flow chart for the proposed algorithm. The voltage and frequency at PCC are monitored using this technique. ROCOF (df/dt) and voltage unbalance is determined for each DG. For any disturbance such as switching of loads or islanding, a spike can be observed in VU. Whenever VU spike crosses the threshold value, the df/dt value at PCC is observed for 2 to 50 cycles and sent to the low pass filter (LPF). The aim to use LPF is to remove high frequency transients generated by components of the power system. The islanding case is observed if the ROCOF value still exceeds the threshold value. The maximum permissible VU spike value can be determine from [19].
4 Results and Analysis
The proposed hybrid method has been verified on test system as shown in Fig. 2. A diesel generator of 3 MVA is connected through the main grid via 25 kV/2.4 kV, Y-Δ transformer. Moreover, a 5 MW load is connected at main grid. The short circuit capacity (SCC) of main grid is 1000 MVA. The 1 MW load is connected near diesel generator. The Simulink model of test system is shown in Fig. 3.
The voltage and current profile at PCC before islanding and load changing is shown in Fig. 4. The following disturbances were simulated to study the islanding event. First, at 0.25 s, 0.8 MW load is inserted at PCC (near DG) and 0.9 MW load is inserted at 0.5 s. Further, at t = 1.0 s, main grid is disconnected through circuit breaker. The NSV and PSV at PCC is shown in Fig. 5. The VU spikes are observed at the terminal of DG at load switching and main grid isolation. From Fig. 6, it is observed that VU spikes are low in magnitude during load switching; however at main grid failure, the VU value is 0.04 pu. The frequency and ROCOF variation with respect to time can be observed from Figs. 7 and 8 respectively. It is observed that ROCOF is higher at the event of islanding compared to load switching event. From Fig. 9, it is observed that when VU spikes and df/dt both crosses the set threshold, to disconnect the main grid, a trip signal is sent to the circuit breaker. The islanding detection time is 22 ms, according to the simulation data. However, for the same test system, the islanding detection time for hybrid method using VU and frequency set point was found to be 0.21 s.
The voltage variation at DG terminal and current at PCC are shown in Figs. 10 and 11 respectively. A comparison between discussed IDTs is shown in Table 1. It is observed from Table 1 that the proposed method has lowest islanding detection time compared to other techniques.
5 Conclusion
In this paper, a novel hybrid IDT using VU and ROCOF is presented for diesel generators based microgrid system. The proposed hybrid technique is compared with hybrid IDT based on VU and frequency set point (FSP) given in literature. The suggested hybrid system detects islanding in 22 ms, according to simulation results. Moreover, the islanding detection time for hybrid method using VU and frequency set point was found 0.21 s. This proposed method can also be applied on the inverter based DG systems. The simulation results are obtained using MATLAB/Simulink. In future, the proposed method can be investigated for hybrid microgrid system.
References
IEEE application guide for IEEE Std 1547(TM) (2009) IEEE standard for interconnecting distributed resources with electric power systems. IEEE Std 1547.2–2008, 15, 1–217
Mahat P, Chen Z, Bak-Jensen B (2008) Review of islanding detection methods for distributed generation. In: 3rd international conference on electric utility deregulation and restructuring and power technologies (DRPT). IEEE, pp 2743–2748, Nanjing, China
Khamis A, Shareef H, Bizkevelci E, Khatib T (2013) A review of islanding detection techniques for renewable distributed generation systems. Renew Sust Energ Rev 28:483–493
Kunte RS, Gao W (2008) Comparison and review of islanding detection techniques for distributed energy resources. In: 40th North American power symposium. IEEE, pp 1–8, Calgary, Canada
Guha B, Haddad RJ, Kalaani Y (2015) A passive islanding detection approach for inverter-based distributed generation using rate of change of frequency analysis. In: 1st international conference on power electronics, intelligent control and energy systems (ICPEICES), pp. 1–6, Delhi
Marchesan G, Rossato M, Cardoso G, Mariotto L, De Morais AP (2016) Passive method for distributed generation islanding detection based on oscillation frequency. IEEE Trans Power Del 31(01):138–146
Tzelepis D, Dysko ABooth C (2016) Performance of loss-of-mains detection in multi-generator power islands. In: 13th IET international conference on developments in power system protection (DPSP). IET, pp 1–6, Edinburgh, United Kingdom
Jang SI, Kim KH (2004) An islanding detection method for distributed generations using voltage unbalance and total harmonic distortion of current. IEEE Trans Power Del 19(2):745–752
Bower W, Ropp M (2002) Evaluation of islanding detection methods for photovoltaic utility-interactive power systems. International Energy Agency (IEA), Albuquerque, NM, USA
Nougain V, Prakash S, Mishra S (2018) Hybrid islanding detection method based on ROCOF over reactive power and d-axis current injection. In: 8th India international conference on power electronics (IICPE). IEEE, pp 1–4, Jaipur, India
Raipala O, Mäkinen A, Repo S, Järventausta P (2014) A novel anti-islanding protection method based on the combination of a Q-f droop and RPV. In: IEEE PES innovative smart grid technologies (IEEE), pp 1–6, Europe
Zamani R, Golshan MEH, Alhelou HH, Hatziargyriou N (2019) A novel hybrid islanding detection method using dynamic characteristics of synchronous generator and signal processing technique. Electr Power Syst Res 175:105911
Seyedi M, Taher SA, Ganji B, Guerrero JM (2009) A hybrid islanding detection technique for inverter-based distributed generator units. Int Trans Electr Energy Syst 29(11):1–21
Kumar SA, Subathra MSP, Kumar NM, Malvoni M, Sairamya NJ, George ST, Suviseshamuthu ES, Chopra SS (2020) A novel islanding detection technique for a resilient photovoltaic-based distributed power generation system using a tunable-q wavelet transform and an artificial neural network. Energies 13(16):1–22
Mahat P, Chen Z, Bak-Jensen B (2009) A hybrid islanding detection technique using average rate of voltage change and real power shift. IEEE Trans Power Del 24(2):764–771
Khodaparastan M, Vahedi H, Khazaeli F, Oraee H (2015) A novel hybrid islanding detection method for inverter-based DGs using SFS and ROCOF. IEEE Trans Power Del 32(5):2162–2170
Ahmadipour M, Hizam H, Othman ML, Radzi AMM (2018) An anti-islanding protection technique using a wavelet packet transform and a probabilistic neural network. Energ 11(10):1–31
Hashemi F, Ghadimi N, Sobhani B (2013) Islanding detection for inverter-based DG coupled with using an adaptive neuro-fuzzy inference system. Int J Electr Power Energy Syst 45(1):443–455
Menon V, Nehrir MH (2007) A hybrid islanding detection technique using voltage unbalance and frequency set point. IEEE Trans Power Syst 22(1):442–444
Nayak AM, Mishra M, Pati BB (2020) A Hybrid Islanding Detection Method Considering Voltage Unbalance Factor. international symposium on sustainable energy, signal processing and cyber security (ISSSC). IEEE. Gunupur Odisha, India, pp 1–5
Jhuma UK, Mekhilef S, Mubin M, Ahmad S, Rawa M, Alturki Y (2020) Hybrid islanding detection technique for malaysian power distribution system. In: 5th international conference on computing communication and automation (ICCCA). IEEE, pp 785–790, Greater Noida, India
Chaitanya BK, Yadav A, Pazoki M (2020) Reliable islanding detection scheme for distributed generation based on pattern-recognition. IEEE Trans Ind Informat, pp 1–9
Wang G, Gao F, Liu J, Li Q, Zhao Y (2020) Design consideration and performance analysis of a hybrid islanding detection method combining voltage unbalance/total harmonic distortion and bilateral reactive power variation. CPSS Trans Power Electron Appl 5(1):86–100
Dutta S, Olla S, Sadhu PK (2021) A secured reliable and accurate unplanned island detection method in a renewable energy based microgrid. Int J Eng Sci Technol, 1–14
Author information
Authors and Affiliations
Corresponding author
Editor information
Editors and Affiliations
Rights and permissions
Copyright information
© 2022 The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd.
About this paper
Cite this paper
Singh, S.K., Rawal, M., Rawat, M.S., Gupta, T.N. (2022). A Hybrid Islanding Detection Technique for Synchronous Generator Based Microgrids. In: Gupta, A.R., Roy, N.K., Parida, S.K. (eds) Power Electronics and High Voltage in Smart Grid. Lecture Notes in Electrical Engineering, vol 817. Springer, Singapore. https://doi.org/10.1007/978-981-16-7393-1_31
Download citation
DOI: https://doi.org/10.1007/978-981-16-7393-1_31
Published:
Publisher Name: Springer, Singapore
Print ISBN: 978-981-16-7392-4
Online ISBN: 978-981-16-7393-1
eBook Packages: EnergyEnergy (R0)